RW Vent Flashcards

1
Q

What is the purpose of RW Vent?

A

Control the flow of air from least potentially contaminated to most contaminated to minimize spread of contamination

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What temperatures are intented to be maintained for RW Vent?

A

65 to 104F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are teh pressure characteristics of the RW Vent System?

A

Maintained at a negative pressure with respect to outside atmosphere to prevent outleakage (intended for all leakage to be into the building)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Where does the exhaust for RW Vent GO?

A

2/3 Chimney

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are power supplies to Supply and Exhaust Fans for RW Vent?

A

Supply : A MCC 27-2; B&C - MCC 27-5

Exhaust : A MCC 27-2; B&C - 27-4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How many supply and exhaust fans are there for RW Vent?

A

3 supply - 3 exhaust - normally only 2 of each running

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What will happen w/ loss of IA for RW Vent?

A

All AO Dampers close

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What interlock exists between RW Vent Supply and Exhaust Fans?

A

Exhaust Fan trip will trip supply fan

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How many RW Solidification supply and exhaust fans are there? Power Supply? intended building pressure?

A

2 of each - supply can’t run w/ out exhaust fan - 1 normally runs
Powered from Bus 20/30 MCCs
DP of -0.125”WC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How many Supply and Exhaust Fans are there for MR Vent? Power Supply?
Building Pressure?

A

2 exhaust, 1 supply - 1 exhaust and 1 supply normal
Bus 20/30 MCCs
DP -0.125”WC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the general interlock for MR Vent Fans?

A

Loss of Exhaust Fan starts standby and does not trip Supply fan

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What will trip RW Solid fans?

A

Exhaust fan trips will trip associated supply fan.

Smoke in exhaust duct (ONLY SYSTEM WITH THIS) will trip exhaust fan.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly