Fire - Water Flashcards

1
Q

Purpose of the Water FP System?

A

TO protect equipment and personnel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Where is the U2/3 DFP?

A

2/3 Cribhouse

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the rating for the 2/3 DFP?

A

3000gpm at 165psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the autostart pressure for the 2/3 DFP?

A

80psig sense at DFP discharge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What trips are present for the 2/3DFP?

A

Overspeed trip which is never bypassed

Low Oil Pressure trip which is bypassed on low pressure start

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the capacity of the 2/3DFP Day Tank?

A

275gallons - allows for 8 hours operation; refilled by U3 EDG Fuel Oil Transfer Pump (THIS WILL INOP 3EDG)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What provides starting power to 2/3DFP?

A

Own batteries

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What provides charging power to 2/3DFP batteries?

A

Battery Charger fed from MCC 20-2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What are the 3 positions for the 2/3 DFP controller?

A

OFF - MANUAL - AUTO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

In what positions will the DFP auto start?

A

Manual or Auto

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

How is the 2/3 DFP secured?

A

Only manual at DFP Panel?

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How many times is the 2/3DFP designed to attempt to start?

A

up to 5 additional crank and reset cycles (Up to 165 seconds)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the design capacity of the U1 DFP?

A

2500gpm at 145psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the autostart setpoint for the U1 DFP?

A

Pressure below 75psig.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What auto trip exists on U1 DFP?

A

Overspeed trip which is never bypassed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is capacity fo the U1 DFP Day Tank?

A

500 gallons providing 8 hours diesel operation

17
Q

Where is U1 DFP Battery fed from?

A

U1 RLC 17L

18
Q

What autostarts U1 DFP?

A

Low header pressure, loss of AC feed to charger

19
Q

What are 5 positions for U1 DFP switch

A

Off-Man 1-Man2-Test-auto

20
Q

How is U1 DFP secured?

A

Locally ONLY

21
Q

If Both DFPs are inoperable, what must be done?

A

Returned to service or supply backup fire water supply

22
Q

What is the autostart setpoint for U1 Screenwash pump?

A

Fire Header decreases to 70psig

23
Q

What is power source for U1 Screenwash pump?

24
Q

What are the relief valve setpoints for U1 and U2/3 DFPs?

25
How is the 2/3 DFP discharge valve operated?
Electrically disconnected in the open position. FIRE CODE DOES NOT ALLOW AO OR MO valves. would be powered by 250vdc TB2
26
What provides normal keepfill for FP?
Service Water
27
How do the Wet Fire Protection Pipes work?
Filled with water all the time, fusible link on nozzle breaks and allows water flow.
28
What areas are protected by Wet Piping?
``` Most normally accessible plant areas not covered by gaseous (water harmful) or heavy oil areas: EDG rooms Condensate Pmps CCSW pmps Clean/Dirty Oil Rooms HeaterBays 538ft ceiling RFP MG Sets CH Trackway SBO ```
29
What is a Deluge Piping System?
Not normally filled, uses spray nozzles. | Deluge valve tripped electrically from signal.
30
What electrical signal trips a deluge valve?
Xfrmr Differential current or sudden pressure heat detector push button pull station
31
What areas use Deluge Systems?
``` Turb Oil H2 Seal Oil 2/3 DFP U2& 3 Transformers CH Basement and 2/3 DGCWPs ```
32
What is a Pre-action piping system?
Not normally filled and uses closed sprinkler heads and deluge valves; used in areas that may be exposed to below freezing temps. signal opens deluge valve, but will not dischage unless fusible link broken
33
What areas have pre-action piping systems?
``` Unit HPCI Rooms Tb ground floor outside AEER U2 SA & IAC Area TB EHC Area U2 & 3 RB Hatchways U2TB Cable concentration area. ```
34
What are autostart setpoints for DFPs?
U2/3 - 80psig U1 - 75psig (Also loss of AC or 1 DC Feed) Screenwash - 70psig