Tech Spec #s Flashcards

1
Q

What’s the TS Level for the FP Water Storage Tanks?

A

565,000 gal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the TS Level for the Diesel Driven Fire Pump Fuel Oil Storage Tanks?

A

160 gals for 8 hrs of Operation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the TS Level for the Condensate Storage Tank?

A

182,000 gals to maintain plant in hot standby for 9 hrs on PORVs with LOOP

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the minimum pressure in the EDG Starting Air Receiver?

A

190#

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the Minimum Level for the EDG Fuel Oil Storage Tank?

A

46,000 gal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the minimum level for the EDG Fuel Oil Day Tank?

A

101.4 gal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the temperature limit for lower containment?

A

60-120*F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the temperature limit for upper containment?

A

60-100*F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the T.S. Pressure Range for containment?

A

-1.5# to 0.3#

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Plant Batteries are designed to last how long on LOOP?

A

3 hours

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Plant Batteries are designed to last how long on a SBO?

A

4 hours

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Degraded Bus Voltage is sensed on

A

2/3 on A and D T Busses at 113 Volts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Undervoltage is sensed on

A

2/3 on EACH T-Bus at 94 (93) Volts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

The 17 ton CO2 Tank has a TS Limit of ____ #

A

285 #

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the minimum Boron Concentration for the SFP?

A

2400 ppm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the REFUELING WATER STORAGE TANK min level? Why?

A

375,500 gallons min

for Recirc sump volume- 1 hr Spec

17
Q

What is the REFUELING WATER STORAGE TANK Boron concentration? Why?

A

2400 to 2600 ppm boron- 8 hr Spec

Low end ensures subcriticality

High end for max time to HL recirc

18
Q

What is the REFUELING WATER STORAGE TANK temperature range? Why?

A

70°F to 100°F- 8 hr spec

Low End Lower D/P rcs vs cntmt – backpressure

High End CTS to condense steam / 12#

19
Q

What is the band for the volume for accumulators?

A

921 - 971 cuft

20
Q

What is the pressure band accumulators?

A

585 - 658 #

21
Q

What is the boron concentration for the accumulators?

A

2400 - 2600 ppm

22
Q

Why is Hot Leg Recirc used?

A

Prevent boron plating