Systems Comp Study Sesh Flashcards

1
Q

Explain the SDG sequence.

A

Senses UV
Opens MDS
Starts SDGs
First up to speed closes in
Second diesel auto synchs
Tie Breaker closes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

If there is a differential on the BMC/CMC Transformer, how does the protective scheme work?

A

Both high and low side opens at the same time, then the creoss tie will close without any delay

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How does the Degraded Bus Voltage work?

A

Sensed on A & D T Buses
9 sec delay for alarm. If SI or LoLo SG, then loadshed
+90 seconds of correction before Fast transfer to RATs
+21 seconds of RATs trying to correct before Load Shed

If sensed on A or D, that whole train will be loadshed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the normal source of power to the CRIDs?

A

250 vDC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the alternate power source to the CRIDs?

A

600 vAC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Which 600 v bus goes with which CRID?

A

C -1
D -2
A - 3
B - 4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What does the In Synch light being lit on the CRID tell you?

A

Alternate source is available

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What does the ALT Source to Load PB on the CRID do?

A

electronically transfers on static switch to alternate source of power

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How does the Auto Retransfer Lockout work on the CRID?

A

After transfer to the alternate load, if the event clears, and is normal for 30 seconds, the statis switch auto transfers the load back to the normal source. If a 2nd transfer to alt source occurs before the autoretransfer capability is reset manually, the alternate source supplies the load. The static transfer switch locks out on alternate source until reset.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What does a rectifier do?

A

Changes AC to DC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What normally powers the batteries?

A

Battery Chargers from 600 vAC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the order of starts with time delays for all the fire pumps?

A

Motor/Electric 140 psi for 2 secs
East Diesel 130 psi for 15 secs
West Diesel 120 psi for 25 secs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What are the SDGs sized for?

A

1 Unit, 1 Train of RCS Inventory Control

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

How does the LoadShed Scheme work?

A

Sensed on EACH T Bus at 94 (93) Volts and lowering for 2 seconds. Loadsheds that one bus

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

If there is a differential on the B/C bus 600 v transformer, will that bus be powered from the EDG?

A

NO. No high side disconnect, so entire bus is dropped

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Who has command function?

A

Shift Manager

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

What is the fire protection provided to both Units CRCVs?

A

Auto Halon
Manual CO2
Auto Water for Unit 2 Only

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

Define the Modes of Operation Per Tech Specs

A

Mode 1 - Keff Greater than or equal to 0.99 and Rated Thermal Power > 5%

Mode 2- Keff Greater than or equal to 0.99 and Rated Thermal Power less than or equal to 5%

Mode 3 - Keff < 0.99 and RCS Tavg Greater than or equal to 350 degrees

Mode 4 - Keff < 0.99 and RCS Tavg btween 200 and 350 degrees

Mode 5 - Keff < 0.99 and RCS Tavg less than or equal to 200 degrees

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

What is the pressure safety limit?

A

2735 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

If the safety limit for pressure is violated, what must be done?

A

Modes 1&2, Be in Mode 3 and restore within 1 hour

Modes 3-5, Restore within 5 mins

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

Whats the purpose of the safety limits in section 2 of Tech Specs?

A

Protect from fuel damage and maintain vessel integrity.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

Who is responsible for overall safe operations?

A

Plant Manager

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

What are the Tech Spec credited sources for Offsite Power?

A

RATs and EP

SDGs are NOT credited

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

What is the normal Split Bus alignment?

A

BXfmr 5 to Train B
Xfmr 9 to Train A
BD is Open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

What is the purpose of Xfmr 4?

A

Connects the 345 and 765 kV Yards

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
26
Q

What are the requirements regarding shift staffing?

A

May be less than minimum for less than or equal to 2 hours for unexpected absence, provided immediate action is take to restore

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
27
Q

If a surveillance is MISSED, what must be done?

A

Performed within 24 hours or the normal surveillance frequency, whichever is GREATER

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
28
Q

Can Grace be applied to the first performance of an EIS?

A

Nope! Only subsequent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
29
Q

How much grace is allowed for surveillances?

A

25%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
30
Q

What is the maximum extension time for a TS Entry?

A

additional 24 hours from the first inoperability, without making the second INOP go greater than the original spec time

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
31
Q

What supplies power to the pressurizer heaters?

A

T Busses A & D

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
32
Q

What causes a load conservation?

A

LOOP + SI/CTS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
33
Q

How are the Plant Batteries Sized?

A

4 hours for SBO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
34
Q

What are the trips available to the EDGs during a SI or LOOP?

A

Generator Phase Differntial
Electronic Overspeed at 110%
Manual Push Button

If using the control switch, must HOLD it to keep if from restarting.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
35
Q

What is the minimum pressure in the EDG Air Receiver?

A

190 psi

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
36
Q

What is the minimum volume of the Diesel FOST? Good for how long?

A

> 46,000 gallons good for 1 EDG at full load for 7 days

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
37
Q

What happens if the electronic governor for the EDG fails high?

A

speed rises and machine will be controlled by the mechanical governor (if not paralleled, otheriwse speed droop takes over and grid maintains speed)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
38
Q

If control air is lost, will the EDG continue to run / start?

A

No! Throttle Control Cylinder will be extended, stopping fuel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
39
Q

where is the EDG field flash powered from?

A

1 kV interter until 80% speed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
40
Q

When do the LO upper valve gears open for the EDGs?

A

ON the EDG start signal (95% run relay)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
41
Q

What is the Circ Water Pump Auto Start?

A

failure of running pump, if the control switch is in AUTO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
42
Q

What is a Circ Water Pump Trip?

A

Undervoltage on associated 4 kV Bus

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
43
Q

When does the circ water pump discharge valve auto open?

A

on auto pump start only, NOT manual

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
44
Q

What are the power supplies to the CW Pumps?

A

1 - D
2 - A
3 - B
4 -C

RCP Buses

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
45
Q

What does De-Ice Look like?

