Equipment Trips Flashcards

1
Q

What are the Diesel Fire Pump Trips?

A
  1. Engine Cranks for 6 15-sec cycles then stop

2. Engine Overspeed 2112 RPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are ALL the EDG Trips?

A

BIG C FLANGE

B earing Temp Hi
I ncomp Start
G enerator Phase Overcurrent
C 02 Actuation
F uel Oil Pressure Low
L ube Oil Pressure Low
A ir Chest Pressure Hi
N eutral Overcurrent
G enerator Phase Diff
E lectronic Overspeed
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the EDG Trips if the EDG is actually needed?

A

GEM

G enerator Phase Diff
E lectronic Overspeed
M anual PB

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the EDG Trips with 250 VDC Unavailable?

A

Worthington

Mech Overspeed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What will Trip a Circ Water Pump?

A

Undervoltage on Associated 4 KV Bus

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What will trip the SFP Pump?

A

Load Cons

Load Shed

Overload / Overcurrent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the CAC Trips?

A

Does NOT Loadshed

Low Oil Pressure
Low NESW Pressure
Overload

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What are the PAC Trips?

A

Loadshed

Load Cons

Overload

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What trips the AS/AX and AFS/AFX Fans?

A

Load Conservation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What are the Heater Drain Pump Trips?

A
  1. Lo-Lo Level in Suction Heater
  2. Turbine Trip
  3. Overload / Overcurrent
  4. Both Suction Valves FULL CLOSED (M HDP only)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

If the Unit Emergency Trip PB is pressed, what is the only DIRECT result?

A

HEAs open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What are the U1 Turbine Trips?

A

ASS MOISTURE COOLL

A MSAC
S I
S team Gen Level Hi-Hi 67%
M anual
O verall HEA
I OPS 110%
S tator Cooling Water (10 sec Delay)
   Lo Press 13 #
   Lo Flow 195 gpm
   Hi Temp 95*C (+ 5 sec delay)
T hurst Bearing Wear Abnormal
U nit HEA
R eactor Trip
E mergence Trip
C ondenser Vac
O verspeed 107%
Oil Pressure < 8 psig > 5 sec
L o EHC HDR Press
L o Trip HDR Press
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What are the U2 Turbine Trips?

A

ASS MOISTURE COOLL

A MSAC
S I
S team Gen Level Hi-Hi 67%
M anual
O verall HEA
I OPS 110%
S tator Cooling Water (10 sec Delay)
   Lo Press 28 #
   Lo Flow 666 gpm
   Hi Temp 95*C (+ 5 sec delay)
T hurst Bearing Wear Abnormal
U nit HEA
R eactor Trip
E mergence Trip
C ondenser Vac
O verspeed 107%
Oil Pressure < 14.7 psig > 5 sec
L o EHC HDR Press
L o Trip HDR Press
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the Low Oil Pressure Turbine Trip for U1?

A

Oil Pressure < 8 psig > 5 sec

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the Low Oil Pressure Turbine Trip for U2?

A

Oil Pressure < 14.7 psig > 5 sec

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What are the MFP Trips?

A

MR. SHIT COOLL

M anual
R eactor Trip
S I
H i-Hi SG Level (P-14)
I OPS (110%)
T hurst Bearing Wear
C ondenser Vac Low
O il Pressure Low
O verspeed 107%
L ow Suction Pressure
L ow Trip Hdr Pressure
17
Q

RHR Pump will trip on low-low level of what?

A

9% Level in RWST IF RHR suction valves (IMO-310 and 320) are not fully closed.

18
Q

What would cause the Unit specific Release Valve RRV-287 or RRV-286 to Trip?

A

Loss of all Circ Water Pumps for your Unit

19
Q

What would cause the Liquid Release Valve RRV-285 to Trip?

A

RRS-1001 Hi Rad

RRS-1000 Failure

High/Low Rad Monitor Sample Flow on RFS-1010

20
Q

What would Trip off a Monitor Tank Pump?

A

If in RELEASE:

RRS-1001 Hi Rad
RRS-1000 Failure
High/Low Rad Monitor Sample Flow on FRS-1010

When proper tank selected:
Low Monitor Tank Level

21
Q

What will trip the WGC?

A

Low Moisture Sep Pressure - 25#

Load Cons

< 0.5 #

22
Q

What will close the inlet to the I/S GDT ?

A

Hi-Hi Oxygen at 2.7% from AOM.

100# on I/S Tank

Swaps to Standby GDT if 1 is selected

23
Q

What will trip closed the Waste Gas Release Flow Control Valve RRV-306?

A

Loss of both U1 Aux Exhauste Fans

Hi Rad on U1 or U2 Vent Stack Rad Monitors

24
Q

What will trip the Rod Drive MG Supply Breakers?

A

Load Cons

Overcurrent

25
Q

What will trip the Rod Drive MG Output Breakers?

A

Overvoltage
Overcurrent
Reverse Current
Supply Breaker Open