DC Electrical/Instrument Electrical Flashcards
250VDC Battery is sized to ensure how many hours during a Loss of Offsite Power (LOOP)?
3 Hrs
250VDC Battery is sized to ensure how many hours during a Station Blackout (SBO)?
4 Hrs
Per T.S. 3.8.4 D (D.C. Sources - Operating), If N Train DC electrical Power subsystem is INOPERABLE,
IMMEDIATELY Declare TDAFW inoperable
Per T.S. 3.8.4 E (D.C. Sources - Operating), If one or both required Unit 2 Train A and Train B electrical power subsystems inoperable,
IMMEDIATELY declare the associated ESW train(s) inoperable
Per T.S. 3.8.5 A (D.C. Sources - Shutdown), if required DC electrical power subsystem inoperable,
IMMEDIATELY Suspend core alterations, suspend fuel movement activities, do not reduce SDM or Boron concentration, initiate action to restore to operable
Per T.S. 3.8.6 F (Battery Parameters), if required Actions and associated Completion Time of Condition A, B, C, D, or E not met
OR
One or more batteries with one or more battery
cells float voltage < 2.07 V and float current > 2 amps
OR
SR 3.8.6.6 not met
IMMEDIATELY Declare associated Battery Inoperable
Per T.S. 3.8.8 A (Inverters - Shutdown ), if one or more required inverters inoperable,
IMMEDIATELY Suspend core alterations, suspend fuel movement activities, do not reduce SDM or Boron concentration, initiate action to restore to operable
If one of the two ground detection lights goes out, which one indicates the ground?
The one that is not lit indicates ground (Could be dimmer than the other as well)
Which 250V DC battery has more capacity than the others and why?
U1 CD Battery, because it has additional loads on it (WDS, Drumming Room, MUP, etc)
Where do the BOP battery Chargers get their power from?
600 V BMC/CMC
Where do the U1 AB battery Chargers get their normal power from?
11A via EZC A - AB Charger 1
11B via EZC B - AB Charger 2
Where do the U1 CD battery Chargers get their normal power from?
11D via EZC D - CD Charger 1
11C via EZC C - CD Charger 2
What is the 250V DC BOP Battery sized for?
2 hrs for Loss of Offsite Power (LOOP)
What load does not strip off the BOP battery? WHY?
Emergency Seal Oil pump to prevent H2 from leaking out of generator (explosion hazard)
If a battery is supplying loads without a charger connected, and the equipment loaded on battery does not change, what will happen to current draw (amps) as the battery is expended (voltage lowers)?
Rise steadily until the design battery capacity is exhausted