A

WMO-30 is closed
WMO-16 or WMO-26 Open

done slowly to prevent debris agitation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
46
Q

Which valves are used if the center intake is crushed?

A

WMO-17/27

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
47
Q

What are the Tech Spec Pressure Limits for containment?

A

-1.5 psig to +0.3 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
48
Q

What are the tech spec containment temperature limits?

A

Upper = 60-100 degress
Lower = 60-120 degrees

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
49
Q

What are the power supplies to SFP Pumps?

A

North = 11C
South = 21C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
50
Q

What will isolate CCW to the SFP Hx?

A

Phase A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
51
Q

If there is a rupture on the suction piping for the SFP Pump, what is the lowest the water will drain below the normal level?

A

19 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
52
Q

Will X-tie through SFP purification piping prevent boiling?

A

No! Just delays it

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
53
Q

Per the bases, why is there greater than 23 feet of water above the fuel?

A

Iodine Decon Factor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
54
Q

What are the NESW Pump Auto Starts?

A

Load Shed
SI
Low Pressure 55 (60) psi in auto
*For pressure, it is unit specific. A low pressure on Unit 1 N NESW will start the Unit 1 S NESW. It will not autostart any Unit 2 pumps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
55
Q

What are the ESW Pump auto starts?

A

SI - Either Unit, Train Specific
Load Shed
Low Header Pressure of 40 psig in AUTO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
56
Q

If the EDG starts but power is lost to the normal cooling valve is lost (A/D did not repower ), will the EDG have cooling?

A

Manual from Opposite train is available, but without Operator Action, NO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
57
Q

What happens to ESW from CCW Hx on a SI?

A

Throttles to ~5,000 gpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
58
Q

What are the auto starts of the CCW Pumps?

A

SI
Load Shed
Low pressure on running pump discharge of 80 psi if in AUTO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
59
Q

What is the makeup to the CCW Surge Tank?

A

MANUAL Demin Water

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
60
Q

What happens on a high rad in the CCW Surge Tank?

A

Vent Valve (CRV-412) goes closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
61
Q

What happense to the CCW Hx Outlet valves on a SI?

A

They go Full Open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
62
Q

What happens to the CCW Outlets from RHR Hx on a SI?

A

Throttles to ~3500 gpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
63
Q

What manual action must be done on a Phase B?

A

RCPs must be tripped because CCW has been isolated to the thermal barrier and MACs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
64
Q

What happens on a Low Low Glycol Expansion Tank LeveL?

A

Outside containment isolation valves VCR-10 and 20 close

Glycol Expansion Tank Outlet Valves VSO-20 and 21 Close

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
65
Q

Which Containment Fans trip on a Phase B?

A

CLVs
CRDMs
Prssurizer Fans
Rx Cavity Fans

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
66
Q

What happens if an odd numbered radiation monitor receives a High Rad Signal? (ie. 1300 or 2300)

A

Inside Containment Valves close and Instrument Room Purge Supply Fan Trips

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
67
Q

What happens if an even numbered radiation monitor receives a High Rad Signal? (ie. 1400 or 2400)

A

Outside containment isolation valves close and all fans other than instrument room purge supply trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
68
Q

Where do CEQ Fans take suction?

A

SG Enclosures
Pzr Doghouse
CLV Fan Rooms
Instrument Room

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
69
Q

What are the auto starts of the AES Fans?

A

ECCS Pump Starts
SI
(Train Specific)

Train Specific

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
70
Q

What accident condition will place the AES Fan in charcoal filter mode?

A

Phase B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
71
Q

Where do AES Fans take suction from?

A

Vestibule
CTS and RHR Hx Roms
SI, RHR, CCP and CTS Pump Rooms

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
72
Q

When moving fuel, what happens on a High Rad on RRC-330?

A

Fuel Supply Fans TRIP
Filter Bypass Damper gets a close signal
Charcoal filter inlet face dampers gets an open signal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
73
Q

If air is lost to VRV-315/325 for the control room chilers, how does it fail?

A

full flow to chillers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
74
Q

How do the control room dampers fail on a CRCV fire?

A

1/1A Closed
2/2A Part Open
3 Closed

Control Room Pressurization Fan also auto starts.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
75
Q

How do the control room dampers fail on a Hi Rad Alarm?

A

1/1A Closed
2/2A Part Open
3 Open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
76
Q

How do the control room dampers fail on a SI?

A

1/1A Closed
2/2A Part Open
3 Open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
77
Q

How are the control room dampers aligned on a toxic gas?

A

All dampers are manually closed!

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
78
Q

When cross-tying the 600 vAC buses 11B and 11C, how is it done?

A

Break before Make. Crosstie has to see the normal feeder breaker open. These come from the T buses, and may be out of phase, depending on the power supply to the T bus.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
79
Q

When cross-tying the 600 vAC buses BMC and CMC, how is it done?

A

Make before Break because they come from the RCP buses and will ALWAYS be in phase.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
80
Q

What is the purpose of the volts over herts alarm?

A

Telling operators that there is too much excitation which could lead to damage due to voltage. Will cause a trip if the turbine is not paralleled.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
81
Q

What voltage does the main generator exciter produce?

A

3 phase AC that gets rectified and sent to the main generator.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
82
Q

Where is 11PHA and 11PHC powered from?

A

11PHA - T11A
11PHC - T11D

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
83
Q

What is the power supply to the logic cabinets for Rod Control?

A

120 vAC which was stepped down from the 260 vAC from the MG Set Output.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
84
Q

What powers the CRIDs on a loss of all AC?

A

the 250 vDC Batteries

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
85
Q

What powers the slave relays for Train A?

A

CRID 1 (120 vAC)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
86
Q

What powers the slave relays for Train B?

A

CRID 4 (120 vAC)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
87
Q

What is the DIRECT result of pushing the emergency trip push botton?

A

Unit HEA trips

the button is in the UNIT

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
88
Q

What happens if the excitation breaker to the generator opens at power?

A

Excitation is lost and the HEAs will trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
89
Q

What prevents you from opening the exciter field breaker at power?

