Reactor Trips Flashcards

1
Q

List all 19 Reactor Trips.

Do NOT include coincidence, setpoints or interlocks

A
  1. SR Hi Flux
  2. IR Hi Flux Trip
  3. PR Hi Flux, Low Setpoint
  4. PR Hi Flux, High Setpoint
  5. PR Hi Positive Rate
  6. OTΔT
  7. OPΔT
  8. Pressurizer Pressure Low
  9. Pressurizer Pressure High
  10. Pressurizer Water Level High
  11. RCS Loss of Flow
  12. Undervoltage on RCP Buses
  13. Underfrequency on RCP Buses
  14. RCP Breaker Position
  15. SG Water Level Low Low
  16. SG Water Level Low with Feed Flow less than Steam Flow
  17. Safety Injection
  18. Turbine Trip
  19. Manual
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the setpoint, coincidence and interlock for the SR Hi Flux Reactor Trip?

A

90,000 CPS ↑ on 1/2 SR NIs with a P-6 interlock

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the setpoint, coincidence and interlock for the IR Hi Flux Reactor Trip?

A

22.5 (20)% RTP ↑ on 1/2 IR NIs with a P-10 interlock

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the setpoint, coincidence and interlock for the PR Hi Flux, Low Setpoint Reactor Trip?

A

20% RTP ↑ on 2/4 PR NIs with a P-10 interlock

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the setpoint, coincidence and interlock for the PR Hi Flux, High Setpoint Reactor Trip?

A

107% RPT ↑ on 2/4 PR NIs with NO Interlock

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the setpoint, coincidence and interlock for the PR High positive rate Reactor Trip?

A

4.5% ↑ in 2 sec on 2/4 PR NIs with NO Interlock

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the setpoint, coincidence and interlock for the OTΔT Reactor Trip?

A

Variable setpoint on 2/4 with NO Interlock

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the setpoint, coincidence and interlock for the OPΔT Reactor Trip?

A

Variable setpoint on 2/4 with NO Interlock

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the setpoint, coincidence and interlock for the Pressurizer Pressure High Reactor Trip?

A

2385 psig ↑ on 2/4 Pressurizer Pressures with NO Interlock

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the setpoint, coincidence and interlock for the Pressurizer Pressure Low Reactor Trip?

A

1950 # ↓ on 2/4 Pressureizer Pressures with a P-7 Interlock

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the setpoint, coincidence and interlock for the Pressurizer Water Level High Reactor Trip?

A

92% ↑ on 2/3 pressurizer water levels with a P-7 Interlock

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the setpoint, coincidence and interlock for the RCS Loss of Flow Reactor Trip?

A

2/3 on 1/4 Loops at 91% if greater than P-8
or
2/3 on 2/4 Loops 91% ↓ if less than P-8 but greater than P-7

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the setpoint, coincidence and interlock for the Under Voltage Reactor Trip?

A

1/2 on 2/4 RCP Buses at 88V ↓ with a P-7 Interlock

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the setpoint, coincidence and interlock for the Under Frequency Reactor Trip?

A

1/2 on 2/4 RCP Buses at 58.2 Hz↓ with a P-7 Interlock

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the setpoint, coincidence and interlock for the RCP Breaker Position Reactor Trip?

A

2/4 Open Aux Switches with a P-7 Interlock

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the setpoint, coincidence and interlock for the SG Water Level Low Low Reactor Trip?

A

2/3 on 1/4 SG at 5%↓ for Unit 1 or 22% ↓ for Unit 2.

There are NO Interlocks

17
Q

What is the setpoint, coincidence and interlock for the SG Water Level Low with Feed Flow greater than Steam Flow Reactor Trip?

A

1/2 on 1/4 SG at 15%↓ for Unit 1 and 26% ↓ for Unit 2 WITH 1/2 on same SG Feed Flow Less than Feed flow by 0.71E6 lbm/hr for Unit 1 and 1.47E6 lbm/hr for Unit 2.

There are NO Interlocks.

18
Q

What is the setpoint, coincidence and interlock for the Safety Injection Reactor Trip?

A

Either Train of SI will cause a Reactor Trip and there are NO Interlocks

19
Q

What is the setpoint, coincidence and interlock for the Turbine Trip Reactor Trip?

A

2/3 Oil Press 800 psig ↓
OR
4/4 Stop Valves 1% ↓

With P-8 as an Interlock

20
Q

What are the 6 at power trips that are automatically blocked when lowering power and the P-10 status light goes out?

A

Pressurizer Pressure Low
Pressurizer Water Level High
RCS Loss of Flow
UV - RCP Buses
UF - RCP Buses
RCP Breaker Position