Liquid Rad Waste (WDS) Flashcards

1
Q

What will auto close the Unit Release Valve (RRV-286/287)?

A

NO CW Pumps running in associated unit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What happens on a High Rad Signal or failure of RRS-1000

A
  • Liquid Waste Disposal Effluent Hdr to Circ Water Disch Control valve, 12-RRV-285 CLOSES
  • MT/WECT Pump selected for Release Trips
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What can trip a Monitor Tank Pump?

A
  • Hi Rad / Failure of RRS-1000 when selected to release.
  • Low Monitor Tank Level when proper tank selected
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

When do the aux building floor drains drain to?

A
  • 609’ and above drains go to DWHUT.
  • 587’ drains go to Dirty Sump Tank.
  • 573’ drains go to Aux Sump.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the purpose of the Time Delay Chamber in the Liquid Release flowpath?

A

Gives sufficient delay time in the release flowpath- allows RRV-285 to close in time to prevent the release of bad water.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the Interlock for CWHUT and DWHUT inlet valves? (RRV-255/256)

A

Interlocked so that both cannot be closed at the same time (prevents backing up of drains)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Which ONE of the following describes three sources of liquid waste to the Reactor Coolant Drain Tank?

A. Excess Letdown Heat Exchanger , Lower Containment Sump, Charging Line Suction Relief

B. RCS Loop Drains, Reactor Vessel Flange Leak Off, SI Accumulator Tank Drains

C. RCS Loop Drains, Pressurizer Relief Tank, Reactor Cavity Sump

D. RCP Thermal Barrier Relief, Excess Letdown/Seal Return Relief, Reactor Vessel Flange Leak Off

A
  • B. RCS Loop Drains, Reactor Vessel Flange Leak Off, SI Accumulator Tank Drains
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What Drain sources tap into RCDT Outlet piping?

A
  • RCP #3 Seal
  • PRT
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What drains into the CWHUT?

A

Hard Piped equipment drains from the 609’ and above

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What 3 sumps are pumped out of containment? Where do they go?

A

All pump to DWHUT/CWHUT
- Lower Ctmnt Sump
- Reactor Cavity Sump
- Pipe Tunnel Sump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Where do the Clean/Dirty Sump tanks overflow?

A

Aux Sump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What drains into the Clean Sump Tank?

A

Hard Piped drains on the 587’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Where do drains on the 573’ Elevation go?

A

Aux Sump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Where can the RCDT contents be pumped to?

A
  • CVCS HUT
  • CWHUT
  • RWST
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Where does the RCDT receive drains from?

A
  • Accumulator Drains
  • XS LD Hx Drains
  • Regen Hx Drains
  • RCS Loop Drains
  • RCP #2 Seal Leak off
  • Rx Vessel Flange Leakoff
  • Refueling Cavity
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When does TRO 8.7.11, Liquid Holdup Tanks, apply?

A

At all times.

17
Q

Which tanks does TRO 8.7.11, Liquid Holdup Tanks, apply to?

A

Outdoor tanks not surrounded by liners, dikes, or walls capable of holding the tanks contents and that do not have overflows and surrounding area drains connected to the liquid radwaste system

18
Q

Per TRO 8.7.11, Liquid Holdup Tanks, what do you do if rad matieral in any outdoor tank is greater than the limit?

A

IMMEDIATELY stop putting more in!

Ya big dummy.