A

Interlocked with the generator output breaker.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
90
Q

When paralleling the EDG, how do you prevent becoming a load on the grid?

A

By making sure EDG frequency is slightly higer than the grid. (Slow in the fast direction)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
91
Q

What are the 3 parameters on the Generator Capability Curve?

A

Hydrogen Pressure
Vars
Megawatts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
92
Q

What is the purpose of the Thyristor / Converter?

A

to turn AC into DC
(fancy names for rectifiers)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
93
Q

What happens if the TSCUPS battery is lost?

A

Nothing. It is normally supplied by 11C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
94
Q

Where are the AB/CD battery chargers normally supplied from?

A

600v Vital Buses

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
95
Q

What happens to a pump if 250 vDC control power is lost?

A

Pump cannot be operated remotedly. Protective trips are also unavailable.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
96
Q

Where does the voltage regulator sense voltage?

A

At the output of the main generator

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
97
Q

How can you lower amperage to lessen heat if bus duct cooling temperature is a concern?

A

Get closer to Unity. So, in MVARs are in, raise voltage. If MVARS are out, lower voltage.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
98
Q

Where are the Generator output breakers powered from?

A

125 vDC Yard Power
Unit 1 is from 345 kV yard
Unit 2 is from 765 kV yard

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
99
Q

How is the anti-pumping circuit cleared?

A

Taking control switch to TRIP

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
100
Q

How does the protection scheme for BMC/CMC work if there is a high current sensed on the transformer?

A

Transformer output breaker (low side) opens
If the high current remains, then it is faulted and the HEA will trip
If no longer sensed, then the high side breaker will open and another signal is sent to reopen the low side.
11BCMC will close to repower the bus

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
101
Q

How do the master valves for CO2 fail on a loss of DC?

A

OPEN

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
102
Q

What is the maximum number of fire pumps expected to be running at any time?

A

2! For a unit 1 main transformer fire.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
103
Q

How do the selector valves for fail on a loss of DC?

A

CLOSED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
104
Q

If the invidividual selector switch is in isolate for CO2, what protection is available?

A

No automatic. Only manual.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
105
Q

How does CO2 put out a fire?

A

It displaces Oxygen

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
106
Q

Can the Before and After pump provide all the LO needed for the EDG while it is running?

A

NO! Engine/Shaft drive pump is required.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
107
Q

What trips are available to the EDG if 250 vDC is lost?

A

Worthington manual fuel valve
Mechanical Overspeed at 112% of 514 RPMs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
108
Q

Will the EDG stay running if the 250 vDC is lost?

A

Yep!

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
109
Q

What is the design of the fuel oil transfer pumps?

A

Both will start on low level and cycle off and on to maintain level

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
110
Q

If there is a hole in the downstream piping of the starting air receiver, will the EDG still start?

A

Yes! Only one starting air valve is needed, but the crosstie downstream gets air to all of the cylinders

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
111
Q

What are the indication that the field flash did not work?

A

No field volts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
112
Q

Why is the EDG INOP during surveillance testing?

A

A loadshed signal will not be generated.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
113
Q

What are the loads on the EDG 1 kV Inverter?

A

Field Flash Power
Local / Remote Control Transfer Relays
Dynalco Speed Transmitters
Bearing Temp Monitor (SG 40)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
114
Q

How do the EDG Starting air valves fail on a loss of control air?

A

As Is

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
115
Q

What will cause the EDG ventilation to start?

A

EDG Start or 95 degree room Temp

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
116
Q

What can cause the EDG supply/exhaust fans to stop?

A

CO2 Actuation, 70 degree room temperature or 30 minutes after EDG is shutdown

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
117
Q

What are the 3 parts to the Hi-Storm Dry Cask System?

A
  1. Hi-Storm Overpack
  2. MPC
  3. Hi-TRAC Transfer
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
118
Q

What main purpose does the MPC serve?

A

Confinement boudnary

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
119
Q

Why is helium used in the MPC?

A

Cooling, Inert atmosphere to prevent chemical reaction with fuel cladding and leak detection.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
120
Q

What is the purpose of the COC?

A

Approves the design of the dry cask storage system.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
121
Q

What produces most of the heat in the SFP ?

A

Fission products

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
122
Q

What is a support function of the SFP System?

A

Used to clean up the RWST

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
123
Q

How does a NESW pump respond to a loadshed with a CTS?

A

The pump will restart with the loadshed and then trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
124
Q

What happens to the NESW system on a Load Conservation?

A

LO Cooler WMOs close
NESW closes to CUVs, CIRs and MACS
Unit cross tie to the misc hder closes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
125
Q

What supplies control air to the strainer backwash for ESW?

A

Unit 1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
126
Q

What supplies a backup water supply to the Aux Feed Pumps?

A

East ESW Header = MDAFPs
West ESW Header = TDAFPs

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
127
Q

What would happen if ESW was lost to the CRAC?

A

They may trip without a Heatsink

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
128
Q

What does Containment Chill water provide cooling for?

A

CLVs, CUVs and CIRs
RCP MACs
SG BD Hx

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
129
Q

What is the purpose of the divider barrier seal?

A

Prevents flow of steam and air from bypassing the ice condenser

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
130
Q

What are the autostarts for the control room pressurization fan?

A

Either Unit SI (Train Specific)
High Radiation (Unit Specific)
CRCV Fire

131
Q

If control air is lost to VRV-315/325 (CR Vent Unit Chillwater Control Valves), How does it fail?

A

Full flow to the chiller

132
Q

What are the flow rates for the containment Purge system design?

A

Lower containment at 21,000 CFM
Upper containment at 11,000 CFM

133
Q

What is the flow path for the Purge supply and Exhaust?

A

Supply - Roughin Filter to Med Efficiency Filter to Steam Heater to Fan
Exhaust - HEPA Filter to Fan

*Fans are located on AUX BUILDING Roof

134
Q

How does a loss of control air to aux building ventilation effect the dampers?

A

Face Damper failrs Open
Bypass Damper Fails Closed

135
Q

What will autostart the CEQ Fan and make the valves reposition?

