Aux Building Ventilation Flashcards
What are the AES Fan Starts?
- SI
- Associated Train ECCS pump start
- CTS pump start
When is the AES Fan Charcoal bed I/S?
- Phase B (Either Train)
- Ctrl Stch in “Stop” (specific fan)
- Loss of Control Air (specific fan)
- Loss of power to either AES Fan
Where does the AES Fan take its suction from?
- CTS Heat Exchanger
- RHR Heat Exchanger
- Charging Pumps (and Reciprocating)
- SI Pump
- RHR Pump
- CTS Pump
- Fans take suction directly from Vestibule
What are the AS/AX trips?
- Load Con
-Thermal Overload
What are the AFS Trips?
- Load Con
- SFP High Rad (RRC-330)
- Thermal Overload
What are the AFX Trips?
- Load Con
- Charcoal Bed Fire
- Thermal Overload
When is the AFX Fan Charcoal bed I/S?
- SFP High Rad (RRC-330)
- Loss of power to either fan
- Loss of control air
When do the CCW supply fans start?
- Load Con (Unit Specific)
- 1 U2 AS fan OOS 1 ACCP running
- 2 U2 AS fans OOS 2 ACCPs running
What unit are the CCW supply fans powered from?
- # 1 fan powered from Unit 2
- # 2 and #3 fans powered from Unit 1
How does the CCW fans maintain temperature when its cold outside?
A Supply/Recirc damper is opened to provide a supply from inside the AB and the outside supply is closed
Per TS 3.7.13A (FHAEV System during fuel movement), what must be done if Required FHAEV train Inoperable or not in operation
IMMEDIATELY Suspend movement of irradiated fuel assemblies in the Aux Building
What will cause 12-RV-306 [Vent Stack] to Auto Trip Closed?
A loss of BOTH Unit 1 AX Fans will close 12-RRV-306
What is the purpose of the Charcoal Filters for the Spray Add Tank Room?
Removes radioactive iodine and methyl iodide from air
Do the Spray Add Tank Room Fans trip on a
charcoal fire?
No, they do not
What is the 3.7.12, ESF Ventilation System Basis?
The system limits radioactive release to within the 10 CFR 100 limits and to 5 rem TEDE for CR operators during recirc mode of a large break LOCA.