When are the MFPs forced to speed ctrl?

A
  • Both MS Press xmitters Fail
  • Both MFP Hdr # xmitters Fail
  • MFP DP Setpoint xmitter Fails
  • Other MFP Trip when > 60% Power
  • MFP Speed > 5220 (5300) rpm when its forced to speed ctrl
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What will override MFP Speed Ctrl on U2? Why?

A

MFP 1st Stage # Limiter to prevent excessive 1st stage pressure

- Will close down on control valves to prevent excessive 1st stage #. (@ 105# first stage # and 5300 rpm)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

When is MFP ΔP enabled?

A
  • Unit 1MFP Speed > 3650 RPM
    -Unit 2 MFP Speed > 3500 RPM
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What feeds the Steam Flow input for the DP Control for program DP?

A

Total Steam Flow selected Channels

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What transmitters feed the steam pressure portion for DP Control for actual DP?

A

UPC-102A/B (Bypass Steam header) (Higher of 2)

- FPC-250A/B (6A FW Htr outlet) (Lower of 2)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What parameter tells the Main Turbine that power is > 60%?

A
  • Actual Load
    Unit 1 > 626.4 MW
    Unit 2 > 730.2 MW
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the Hardwired (direct) Trips for the MFPs?

A

Manual
Rx trip
SI
Hi-Hi S/G level at 67%
IOPS (110%)
Thrust Bearing position

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What are the PLC Trips for the MFPs?

A
  • Overspeed (107%)
  • Low Condenser Vacuum ≤ 20.0 (15 for Unit 2) in Hg
  • Low Lube Oil press (4#) (5 sec TD)
  • Low Suction press (180#) (5 sec TD)
  • Low Trip Header Press (800#)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

At what percent power do we normally use Main Steam for the MFP motive force?

A

Until ~ 55-60% Power

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How is MFP DP Calculated?

A

By using the highest Bypass Hdr Steam Pressure and the lowest FW Pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What are the inputs to the MFP Speed Control System?

A

SG Pressure, FP Disch Pressure and TOTAL STEAM FLOW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

If there is an equipment issue with on of the MFP suction flow transmitter (fails low), what is affected?

A

Load Sharing and ELO Control