A

1.0 psi in containment on a separate signal than the Phase A

136
Q

How will VDC-207 (CONTAINMENT PRESSURE RELIEF VENTILATION UNIT INLET VOLUME DAMPER) fail is control air is lost?

A

Full Flow

137
Q

During refueling, the divider barrier and missile blocks separating the reactor cavity from the refueling cavity are removed. This causes higher flow rates in the purge exhaust system. What is the benefit of this?

A

Prevents the formation of vaport clouds on the water, which will keep the whiny refuelers from complaining.

138
Q

What will auto start the CCW Pump Fans?

A

Unit specific Load Conservation

139
Q

What are the key pressures for the compressed air system?

A

97 psig - Standby PAC Starts
90 psig - CAC Starts (sensed in wet air receiver)
85 psig - PA Hdr Isolation Valves Close
80 psig - manual reactor trip

140
Q

What trips the PAC?

A

Loadshed
Load Conservation
Overload
(Low LO Pressure, High LO Temp and a few other things that don’t matter as much)

141
Q

What trips the CAC?

A

DOES NOT LOADSHED
Overload, Low Oil Pressure, Low NESW Pressure

142
Q

What are the interlocks for the CAC Start?

A

NESW and Oil Pressures

143
Q

Where does the backup PAC tie into the air system?

A

Between the ring header isolations. If isolations are closed, it can still provide control air.

144
Q

What is the control air flowpath?

A

Intake to CAC to aftercooler/Moisture Sep to Wet Air Receiver to Filters and dryers to dry air receives to valves

145
Q

If there is a leak between the 2 units plant air header isolation valves, can control air still be provided?

A

YES! There are check valves.

146
Q

In standby alignment, which valves are normally opened and normalled closed for the CTS System?

A

Suction and Eductor Valves OPEN
Pump Discharge and SAT Outlet Valves CLOSED

147
Q

What signal starts the CTS Pump?

A

Phase B

148
Q

What signal repositions valves in the CTS System?

A

CTS Signal

149
Q

What is the purpose of using NaOH in containment spray?

A

Removes radioactive elemental iodinde from containment atmosphere during a DBA

150
Q

What would the potential side effect be if the contects of the SAT never made it into containment?

A

Corrosion

151
Q

What is the low end and high end of the 7-10 pH band for in the SAT?

A

Low - Keeps iodine in solution
High - Avoids chlroide and caustic stress corrosions on equipemnt

152
Q

What is the purose of the nitrogen blanket in the SAT?

A

Prevents diluting the NaOH

153
Q

What happens prior to the Low Low SAT Level and why?

A

SAT Outlet and Eductor Supply valves close to prevent gas binding the pump

154
Q

How is temperature of the hydrogen recombiners controlled?

A

Controlling the power to them

155
Q

What will autostart a hotwell pump?

A

Low pressure at 130 (110) psig

156
Q

What will autostart a CBP?

A

Low pressure at 325 psig

157
Q

When will hood spray automatically go in serivce?

A

Generator Load < 7.5% with Turbine Speed > 900 RPM

158
Q

What is the TS Minimum for the CST and the bases?

A

182,000 gallons for 9 hours steaming in Mode 3 assuming loss of offsite power

159
Q

What are the power supplies to the CBPs and HWPs?

A

RCP Buses
North - D
Middle - A
South - C

160
Q

What triggers the recirc valves for the CBP to open?

A

Flow Switch at the discharge of the pump

161
Q

For the low pressure heater strings, how much flow capaity is provedied by each sting?

A

LP 1 Heaters (3 of them) = 50% flow capacity each
LP Heaters 2-4 (2 strings) = 80% flow capacity each

162
Q

What is the purpose of CRV-224, LP Heater Bypass Valve? How much flow is it good for?

A

Maintains 210-240 psig at the MFP Suction
Good for 20% bypass flow

163
Q

What are the autostarts for the TACW Pumps?

A

Low discharge pressure at 155 (145) psig

164
Q

What are the TACW Loads?

A

Bus Duct Cooling
Hydrogen Coolers
Steam Packng Exhauster / Gland Steam Condensers
Exciter Coolers
Stator Water Coolers

165
Q

Where does TACW system tap into condensate at?

A

Between the discharge of the hotwell pumps and the excess flow line to the CSTs.

166
Q

How does open vs closed cycle effect TACW efficiency?

A

Open Cycle = more efficient
Closed Cycle = Less efficient bc rejectiong heat to Circ Water

167
Q

How is CMO-600 positioned for the various operational cycles of TACW?

A

Open Cycle = Full Open
Closed Cycle and Modified Cycle = Throttled as needed.

168
Q

What are the hardwired MFP Trips?

A

MR. SHIT
Manual
Rx Trip
SI
Hi Hih SG Level
IOPS at 110%
Thrust Bearing Wear

169
Q

What are the PLC MFP Trips?

A

Overspeed at 107%
Low Condenser Vacuum
Low Lube Oil Pressure (4 psig for 5 secs)
Low Suction Pressure (180 psig for 5 secs)
Low Trip Hdr Pressure at 800 psig

170
Q

When operating at different power levels, different steam sources are utilized for the MFPs. What are they for low and high power?

A

0 - 60% power = Main Steam
> ~60% power = Reheat Steam

171
Q

What will give a Feedwater Isolation?

A

SG High High at 67% on 2/3 on 1 SG
SI
Rx Trip (P-4) with Low Tave at 554 degrees

172
Q

What will autostart the MFP Seal Water Pump?

A

< 15 psid between the CBP Discharge and MFP Suction pressures

173
Q

What are the available water sources for the MFP Seal Water Pump?

A

Normal = CBP Discharge Pump
Alternate = MFP Seal Water pump from U1 CST or HWP Discharge

174
Q

What is utilized to set the DP Target on the MFPs?

A

Total Steam Flow

175
Q

How is actual MFP DP calculated?

