CIRC WATER Flashcards

1
Q

What are the CW Pump Trips?

A

Manual
Overload
Inst Overcurrent
UV on associated RCP Bus

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the De-icing flowpath?

A

From a single unit discharge vault (WMO-16/26), through the de-ice tunnel and out the middle intake tunnel (WMO-30 is closed).

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the indications of icing?

A
  • Circulating Water temperature ≤ 35°F.
  • Frazzle Ice
  • > 1 Foot of drawdown in the Forebay not caused by starting a CW Pump
  • Traveling screens high and/or extreme high differential pressure alarms are annunciating with little or no trash collection in the screen wash trash
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What systems support the CW System?

A
  • Chlorine Injection
  • Miscellaneous Sealing and Cooling Water
  • Screen Wash System
  • Vacuum Priming
  • 250v DC
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the CW System loads?

A
  • TACW Heat Exchanger
  • Main Condensers
  • Feed Pump Condensers
  • Radiological Liquid Waste
  • Turbine Room Sump- Overflow
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is necessary to meet T.S. 3.7.9, Ultimate Heat Sink?

A

UHS temperature limit of ≤ 86.9°F and the level should not fall below the level necessary for normal unit operation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When do the CW discharge valves auto open? Why?

A

With associated CW pump auto start to prevent pump run out

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Will CW discharge valves auto open on a manual CW pump start?

A

No, you must manually open the CW outlet valves on a Manual CW Pump start. This prevents pump runout

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When do the CW discharge valves auto close? Why?

A

On associated CW pump breaker opening. This prevents short cycling the system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When will a CW pump auto start?

A

On a failure of a running CW Pump, IF the control switch is in AUTO

(Running CW control switch in Run with the breaker open)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What are the CW pump power supplies?

A
  • 1D(2D) = CW Pump #11(21)
  • 1A(2A) = CW Pump #12(22)
  • 1B(2B) = CW Pump #13(23)
  • 2C = CW Pump #24
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What are the Circ Water discharge crosstie loads?

A

NESW
Chlorine Injection
Misc Sealing Cooling Water
Lawn Sprinkler System

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

If there is damage to the intake piping, how can we get water to the ESW pumps?

A

Via WMO-17/27, Circ Water Forebay Emergency Intake Shutoff Valves

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the safety related function of Circ Water System?

A

Provide water source to ESW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly