Instrument Air Flashcards
What is the purpose of the Instrument Air System?
To supply clean, filtered, MOISTURE FREE compressed air for air operated control devices and instruments
What powers the IACs?
2(3)A - Bus 26 (36)
2(3)B - Bus 27 (37)
3C - Bus 37
What is the preferred configuration for IA lineup?
Preferred that set up with parallel output of the IA compressors, Units not cross tied together, with 2 IACs running on each unit.
If NECESSARY, what is the preferred IA cross tie line-up?
Set up lined through 2 check valves. This prevents a dual unit failure of the one unit’s IA header. Shift Manager Permission REQUIRED
What Unit IA system supplies the common site buildings?
Site Buildings supplied by U2 IAC
What is the purpose of the Service AIr Crosstie to the IA system?
Provides backup air supply from service air header
What is the automatic actions for the IA/SA Crosstie?
Crosstie auto opens within 30 seconds when 85psig sensed on Units main instrument air receiver
Once crosstie valve opens, solenoid must be manually reset with local pushbutton located on side of main receiver when pressure rises above 87 psig
What are the setpoints for SA-IA crosstie?
85psig auto opens
87psig may be manually reset
What cools the IACs?
TBCCW via temp regulating valve
What happens to the TBCCW Temp Regulating Valve on an IAC TRIP? Why?
The solenoid closes on an IAC Trip to prevent admitting “cold” water into a hot compressor potentially causing brittle fracture of the components
How many cooling circuits are there fore each IAC?
2 cooling circuits
2B,3B &3C: 1st- cools oil cooler, intercooler, bleed off cooler, 1st stage water jackets, 2nd stage water jackets
2nd: After cooler
2A: 1) oil cooler, low pressure elements cooling jacket and intercooler
2) high pressure element cooling jacket and aftercooler
3A: 1) Oil cooler and cooling jacket of low and high pressure compresser elements
2) Intercooler and aftercooler
What are the power supplies for the IAC Dryers?
2A: MCC 25-2 2B MCC 25-1 3A: MCC 35-2 3B: MCC 36-4 3C: MCC 38-2
What happens if the IA dryer discharge pressure drops below 60psig?
dryer bypass valve auto opens and Dryer Trouble Alarm annunciates
- ALL IA DRYERS HAVE THIS
- 2A/B&3A/C have reset pushbutton on dryer
- 3B has auto/close/open c/s needed to reset
What is the setpoint for IA Dryer bypass?
60psig
How does the U1 - U2 IA crosstie function? How is it normally aligned?
Normally PCV OOS and requires Shift Manager permission to be put in service
When in service, valve opens on downstream pressure of 95psig sense on U2 side of PCV (near U2 main receiver)