A

Uses the highest of the Bypass Header Steam Pressures (UPC-102a/b) and the lowest of the FW Pressures (FPC-250a/b)

176
Q

What is the purpose of a thrust bearing?

A

prevents axial movement to prevent stationary and rotating blade contact

177
Q

What is the purpose of a thrust bearing?

A

prevents axial movement

178
Q

How do the runbacks work on a loss of a main feed pump for both units?

A

Unit 1 sets target to 625 MW. Not active until then. Runs back at 600 MW/Min
Unit 2 sets target to 752 MW. Not active until then. Runs back at 1000 MW/Min at first, then at 140 MW/Min

179
Q

If Main Steam pressure fails, How does Steam flow fail?

A

Steam pressure is density compensated. SF will fail the same direction as steam pressure.

180
Q

Can different SG Level channels be selected for control?

A

NO! Always the middle channel.

181
Q

When it comes to SG Water Level Control, what is dominant?

A

LEVEL! Always tries to get back to 43.8% if the failure ins’t too bad, and there is enough time.

182
Q

What are the setpoints for the SG PORVs and Safeties? What is the equivalent power?

A

PORV - 1025 psig
2 Safeties - 1065 psig
2 Safeties - 1075 psig
1 Safety - 1085 psig

Each PORV is worth ~ 2.5% power
Each Safety is worth ~ 5 % power

183
Q

What is the purpose of the lockout position on the SGSV Dump Valves?

A

allows closing dump valves with a SLI standing to prevent the release, since there is not way to reset the SLI signal (if its standing, its in!)

184
Q

What will give a SI?

A

1lb in lower containment 2/3
1775 psig 2/3
< 500 psig on 1/1 on 2 SGs
DP between steamlines > 100 psid with 1 SG lower than 2 others on 2/3 instruments

185
Q

What’s the design bases of the SG PORVs?

A

Prevents lifting the safeties and to Cooldown to RHR in manual

186
Q

If the CRID is on its Alternate source, what does operability look like?

A

Inverter INOP but CRID Bus is OPERABLE

187
Q

If a CRID is on CRP-3, what does operability look like?

A

CRID BUS and Inverter are both INOPERABLE

188
Q

What will give a Steam Line Isolation?

A

< 500 psig on 1/1 on 2/4 SGs
> 2.8 psig in containment 2/4
> High Steam Flow on 1/2 on 2/4 SGs with Low Low Tave at 541 degrees (P-12)

189
Q

How do SGSV Dump Valves fail on loss of air?

A

OPEN, which will close the SGSV

190
Q

How do SGSV Dump Valves fail on loss of power?

A

CLOSED, which will keep the SGSV open

191
Q

What is the TS Bases for the MS Safety Valves?

A

Ensures secondary Steam pressures will be limited to 110% of desired pressure during most severe anticipated operational transient

Backup for RCS primary Pressure

192
Q

How many PORV Rad Monitors are there?

A

2 monitors, 4 detectors

193
Q

How many PORV Rad Monitors are there?

A

2 monitors, 4 detectors located downstream of the PORVs

194
Q

When is the PORV Rad Monitor inoperable?

A

Any time the PORV is isolated (even if just manual from the control room)

195
Q

What are the autostarts of the MDAFP?

A

Both MFPs Trip (if switch is in auto)
AMSAC (if active. So > 40% on MPC-253/254)
Loadshed
Low Low SG Level 2/3 on 1/4 SG
SI

196
Q

What are the autostarts for the TDAFP?

A

Undervoltage on RCP Bus (1/2 on 2/4 buses at 88V)
SG Low Low 2/3 on 2/4 SGs
AMSAC (if active. So > 40% on MPC-253/254)

197
Q

How do you know if it is the electronic overspeed vs the mechanical overspeed that tripped the TDAFP?

A

If it is the electronic overspeed, drop 50 will clear once the seal in is reset after running the TTV closed.

198
Q

What is the difference bewtween a flow conservation signal and a flow retention signal?

A

Flow Retention protects against run out after a steam/feed break
Flow Conservation conserves inventory by closing the AFW Test Valves and SG BD Isolation Valves.

Flow Retention will override the Flow Conservation

199
Q

How is C-20 met to enable AMSAC?

A

2/2 first starge turbine impulse pressures > 40%

200
Q

What will actuate AMSAC?

A

Feed Flow < 25% on 3/4 (1 channel from each SG)

201
Q

What does AMSAC Do?

A

Trips the Turbine and starts all AFW Pumps

202
Q

What will a high radiation signal in the CCW System dO?

A

Close the vent valve on the surve tank. CRV-412. Once the high rad signal is clear, the valve may be reopened without any system realignments

203
Q

What will a high rad signal do on DRA-300? How is this different from DRA-353?

A

Closes DRV-350
Closes SGBD Isolations
Closes BD Sampling Valves

IF it is DRA- 353, ALSO trips the blowdown treatment pump

204
Q

Where is SG Level measured?

A

In the downcomer

205
Q

What could cause SG Level to shrink?

A

reduction in steam flow

206
Q

What could cause SG Level to swell?

A

increase in steam flow

207
Q

What are the Low Level SG Reactor Trips?

A

Unit 1
5%
15% with SF/FF mismatch of 0.71 Million Lbm/hr

Unit 2
22%
26% with SF/FF mismatch of 1.47 Million Lbm/hr

208
Q

How are SGSVs opened and closed?

A

Hydraulic to Open
Steam to Close

209
Q

How many acoustic monitors are there for the pressurizer Safeties?

A

1 for each safety.

210
Q

How many acoustic monitors are there for the pressurizer PORVs?

A

1 acoustic monitor. All PORVs share it.

211
Q

Where do the Moisture Seperator Drains Go?

A

To the same heater that the HDPs take suction from.
Unit 1 = 5 Heaters
Unit 2 = 4 Heaters

212
Q

Where do the Reaheater Coil Drain Tanks drain to?

A

The 6 Heaters

213
Q

What will trip a HDP?

