TB Vent Flashcards

1
Q

WHat is the purpose of TB Vent?

A

Maintain temps between 65F and 120F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

WHat are the general intended flow/pressure characteristics for TB Vent?

A

Flow from least to most contaminated w/ a dp of -0.25” WC between clean areas and areas potentially contaminated to prevent leakage out.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What will cause the trips of all TB Fans?

A
High Pressure (+2.2"WC) trips supply fans
Lo Pressure (-2.7"WC) trips all exhaust fans
Lo Flow trips - w/ standby fan autostart
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the supply fan power sources for N and S Turb Building Vent?

A

N Supply: A/C on 25, B on 26

S Supply: A on 28, B on 29

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How many supply fans are there for the three systems?

A

3 for North
2 for South
3 for East

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How many exhaust fans are there for the 3 TUrbine Building Vent Systems?

A

3 for North and South - Shared

3 for East

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are teh power supplies for North and South Turb Build Vent Exhaust Fans?

A

A - Bus 25
B - Bus 26
C - Bus 27

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What are teh power sources for the East Tb Vent Fans?

A

ALL 6 (3 supply, 3 exhaust) powered by MCC 26-4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

WHat alternate purpose can teh E. TB Vent Supply?

A

Can provide Cooling/Purge Air for AEER when needed (Backup to AEER Vent)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How is TB Vent System Monitored for Radiation?

A

The North and SOuth Exhaust to the 2/3 Chimney, which is monitored by the SPING. This is a major source of dilution air.
The East TB Vent is not monitored

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

WHat actions are needed to start a TB Vent Fan?

A

Hold Closed for 45 seconds - this bypasses low flow trips when held in closed.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Where does N/S TB Vent Exhaust to?

E TB Vent?

A

N/S exhausts out 2/3 Chimney

E Exhausts out north side of building (OR THROUGH RECIRC)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What areas are fed by N/S TB Vent?

A

CCSW/Cond Pp Areas, Clean Dirty Oil Tank Room, general TB areas

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What powers the CCSW/Cond Area Vent?

A

MCC 25-2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What powers the D Heater Area Booster Fan?

A

MCC 26-4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is in the air mixing box for E. TB Vent?

A

Filters, Hot Water Heating Coils

17
Q

What will cause cause an autostart of TB Vent Fans?

A

Lo Flow through running Fan

18
Q

What will caust an auto trip of TB Vent Fans?

A

Hi TB or RW Pressure - Trips Supply Fans

Lo TB or RW Pressure - Trips Exhaust Fans

19
Q

What redundant featers are available in TB Vent System?

A

ALl TB Vent systems provide redundant fans provided with auto start of standby fan if low flow through running fan is sensed by DP