Aux Building Ventilation Flashcards

1
Q

What are the AES Fan Starts?

A
  • SI
  • Associated Train ECCS pump start
  • CTS pump start
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

When is the AES Fan Charcoal bed I/S?

A
  • Phase B (Either Train)
  • Ctrl Stch in “Stop” (specific fan)
  • Loss of Control Air (specific fan)
  • Loss of power to either AES Fan
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Where does the AES Fan take its suction from?

A
  • CTS Heat Exchanger
  • RHR Heat Exchanger
  • Charging Pumps (and Reciprocating)
  • SI Pump
  • RHR Pump
  • CTS Pump
  • Fans take suction directly from Vestibule
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the AS/AX trips?

A
  • Load Con
    -Thermal Overload
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the AFS Trips?

A
  • Load Con
  • SFP High Rad (RRC-330)
  • Thermal Overload
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are the AFX Trips?

A
  • Load Con
  • Charcoal Bed Fire
  • Thermal Overload
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When is the AFX Fan Charcoal bed I/S?

A
  • SFP High Rad (RRC-330)
  • Loss of power to either fan
  • Loss of control air
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

When do the CCW supply fans start?

A
  • Load Con (Unit Specific)
  • 1 U2 AS fan OOS 1 ACCP running
  • 2 U2 AS fans OOS 2 ACCPs running
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What unit are the CCW supply fans powered from?

A
  • # 1 fan powered from Unit 2
  • # 2 and #3 fans powered from Unit 1
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How does the CCW fans maintain temperature when its cold outside?

A

A Supply/Recirc damper is opened to provide a supply from inside the AB and the outside supply is closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Per TS 3.7.13A (FHAEV System during fuel movement), what must be done if Required FHAEV train Inoperable or not in operation

A

IMMEDIATELY Suspend movement of irradiated fuel assemblies in the Aux Building

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What will cause 12-RV-306 [Vent Stack] to Auto Trip Closed?

A

A loss of BOTH Unit 1 AX Fans will close 12-RRV-306

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the purpose of the Charcoal Filters for the Spray Add Tank Room?

A

Removes radioactive iodine and methyl iodide from air

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Do the Spray Add Tank Room Fans trip on a

charcoal fire?

A

No, they do not

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the 3.7.12, ESF Ventilation System Basis?

A

The system limits radioactive release to within the 10 CFR 100 limits and to 5 rem TEDE for CR operators during recirc mode of a large break LOCA.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Why do we manually place SFP Vent in manual Charcoal when working in SFP?

A

Due to FSAR stating that automatic damper operation on a high rad alarm is too slow.

17
Q

Unit 1 has just entered mode 3 following a maintenance outage to replace a leaky fuel assembly. During work on the East RHR pump, an accidental spill causes radiation levels to increase.

The following radiation channels have alarmed:
ERA-7305 U1 East RHR Pump Room - RED
VRS-1505 Unit Vent Effluent Low Range Noble Gas – RED

What must be done based on these conditions?

A

The AES Fan Charcoal Filter must be manually placed in service.

18
Q

What realign on loss of ctrl air?

A

Face dampers and bypass dampers

19
Q

Which Aux building fans trip on a load conservation?

A
  • AS
  • AX
  • AFS
  • AFX
20
Q

Per Technical Specification 3.7.13, Fuel Handling Area Exhaust Ventilation (FHAEV) System, what is the bases for stopping fuel movement immediately if you do not have a AFX fan?

A

A total system failure could result in the atmospheric release from the auxiliary building exceeding the 10 CFR **100 **limits in the event of a fuel handling accident.