A

Both Suction Valves Closed (Trip Middle HDP)
Low Low Level in suction Heater
Main Turbin Trip
Overload/Overcurrent

214
Q

What is the purpose of the Bleed Steam Air Assis Check Valves?

A

Close to prevent turbine overspeed.

215
Q

What is the purpose of steam dumps?

A

Non-Safety Related system to handle a step load reduction of 40% without the use of rod control

216
Q

What are the Turbine Trip and Load Rejection controllers based on for steam dumps?

A

Auctioneered High Tave

217
Q

What is the only CRID that has no steam dump loads?

A

CRID 3

218
Q

What is C9?

A

1 CW Pump Breaker Closed
CRID 2 Energized
3/3 Condenser Vacuums Greater than or equal to 20.6 in Hg

219
Q

If on the Load Rejection controller, how far will dumps bring you back in temperature?

A

Within 5 degrees of Tref

220
Q

What is the turbine trip control comparing Tave to?

A

T No Load (547 degrees)

221
Q

What is the load rejection controller comparing Tave to?

A

Tref

222
Q

What is the purpose of bypass interlock on steam dumps?

A

allows ofr 1 group of dumps to operate for a cooldown to go below P-12.

223
Q

What is P-12?

A

Blocking Signal that tells dumps to close unless bypass Interlock is selected.

2/4 Tave < 541 degrees

224
Q

How many groups of valves are available on the turbine trip controller? What are the temperature deviations that will cause those valves to trip open?

A

2 groups (6 valves)
Group one trips open at 10 degrees
Group 2 trips open at 20 degrees

225
Q

How many groups of drumps are available during a load rejection? How does the temperature deviation work on the load rejction controller?

A

10% rejection = 2 groups
30% rejection = 3 groups

Valves trip open at 9, 13 and 17 degree. Start opening at 5 degree deviation

226
Q

If on the steam pressure controller, what effect will there be if UPC-101 fails?

A

Hi = Cool down to P-12, or if interlock is already bypassed, 1 group opens until there is operator action.

Low = All open valves will close

227
Q

If there is a turbine trip and Tave fails high, what happens?

A

Valves will open to reduce temperature until 547 degrees. It won’t see that right away. Dumps will not close until P-12 is met.

228
Q

Will a failure of MPC-253 or MPC-254 affect steam dumps?

A

Not unless there is also a temperature deivaition. If on the turbine trip controller, it will have no effect either because it’s not being looked at.

229
Q

What is the purpose of the Generator brushes?

A

Make contact with the collector rings to cmplete the current flow path between the stationary and rotating coilds

230
Q

What are the SCW Trips for Unit 1 Main Turbine?

A

81 degrees C after 15 secs
Low Flow at 499 gpm for 10 secs
Low Oil Pressure at 36 psig for 10 secs

231
Q

What are the SCW Trips for the Unit 2 Main Trubine?

A

95 degrees C after 15 secs
Low Flow at 666 gpm for 10 secs
Low Oil Pressure at 28 psig for 10 secs

There is also a manual trip at 18 micro mhso/cm conductivity

232
Q

What are the autostarts for the SCW Pumps?

A

Unit 1 - 130 psig low pressure
Unit 2 - 80 psig low pressure of low flow of 845 gpm

233
Q

What is warmer, SCW or cold gas temp?

A

SCW is 3-4 degrees C greater than Cold Gas Temp to avoid condensation

234
Q

What is the auto makeup to the SCW Tank?

A

Demin Water

235
Q

What is the purpose of the teflon connectors use in SCW?

A

Provides electrical insulation between the stator bars and the system piping.

236
Q

During outages, how do we get air in the Main Generator?

A

Use CO2 to purge the hydrogen, then use air.

237
Q

What pressure is the hydrogen in the Main Generator online?

A

Unit 1 = 75 psig
Unit 2 = 60 psig

238
Q

What does the generator condition monitor look for?

A

products of combustion

239
Q

What is the puropuse of GSO-251 closing ?

A

closes at 50 psig to prevent a hydrogen leak into the turbine building.

240
Q

What will trip the seal oil vacuum pumps?

A

High tank level. Will restart when it recovers

241
Q

What is the purpose of hte Unit 1 seal oil recirc pump?

A

Recirc the contents of the seal oil tank to retard foaming and aid in degassin

242
Q

Which pump can the unit not survice the loss of for Unit 2 Seal Oil?

A

Air Oil

243
Q

How do the Unit 2 seal oil pressures work for Air, Vac and Hydrogen Oil ?

A

Air oil is 7 psi greater than generator hydrogen pressure

Vacuum Oil is 6 psig greater than air oil

hydrogen oil is equal to vacuum oil

244
Q

What is the flowpath for bus duct cooling for each unit?

A

Unit 1 is out the middle phase and back the North and South.

Unit 2 is out the South Phase and back the North and Middle.

245
Q

What will autostart a bus duct fan?

A

LOW FLOW!

246
Q

What are the hardwired Main Turbine Trips?

A

ASS MOISTURE
AMSAC
SI
SG Level High High
Manual
Overall HEA
IOPS at 110%
SCW Loss
Thrust Bearing Wear abnormal
Unit HEA
Reactor Trip
Emergency Trip

247
Q

What are the PLC trips for the Main Turbine?

A

Low Condenser Vaccum at 22.5 in Hg
Overspeed at 107%
Oil Pressure < 8 psig (14.7 psig) for 5 secs
Low EHC Header Pressure < 1100 psig
Low trip header pressure 2/3 < 800 psig
Loss of both DCS Power Supplies

248
Q

Which LO Pumps start on a Unit 1 Turbine Trip?

A

AC Suction Oil Pump
Turbning Gear Oil Pump
DC Backup Oil Pumps
DC Bearing Oil Pumps

ALL BUT LIFT PUMPS

249
Q

What do Unit 1 steam seals look like at a low power?

A

SRV-10, the pegging valve, will be throttled as necessary until ~50% power
SRV-11, the dump valve, will be closed.

250
Q

What autostarts the bearing lift pumps?

