Equipment Auto Starts Flashcards
What is the starting sequence for the Fire Pumps?
Motor Driven 140 psig for 2 sec
East Diesel 130 psig for 15 sec
West Diesel 120 psig for 25 sec
What are the EDG Starts?
CR Control Switch Local PB Loadshed SI Manual Starting Air Valves
What are the Circ Water Pump Auto Starts?
Failure of a running pump if in Auto
What are the ESW Pump Auto Starts?
- SI
- Loadshed
- Lo HDR Press 40 #s if in Auto
What are the CCW Pump Auto Starts?
- SI
- Loadshed
- Lo discharge pressure 80#s if in Auto
What are the auto starts for the PAC Aux Oil Pump?
- PAC Start (until pressure >42psi)
- PAC Stopped (15 mins)
- Low LO Press
- Loss of DCCS Control Power
- Plant Air HDR 97#
What are the Glycol Pump Auto Starts?
Low Discharge Pressure 95 #s
What are the CTS Pump Starts?
- Phase B
- Loadshed w/ Phase B
- Manual
What are the AES Fan Auto Starts?
- SI
2. ECCS / CTS Pump Start on that Train
What are the Auto Starts for the EDG Fans?
- EDG Start. Exhaust then 20 sec later Supply
2. 95*F room temperature
What are the auto starts for the ESW Room Fans?
- One starts on Pump Start
2. The other cycles on 90*F Room Temp
What will auto start the CCW Pump Fans?
Unit Specific Load Conservation
Unit 1: #2 and 3
Units 2: #1
What will auto start the control room pressurization fan?
- Either Unit SI
- Unit Specific High Control Room Radiation
- CR Cable Vault Fire
What will Auto Start a Heater Drain Pump?
NOTHING
What will Auto Start a Hotwell Pump?
Low Pressure 130 (110) #