What are the Bus Duct Fan auto starts?
Low Flow with C/S in auto
(5” H2O decreasing)
What cools the Bus Duct?
TACW
What has to be done if both Bus Duct fans fail?
Bus loading must be reduced to a maximum of 10,000 amps per phase (~40% power)
What is the Deionizing Baffle for?
Prevents transferring ionized air (arcing) from one phase to another (they are between the main transformer connections)
What is the bus duct flow path for U1?
- Fan
- Out Middle Duct
- Supplies generator terminals, bus PT xfmrs, GSUs, and UATs
- Return in North and South ducts
- Cooler
- Fan Inlets
What is the bus duct flow path for U2?
- Fan
- Out South Duct
- Supplies generator terminals, bus PT xfmrs, GSUs, and UATs
- Return in North and Middle ducts
- Cooler
- Fan Inlets
How many Bus Duct Cooling Fans do we need to operate at 100% power?
1 Bus Duct Cooling fan needed for 100% operation
At what temperature would a Unit Trip be required?
At the High High Limit of 105°C ( 221°F )
What are the U1 and U2 Bus Duct Loads?
- Main Gen Connections
- Bus PTs
- Main Transformer Connections
- Unit Aux Transformer Connections