A

Unit 1 = Low Speed of Turbine
Unit 2 = Turbine Trip

251
Q

How do you adjust the galnd steam condenser vacuum?

A

Adjust the blower suction inlet orifice plate (sliding damper) position

252
Q

What is the purpose of backseating the Unit 2 Main Turbine?

A

Minimize packing leakage by isolating system pressure from the packing and stuffing box.

253
Q

When is the power load unbalance runback active?

A

> 40% 1st stage impulse pressure

254
Q

What does a power load unbalance runback look like?

A

30 MW at 1389 Mw/Min in MW OUT

255
Q

Where is IOPS powered from?

A

CRIDS 1, 2 and 3

256
Q

What is the load target on a OP or OT Delta T Runback?

A

30 MW

257
Q

Will a failure of all 3 PLC Speed sensore trip the Main Turbine?

A

ONLY when NOT paralleled.

258
Q

What is the purpose of the exhuase hood spray?

A

Prevents the LPT lades from overheating.

259
Q

What does MW IN mean?

A

Valves will move around to maintain a constant MW

260
Q

What does MW Out mean?

A

Valves will maintaing their position based on a curve. MW will swing around with lake temperature changes.

261
Q

what will autostart a CCP?

A

SI

262
Q

What is the bases for the maximum VCT Pressure? How about minimum?

A

37 psig - ensure adequate emergency boration flow
15 psig - during RCP operations for RCP seal # 2 flow

263
Q

What do QLC-451/452 do?

A

QLC-451 starts makeup at 14% and stops at 24%. It also Trips open to divert flow to the CVCS HUTs at 87%

QLC-452 starts diverting at 78% with a full divert at 87%

2/2 at 2.5% will give a Refueling Water Sequence, which will transfer suction of the CCPs over to the RWST

264
Q

What happens to the CVCS system on a Phase A?

A

LD Orifice valves close
LD CIVs Close
Seal Return Valves Close
CCW to XS LD Hx Closes

265
Q

What happens to CVCS on a SI?

A

Charging Hdr Isolation Valves Close
CCW to LD Hx Closes
CCP Recrics close for 2 secs then modulate on pressure (1812-1825 psig)

CCP Suction relaigns to RWST

BIT valves open

CCP Starts

266
Q

What must be done when emergency borating?

A

shift BAT Pumps to FAST manually

267
Q

What can cause flashing in the letdown line?

A

Chargin flow too low or QRV-301 too far open

268
Q

If QCM-250/350 fails closed, where is your seal leak off going?

A

PRT

269
Q

If QCR-300 or QCR-301 LD Containment CIVs fail closed, where does letdown go?

A

Assumin orific valves are still open with flow, then to the PRT

270
Q

What would cause the LD orifice valves to close?

A

Close when either LD Isolation valve QRV-111/112 are closed
Close if a CCP Breaker is open
Pzr Level 17%
Phase A

271
Q

At what temperature does the Demin Divert Valve (QRV-302) fail to the VCT?

A

143 degrees

272
Q

What is the purpose of the throttle valves in the ECCS injection loops?

A

Flow balancing to ensure all loops will get the same flow.

273
Q

What is utilized if Seal Injection is lost to the RCPs?

A

rcs via the thermal barrier

274
Q

What instruments do the CCP Recirc valves look at?

A

East CCP QMO-225 looks at NPP-151
West CCP QMO-226 looks at NPP-153

NR Pressurizer Pressure

275
Q

What is the concern if seal line resistance isn’t within it’s TS Value?

A

If it is too small, ECCS injection flow may be less than required for core cooling during a LOCA.

276
Q

What is the purpose of the reactor vessel head vent system?

A

remove noncondensable from the RCS

Sized to not exceed capability of one charging pump

277
Q

What are the interlocks for starting a RCP?

A

Bearing lift motor started closed
Bearing lift oil pressure > 510 psig

278
Q

other than the interlock met, what is needed to start a RCP?

A

No 1 seal DP > 215 psid
VCT Pressure > 15 psig
Cooling aligned

279
Q

What are the power supplies to the RCPs?

A

RCP Buses
1 - B
2 - C
3 - D
4 - A

280
Q

What is the purpose of the RCP Flywheel?

A

Helps remove decay heat immediately after the trip

281
Q

How many lines go in and come out of containment for CCW to the RCPS?

A

1 line in for both the bearing oil cooler and the thermal barrier
2 lines out, so that a thermal barrier leak can be isolated (it’d get all 4 RCPs)

282
Q

What is the seal injection flowpath for RCPs?

A

3 gpm thru #1 seal
3 gph thru #2 seal
100 cc/hr thru #3 seal

283
Q

What is the seal return flowpath for the RCPs?

A

1 seal to CCP suction (or VCT during outages)

#2 seal to the standpipe and then to RCDT
#3 seal to outlet of RCDT.

284
Q

When starting a RCP, what is the seal dp looking at?

A

CCP Pressure - VCT Pressure

285
Q

What are the normal parameters for the PRT?

A

100 degrees
83%
3-5 psig

286
Q

When in LTOP, what instruments feed into the PORVs?

A

WR RCS Pressure
NRV-152 controlled by NPS-122
NRV-153 controlled by NPS -121

287
Q

What will trip the Pressurizer backup heaters?

A

Loadshed (train specific)
Low Level at 17% in PZR
Overcurrent

288
Q

Which pressurilzer level insturment failure will close QRV-111?

A

Bistable channel failuer Low

289
Q

Which pressurilzer level insturment failure will close QRV-112?

A

control channel failure low

290
Q

Take time to study all level and pressure instrument failures

A

Bistable level channel failing high does nothin g
All level failures will eventually result in a reactor tirp on high pressurizer level in > P-7

If Pressurizer Pressure fails high, then 1/2 of an input to a PORV to open exists. Won’t open bc the confirmatory isn’t there

If a Pressurizer pressure fails low, then you may have at least 1 inoperable PORV

291
Q

What are the TS Values for the accumulators?

