Purpose of the Water FP System?
TO protect equipment and personnel
Where is the U2/3 DFP?
2/3 Cribhouse
What is the rating for the 2/3 DFP?
3000gpm at 165psig
What is the autostart pressure for the 2/3 DFP?
80psig sense at DFP discharge
What trips are present for the 2/3DFP?
Overspeed trip which is never bypassed
Low Oil Pressure trip which is bypassed on low pressure start
What is the capacity of the 2/3DFP Day Tank?
275gallons - allows for 8 hours operation; refilled by U3 EDG Fuel Oil Transfer Pump (THIS WILL INOP 3EDG)
What provides starting power to 2/3DFP?
Own batteries
What provides charging power to 2/3DFP batteries?
Battery Charger fed from MCC 20-2
What are the 3 positions for the 2/3 DFP controller?
OFF - MANUAL - AUTO
In what positions will the DFP auto start?
Manual or Auto
How is the 2/3 DFP secured?
Only manual at DFP Panel?
How many times is the 2/3DFP designed to attempt to start?
up to 5 additional crank and reset cycles (Up to 165 seconds)
What is the design capacity of the U1 DFP?
2500gpm at 145psig
What is the autostart setpoint for the U1 DFP?
Pressure below 75psig.
What auto trip exists on U1 DFP?
Overspeed trip which is never bypassed
What is capacity fo the U1 DFP Day Tank?
500 gallons providing 8 hours diesel operation
Where is U1 DFP Battery fed from?
U1 RLC 17L
What autostarts U1 DFP?
Low header pressure, loss of AC feed to charger
What are 5 positions for U1 DFP switch
Off-Man 1-Man2-Test-auto
How is U1 DFP secured?
Locally ONLY
If Both DFPs are inoperable, what must be done?
Returned to service or supply backup fire water supply
What is the autostart setpoint for U1 Screenwash pump?
Fire Header decreases to 70psig
What is power source for U1 Screenwash pump?
PC5
What are the relief valve setpoints for U1 and U2/3 DFPs?
150psig