Ctrl Room Ventilation Flashcards
How does ESW interface with the CRAC?
- Cooling water for condensers
- Backup supply for cooling coils
Will the CRAC chiller trip off with a loss of ESW?
Yes
When is the backup cooling capability lost with respect to ESW to the cooling coils?
Backup capability lost if ESW > 65°F
What are the CR Pressurization Fan starts?
- SI in either Unit (Train Spec)
- CR High Rad (Unit Specific)
- CRCV Fire (CO2 or Halon actuation)
- Manual
What the trips of the CRAC chiller package?
- High/Low Pressure
- High/Low Oil Pressure
- Low Temperature
- Overload
- Load Conservation (Fan is unaffected)
How do the AHU Temp Control Valves (VRV-315/325) fail on a loss of air?
Fail open (full flow to chillers)
When will Control Room vent intake damper no. 1 dampers ACRDA-1 / 1A be open?
During normal operation
When will ACRDA-2 / 2A CREV outside dampers be part open?
- CRCV fire
- Hi Rad
- SI in either unit
When will ACRDA-3,
C/R recirc damper be open?
- Norm operation
- Hi Rad
- SI either unit
If there is a toxic gas leak, how are all 3 of the CR dampers aligned?
Manually closed
What are the CR Vent Dampers positions during a SI, High Rad or Fire?
- 1/1A CRAC outside supply always close
- 2/2A CREV outside supply always part open
- 3 CREV C/R recirc is usually open - Closes on FIRE ONLY
If U-1 gets a CRCV Fire signal and All U-1 CR Vent Sys Auto actions occur as expected
THEN
U-1 gets a CR High Rad signal,
Does U-1 CR vent Sys realign?
No, “First in Wins.”
The U-1 CR Vent System stays aligned for the U-1 CRCV Fire signal
When will HV-ACR-DA-2A Clean Up Intake Damper go to part open?
If HV-ACR-DA-2 isn’t in part open after 45 sec since actuation
Per TS 3.3.7 B (CREV system Actuation Instrumentation), what must be done if ONE or more required functions with 2 trains INOPERABLE, what must be done:
IMMEDIATELY:
- Place one CREV train in pressurization/cleanup mode
AND
- Enter applicable Conditions and Required Actions for 1 CREV train made Inoperable by Inoperable CREV actuation instrumentation
OR
- Place both CREV trains in pressurization/cleanup mode
Per TS 3.7.10 B (CREV system), what must be done if 1 or more CREV trains Inoperable due to CRE Boundary in Modes 1-4
IMMEDIATELY:
Initiate action to implement mitigating actions