A

921-971 cubic feet
585-658 psig
2400-2600 ppm

Applicable in modes 1, 2 and 3 if > 1000#

292
Q

What are the TS Values for the RWST?

A

375,500 gallons
2400-2600 ppm
70-100 degrees

293
Q

What is the ECCS Acceptance Criteria?

A

Peak Clad temperature < 2200 degrees
Max Cladding oxidation < 17%
Hydrogen generation < 1%
Core maintains a coolable geometry
Long term cooling

294
Q

What does the design anaylsis assume for accumulators?

A

1 dumps all contents out the break, but core remains partiall covered.

295
Q

What is required to Open ICM-305, RHR Suction from the recirc sump?

A

IMO-310 RHR Suction from RWST AND IMO-215 CTS Suction from RWST CLOSED.

296
Q

What is required to Piggy back? (Open IMO-340)

A

On rceirc sump and not sendig water back to RSWT.

IMO-305, RHR Suction from Recirc OPEN and IMO-262 OR IMO-263, SI Recirc to RWST CLOSED

297
Q

What is required to open IMO-330, RHR to Upper Spray?

A

RHR Suction from Recirc valve IMO-305 OPEN

298
Q

What is required to open IMO-310, RHR Suction from RWST?

A

Not on Recirc Sump, Not piggy Backing, Not on RHR Spray
ICM-305, IMO-340 and IMO-33 all closed

299
Q

What is the low level trip for the RHR Pump?

A

9% RWST level with IMO-310/320 Open

300
Q

What is the interlock to open IMO-128 and ICM-129 (RHR Suction from Loop 2 HL)?

A

< 411 psig on RCS Wide Leg Pressure
IMO-128 looks at NPS-122
ICM-129 looks at NPS-121

301
Q

what does a high radiation signal on RRS-1000 do?

A

Trips closed RRV-285
Trips off the MT / WECT Pump selected for release

302
Q

How does a loss of CW Pumps effect your liquid waste system?

A

Trips the unit specific release valve RRV-286/287

303
Q

Where do floor drais on the 609 elevation and above go?

A

DWHUT

304
Q

Where do hard piped drains on the 609 elevation and above go?

A

CWHUT

305
Q

Where to floor drains on the 587 elevation go?

A

DW Sump Tank

306
Q

Where do hard piped drains on the 587 elevation go?

A

CW Sump Tank

307
Q

What will cause a GDT to swap to the standby tank ?

A

100 psig
Hi Hi Oxygen at 2.7% on the AOM

308
Q

What is the interlock to open RRV-306 for the waste gas release flow control valve?

A

at least 1 Unit 1 AX Fan running

309
Q

What will cause RRV-306 for the waste gas release flow control valve to close?

A

High Radiation on either unit vent stack rad monitors VRS-1500/2500
Loss of BOTH Unit 1 AB Exhaust fans

310
Q

What is the purpose of the variable gain unit in rod control?

A

Increases output at lower power because a given reactivity change at low power has a smaller effect on power than at high power

311
Q

What are the inputs to Rod Control?

A

Auctioneered High Tave
Auctioneerd High PRNI
MPC-253

312
Q

How fast do rods move in manual?

A

48 steps per minute

313
Q

How fast do the rods move for shutdown banks whe moved individually?

A

62 steps per minute, with no indication for C and D

314
Q

How fast do rods move in automatic?

A

8 steps per minute from 1.5 - 3.0 degrees
for 3-5 degrees, they move 32 steps per degree +8

315
Q

What is the purpose of bank overlap?

A

Provide a more uniform axial power distribution and more uniform DRW

316
Q

Where are rod bottom lights powered from?

A

CRP-3

317
Q

What are the conditionals for Rods?

A

C-1, Intermediate Range Rod Stop
- 1/2 IRNI > 18% (16%)
- Stops AUTO and MANUAL rod withdraw
- can be blocked based on P-10

C-2, Power Range Rod Stop
- 1/4 PRNI > 103%
- Stops AUTO and MANUAL rod withdraw
- C-2 blocked when ROD STOP BYPASS selected to alarming channel

C-3, OTΔT Rod Stop (Can’t be blocked)
- 2/4 PRNI 3% < trip setpoint
- Stops AUTO and MANUAL rod withdraw.

C-4, OPΔT Rod Stop (Can’t be blocked)
- 2/4 PRNI 3% < trip setpoint
- Stops AUTO and MANUAL rod withdraw.

C-5, Turbine Power Interlock (Can’t be blocked)
- MPC-253 < 15%
- Stops AUTO only rod withdraw

C-11 Control Bank D Rod Stop (Can’t be blocked)
- CBD @ 229 steps (cycle dependant)
- Stops AUTO only rod withdraw

318
Q

What happens to Rod Control if a PR NI Fails? What about MPC-253? How about Tave?

A

PR NI High: Rods Step In due to power rate of change. Rod Stop (C2) may prevent rods from stepping out on temp error (auto & manual)

PR NI Low: No effect unless affected instrument was previously auctioneered high.

MPC-253 High (Tref ˃ 577.9): Rods Step Out due to power rate of change and Tavg < Tref

MPC-253 Low (Tref ≤ 547): Rods Step In due to Power rate of change and Tavg > Tref

Tavg High: Rods Step In because Tavg > Tref

319
Q

What is the cause of the urgent failure when recovering a misaligned rod?

A

Generated in the other bank of rods in that power cabinet due to all lift coil disconnect switches open for that entire group

320
Q

What are the inputs into the subcooling meter?

A

Auctioneered High CETCs OR WR RTD
Auctioneered Low WR RVLIS Pressure

321
Q

Why is RVLIS pressure used in the subcooling meter calc?

A

Its located outside of containment and not susceptable to containment atmosphere during an accident.

322
Q

Per TS 3.4.11 (PORVs), what must be done with 1 or more inoperable PORV with manual control available?

A

Close block valve and maintain power on valve within 1 hour.

323
Q

What are the inputs to the waste gas vent hheader?

A

RCDT
CVCS HUTs
VCT
PRT
AGA
SRST