Condensate Flashcards

1
Q

What is the tech spec minimum of the CST?

A

182,000gal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the HWP auto starts?

A

Low # at:
130# (U1)
110# (U2)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the HWP trips?

A

Overload/Overcurrent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What powers the HWPs?

A

4kV RCP Buses
1/2D North
1/2A Middle
1/2C South

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the CBP auto starts?

A

Low pressure at 325#

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are the CBP trips?

A

Overload/Overcurrent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the flow capacity of the LP #1 heaters?

A

Each string supplies 50% flow (We have 3)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the flow capacity of the LP #2-4 heaters?

A

Each string supplies 80% flow (we have 2 strings) with a bypass that can provide 20% flow via CRV-224

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What does CRV-55 do for you?

A

Allows makeup from the CST to the Condenser Hotwells (Sensed on A and C hotwell lvl)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What does CRV-155 do for you?

A

Allows for excess condensate from hotwells to go back to the CST (Sensed on A and C hotwell lvl)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What does CRV-224 (2,3,4 Heater bypass valve) do?

A
  • Allows having a heater string out and provides 20% flow
  • Auto modulates open when MFP suction < 240#
  • Trips open at 210# MFP Suction
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How do you reset CRV-224 (2,3,4 Heater bypass valve)?

A

Run controller to open when MFP Suction pressure > 260#

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What do CRV-201, 202 and 203 (Condensate Booster Pump Recirc Valves) do?

A

Maintain 4000 gpm on running pumps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Where is the flow switch located for the Condensate Booster Pump Recirc Valves?

A

Flow switch is on the common discharge header

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What do CMO-101(102) (SJAE bypass valves) allow?

A
  • Manually position to achieve desired DP across SJAEs
  • Prevents exceeding design flow of SJAEs
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

How much hood spray does each unit have?

A
  • 138gpm (U1)
  • 1200gpm (U2)
17
Q

What does CMO-61 (SJAE and HWP recirc line valve) do for you?

A
  • Provides continuous flow path from steam jet air ejector header to the main condensers to maintain minimum flow through the hotwell pumps and steam jet air ejector condensers
  • 2400gpm min per pump
18
Q

What does the basis for T.S. 3.7.6 (CST) state

A

To remove heat from 100% to no-load MODE 3 and to either remove decay heat for 2 hours in M3 then cool down to RHR assuming loss of offsite power. OR to remove decay heat for 9 hours in M3 assuming loss of offsite power as the initiating event.

≥ 138,335 usable gallons, which is based on the more limiting of either holding the unit in MODE 3 for 9 hours or holding the unit in MODE 3 for 2 hours followed by a 4 hour cooldown to RHR entry conditions

19
Q

What suction pressure do the CRV-224 valves help to maintain?

A

210 psi - 240 psi MFP Suction Pressure
- Begins modulating at 240 psi
- Trips open at 210 psi

20
Q

What Unit(s) have Condenser equalizations and what are they for?

A

Unit 1 to maintain even stresses (by temperature and pressure) on the Turbine Bearings

21
Q

Explain the purpose and functions of the Condensate Chemical Feed System.

A

Minimizes secondary side piping and steam generator corrosion by injecting chemicals that control pH and scavenge residual dissolved oxygen.

22
Q

What actuates hood spray in Unit 1 (CRV-102) and Unit 2(CMO-40)?

A
  • Generator Load < 7.5% and Turbine Speed > 900 rpm
  • Manual
23
Q

If ‘A’ Hotwell is providing input to the HW Lvl Ctlr, then which hotwell level is being displayed on the Chart Recorder?

A

‘C’ Hotwell level is being displayed on the chart recorder

24
Q

How does CRV-55 fail?

A

Closed

25
Q

How does CRV-155 fail?

A

Closed

26
Q

At what Generator Load OR Turbine Speed does Hood Spray Terminate for both units?

A

Generator load is > 12.5% OR Turbine speed is < 900 rpm