U2 Main Turbine Cooling/SS/LO Flashcards

1
Q

What are the trips of the Unit 2 Main turbine that are DIFFERENT than Unit 1?

A

Hardwired:
S tator Cooling Water (10 sec delay)
- Lo Press 28 psig
- Lo Flow 666 gpm
- Hi Temp 95°C (+ 5 sec delay)
T hrust Bearing Wear Abnormal ± 32 mils

PLC:
O il Press (Bearing) < 14.7 psig > 5 seconds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Is there an auto trip for high vibrations trip for the Unit 2 Main Turbine?

A

NO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

When does the U2 Turning gear auto start?

A

1 min after Main Turbine Trip. Does not engage until < 40 RPM

- Engages when Main Turbine speed < 40 rpm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

When does 2-CMO-40 (Exhaust hood spray) open?

A
  • Generator Load < 7.5%
  • Turbine Speed > 900 rpm
  • Manual
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What does the Main Turbine Thrust Bearing do?

A

Limits Axial Movement to prevent stationary and rotating blade contact

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

When does the AC Lube Oil pump supply oil to the U2 Main Turbine?

A

Turbine speed < 1800 rpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When does the AC Lube Oil pump auto start for the U2 Main Turbine?

A

Turbine Trip

- Low Lube Oil # at 16#

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

When do the 2 DC Lube Oil pumps auto start for the U2 Main Turbine?

A
  • Turbine Trip
    -Low pressure of 16 psig

- Low Lube Oil # at 16#

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When do the 2 DC Lube Oil pumps supply oil to the U2 Main Turbine?

A

supplies bearing oil when the Shaft Driven LO Pump or Aux Oil Pump fail

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What does LRV-32, LO supply header # Reg Valve, do?

A
  • Maintains U2 turbine supply header pressure at 24.5 psi by dumping excess pressure back to the lube oil tank
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What do the reheat stop and intercept valves do?

A
  • Both Close on Main Turbine Trip to minimize the potential for overspeed of Main Turbine
  • Intercept valves throttle to limit overspeed on a load rejection to prevent a turbine trip
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How do the SRV-26/27, aux steam supply valves fail on U2?

A

As is

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What does SRV-12 (U2 MS Bypass Header supply to steam seals) do?

A

Keeps HPT Inner Steam Seals 10# > HPT exhaust during normal operation.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What supplies LPT Steam Seals during normal operation?

A
  • HP inner seals supply most of steam for seal stm header after it exits the HPT
  • Can receive some steam from HP and LP Stop and Ctrl valve leakoff,
  • and some aux steam as necessary when HP and LP stop and ctrl valves are backseated
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What supplies Steam Seals during startup, shutdown and low power operation?

A

50# aux steam supplies steam seals

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What dumps excess steam pressure for the steam seals on U2?

A

SRV-25 (Steam Seal Dump Valve) controls pressure and dumps extra steam to 2A/2B Heaters

17
Q

How does SRV-22 (Aux Steam reg supply valve) fail on loss of air?

A

Fails open

18
Q

How does SRV-25 (Seal disch to 2A/B heaters) fail on loss of air?

A

-Fails closed

19
Q

When do the U2 bearing lift pumps auto start?

A

Turbine Trip

20
Q

Where in the Lube Oil Flowstream does the DC Emergency Lube Oil Pump discharge?

A

After the Lube Oil Coolers (bypasses them)

21
Q

What effect will long term operation on the DC Emergency Lube Oil pump have?

A

Higher LO temps

22
Q

The Unit 2 High Pressure Turbine inner steam seal is supplied with Main Steam which normally is controlled ____ psi greater than turbine exhaust pressure.

A

10#

23
Q

How do we prevent the MT from tripping on a Rx trip?

A

Knife switches are opened to allow turbine to stay on grid when Rx is tripped (prevents turbine overspeed)

24
Q

How do you adjust the Gland Steam Condenser vacuum?

A

Adjust the blower suction inlet orifice plate (sliding damper) position

25
Q

What supplies steam during turbine startup?

A
  • Intermediate pressure header
    Aux steam
  • High pressure header
    Main steam
26
Q

If you lose the glad steam condenser fan, what will happen?

A

Steam will leak out turbine and MPF to atmosphere

27
Q

What is the Bases behind T.S. 3.3.1, Reactor Trip from Turbine Trip above P-8?

A
  • Anticipates loss of heat removal
  • Minimizes temperature and pressure transient
  • Auto Oil Stop pressure and Turbine Stop Valve position provides diversity of turbine trip indication
28
Q

What is the different for the stop and control valves going into the HP Turbine between the units?

A

Unit 1 equalization line is between stop and control valves. Unit 2 valves are combined