What is the starting sequence for the Fire Pumps?

A

Motor Driven 140 psig for 2 sec
East Diesel 130 psig for 15 sec
West Diesel 120 psig for 25 sec

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the EDG Starts?

A
CR Control Switch 
Local PB
Loadshed
SI
Manual Starting Air Valves
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the Circ Water Pump Auto Starts?

A

Failure of a running pump if in Auto

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the ESW Pump Auto Starts?

A
  1. SI
  2. Loadshed
  3. Lo HDR Press 40 #s if in Auto
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the CCW Pump Auto Starts?

A
  1. SI
  2. Loadshed
  3. Lo discharge pressure 80#s if in Auto
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are the auto starts for the PAC Aux Oil Pump?

A
  1. PAC Start (until pressure >42psi)
  2. PAC Stopped (15 mins)
  3. Low LO Press
  4. Loss of DCCS Control Power
  5. Plant Air HDR 97#
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the Glycol Pump Auto Starts?

A

Low Discharge Pressure 95 #s

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What are the CTS Pump Starts?

A
  1. Phase B
  2. Loadshed w/ Phase B
  3. Manual
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What are the AES Fan Auto Starts?

A
  1. SI

2. ECCS / CTS Pump Start on that Train

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What are the Auto Starts for the EDG Fans?

A
  1. EDG Start. Exhaust then 20 sec later Supply

2. 95*F room temperature

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What are the auto starts for the ESW Room Fans?

A
  1. One starts on Pump Start

2. The other cycles on 90*F Room Temp

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What will auto start the CCW Pump Fans?

A

Unit Specific Load Conservation

Unit 1: #2 and 3
Units 2: #1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What will auto start the control room pressurization fan?

A
  1. Either Unit SI
  2. Unit Specific High Control Room Radiation
  3. CR Cable Vault Fire
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What will Auto Start a Heater Drain Pump?

A

NOTHING

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What will Auto Start a Hotwell Pump?

A

Low Pressure 130 (110) #

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What will Auto Start a Condensate Booster Pump?

A

Low Pressure 325 #

17
Q

What will Auto Start a TACW Pump?

A

Low Discharge Pressure 155 (145) #

18
Q

What will Auto Start the MDAFPs?

A
  1. Both MFPs Trip (only in auto)
  2. AMSAC
  3. Loadshed
  4. Lo-Lo SG 2/3 on 1 SG 5% (22%)
  5. SI
19
Q

What will Auto Start the TDAFP?

A
  1. Undervoltage on RCP Bus (1/2 on 2/4 Busses) @ 88 V
  2. SG Lo-Lo 2/3 on 2 SGs @ 5 (22)%
  3. AMSAC
20
Q

What will auto start the Stator Water Pump in U1?

A

Low Pressure at 120#

21
Q

What will auto start the Stator Water Pump in U2?

A
  1. Low Pressure at 80#

2. Low Flow 845 gpm

22
Q

What will auto start the U1 Emergency Seal Oil Pump?

A

MSOP Disch Press < 125 #

23
Q

What will auto start a Charging Pump?

A

SI

Loadshed with SI

24
Q

What is the MFP Seal Water pp Auto Start?

A

Booster Pump discharge vs MFP Suction pressure < 15 psid

25
Q

What will autostart the U1 bearing lift pumps?

A

low speed switch

26
Q

When will U1 bearing lift pumps 2 and 4 start?

A

20 secs after turning gear engagement to ensure sufficient drag

27
Q

When will the U2 bearing lift pumps auto start?

A

Turbine trip

28
Q

When does the U2 Main turbine turning gear auto start?

A

1 min after turbine trip

29
Q

What will auto start the RHR Pumps?

A

SI

Loadshed with SI

30
Q

What will put an AES Fan in Charcoal Mode?

A
  1. Phase B
  2. CS in Stop (only that fan)
  3. Loss of power to either fan
  4. Loss of CA
31
Q

What will auto start the standby WGC?

A

high vent header pressure of 2 #

stops when below 1.3 PSIG