EDG AUX Flashcards

1
Q

What happens to the EDG ventilation system when outside air temp is < 45°?

A

Tempering dampers open to stop drawing in cold outside air

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

When do the EDG Supply and Exhaust fans stop?

A
  • Stop 30 min after EDG shutdown
  • 70°F Room Temp
  • On acutation of CO2
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How often does the gear lube oil ctrl valve open while the EDG is in stby?

A

Solenoid opens every 4 hours for 2 min

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

When do the gear lube oil ctrl valves open when the EDG is started?

A

Immediately on the start of the EDG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When do the gear lube oil ctrl valves close after the EDG is shutdown?

A

8 min after an EDG is shutdown/tripped

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What provides fuel to the EDG while its running?

A

Shaft Driven Fuel Oil Pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When is the field flash disabled?

A

80% speed during a fast start

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What must the Throttle Control Cylinder have to be able to open?

A

Ctrl Air

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When does the supply fan for the EDG Auto start?

A
  • 20 Sec after an EDG start
  • 95°F Room Temp
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When does the exhaust fan for the EDG Auto start?

A
  • EDG start
  • 95°F Room Temp
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the minimum required level of each Fuel Oil Storage Tank?

A

≥ 46,000 gal to supply 1 EDG for 7 days at full load per LCO 3.8.3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the minimum level in the Fuel Oil Day Tank per SR 3.8.1.4?

A

101.4 gal

(15 minutes worth run time at full load)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What are the designed temp bases for the EDG room?

A

< 104°F in standby
< 130°F running

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

When does the Stby EDG JW Pump auto start?

A

Low # (16 psig)

10 sec time delay

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What temp does the EDG Aux Jacket Water Heater maintain the EDG Jacket Water at?

A

145°F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Unit 1 is at 100% power. A relief valve has failed open on 1AB Emergency Diesel Generator Starting Air Receiver #1. The associated starting air compressor has tripped off. What is the response of 1AB Emergency DieselGenerator if a start signal occurs before any operator action? The EDG will …

A

start in the normal time from #2 Starting Air Receiver but only one starting air valve will supply all of the cylinders with starting air pressure.

17
Q

Upon a loss of control air, EDG air aftercooler regulating valves fail to what position?

A

Fails to allow full flow through the EDG air aftercooler

18
Q

What is the makeup water to the EDG JW surge tank?

A

Demin water

19
Q

What is the Emergency Backup source of water to the EDG Jacket Water System?

A

ESW

20
Q

Can the before and after pump supply the EDG while its running if the Shaft Driven oil Pump fails?

A

No. The B and A Pump capacity is insufficient for continued EDG operation.

21
Q

EDG Valve Gear Lube Oil valves fail how on a loss of Ctrl Pwr?

A

Open

22
Q

How many starting air valves do you need to start a diesel?

A

only 1 starting air valve is needed and 1 receiver

Starting air lines and receivers are x-tied

23
Q

Do both starting air valves open on a diesel start?

A

Yes

24
Q

What is the cooling supply to the EDG Woodward Electronic Governor?

A

Jacket Water

25
Q

Are the fuel oil transfer pumps designed for a staggered start based on day tank level?

A

NO! Both pumps are designed to start at the same level.

26
Q

What auxiliary EDG items are supported/cooled by ESW?

A

Jacket Water
Lube Oil
Intake Air After Coolers
Emergency Makeup to Jacket Water

27
Q

What is the purpose of the before and after pump?

A

Maintains positive oil pressure until Engine-Driven takes over operation

28
Q

Is EDG Operability affected by a Failure of Shaft Driven LO Pump?

A

YES! INOPERABLE