Where does the Generator Condition Monitor and H2 Purity Monitor get its flow from?
Differential pressure produced by the fans attached to the generator rotor provide the motive force thru the Condition Monitor and the Hydrogen Purity Monitor.
How is the H2 purged from the Generator?
CO2 is used
When will 12-GSO-251, Bulk H2 Storage Tank Outlet Header Valve, go closed?
Low turbine building header press < 50 psi. This prevents H2 leak to Turbine Building
How do you reset 12-GSO-251, Bulk H2 Storage Tank Outlet Header Valve, after an auto closure?
Push and hold local reset pushbutton until downstream pressure of GSO-251 builds back up to > 50# in the header
What are the Generator H2 coolers cooled by?
TACW
What H2 purity does each unit need to maintain?
- U1 > 96%
- U2 > 94%
What is the Hydrogen flowpath within the Generator?
Fans both ends => Turbine and collector ends => along rotor shaft and stator core => through gaps => vent holes => back through center of rotor and stator => coolers => back to suction of the fan
What does Generator Hydrogen mainly cool?
The Rotor
What are normal pressures for Hydrogen Gas in the generator for both units?
- U1 75#
- U2 60#
How does plant air support the generator?
Plant air provides a safe generator atmosphere for maintenance activities