Condensate Flashcards
What is the tech spec minimum of the CST?
182,000gal
What are the HWP auto starts?
Low # at:
130# (U1)
110# (U2)
What are the HWP trips?
Overload/Overcurrent
What powers the HWPs?
4kV RCP Buses
1/2D North
1/2A Middle
1/2C South
What are the CBP auto starts?
Low pressure at 325#
What are the CBP trips?
Overload/Overcurrent
What is the flow capacity of the LP #1 heaters?
Each string supplies 50% flow (We have 3)
What is the flow capacity of the LP #2-4 heaters?
Each string supplies 80% flow (we have 2 strings) with a bypass that can provide 20% flow via CRV-224
What does CRV-55 do for you?
Allows makeup from the CST to the Condenser Hotwells (Sensed on A and C hotwell lvl)
What does CRV-155 do for you?
Allows for excess condensate from hotwells to go back to the CST (Sensed on A and C hotwell lvl)
What does CRV-224 (2,3,4 Heater bypass valve) do?
- Allows having a heater string out and provides 20% flow
- Auto modulates open when MFP suction < 240#
- Trips open at 210# MFP Suction
How do you reset CRV-224 (2,3,4 Heater bypass valve)?
Run controller to open when MFP Suction pressure > 260#
What do CRV-201, 202 and 203 (Condensate Booster Pump Recirc Valves) do?
Maintain 4000 gpm on running pumps
Where is the flow switch located for the Condensate Booster Pump Recirc Valves?
Flow switch is on the common discharge header
What do CMO-101(102) (SJAE bypass valves) allow?
- Manually position to achieve desired DP across SJAEs
- Prevents exceeding design flow of SJAEs