What is the purpose of the PRocess Rad Monitor System?
TO provide continuous indication of rad levels or releases, and provide indication, alarms and trips/actions when needed
What does the MSL PRM alarm?
Logic?
Required Action?
Power Supply?
Alarms: Indicate Gross fission product release Hi (1.5 x Normal) HI-Hi (3x Normal) Downscale Logic: 4 detectors in X-Area 1 out of 2 twice Downscale alarm on loss of power Action: Mech Vac Pp Trip Power Supply: A&C - RPS Bus A B&D - ESS Bus
Off Gas PRM Alarms: Logic: Action: Power Supply:
Alarms: Indicates release to environs
HI - per ODCM
HI-HI - per ODCM
Downscale
Logic:
1 upscale and 1 downscale OR 2 upscale
Downscale on loss of power - No action unless other is upscale
Action:
15 minute time delay:
Chimney Isol Valve closes (5406), Holdup Volume Drain closes, pressurized drain tank outless vlv closes, press. drain pump trips on lo vac
Power Supply:
A- RPS Bus A
B - RPS Bus B
15 min time delay powered by 24/48vdc
RB Vent Rad Mon. OR Refuel Floor/FP Mon Alarms: Logic: Action: Power Supply:
Alarms: Indicates abnormal rad material in exhaust plenum
Hi 4mR/hr (RB Vent) OR 45mR/hr (Refuel/FP Mon)
Downscale
Logic:
4 channels - 2 in RB Vent ; 2 on Refuel Floor
Any single upscale;
2 downscale from same area (Vent or Refuel Floor)
LOSS OF POWER TO ANY DETECTOR INITIATES TRIP
Action:
RB Vent Dampers Trip
RB Vent Fans Trip on Damper Closer
Auto Start SBGT
u2&3 DW & Torus Purge Fans Trip
Power Supply:
A- RPS Bus A
B - RPS Bus B
SWAP OF RPS POWER SUPPLY MAY CAUSE TRIP
IC Vent Alarms: Logic: Action: Power Supply:
Alarms: Identify Tube Leak Hi - 3-5mR/hr Downscale Logic: 2 detectors Downscale on loss of power Action: ALARM ONLY Power Supply: A - MCC 28-2 B - MCC 29-3
RBCCW PRM Alarms: Logic: Action: Power Supply:
Alarms: HI Downscale Logic: 1 Monitor in Hx Inlet Downscale on LOSS OF POWER Action: Alarm Only Power Supply: 24/48 VDC Bus 2(3B)
SW Rad Mon Alarms: Logic: Action: Power Supply:
Alarms: HI - On 901-2 and SWRM Skid Logic: 1 detector on 48" SW Discharge Header Downscale on LOSS OF POWER Action: Alarm only Has purge mode to clear debris on low flow detector trip if low flow returns in 30 min or if blockage is not clear in 3.5 min Power Supply: MCC 38-3 (via panel 2253-85
Liquid RW Discharge Canal PRM Alarms: Logic: Action: Power Supply:
Alarms: Samples effluent release line to discharge canal in RW buidling HI Logic: 1 detector near RW control Room Action: grab sample on HI alarm Power Supply: MCC 38-3 (via panel 2253-85)
RBOC PRM Alarms: Logic: Action: Power Supply:
Alarms: HI - 40mR/hr Downscale Logic: 1 dector on OPERATORS CAB Action: On hi signal - raising of main or aux hook will be inhibited - LOWERING IS STILL ALLOWED HI CAN BE BYPASSED in cab. Downscale is NEVER bypassed Power Supply: 120 VAC Crane Instrument Power