EDG Logic Flashcards
What are teh EDG Auto-Start Signals?
ECCS Initiation Signal from Core Spray Pump Start Logic
2# DW or -59” (No TD)
Undervoltage on Bus 4kV Bus
Undervotlage on Dash Bus
Main Feed Breaker for Dash Bus Open
BOTH Main and Reserve Feed Breaker to 4kV Bus Open
What is the MAXIMUM allowed time for EDG to be fully loaded after auto start?
30 seconds
What is the initation sequence for EDG?
Auto Start relay picks up and bypasses all breaker trips except Diff Current
ASR Picks up FSR
FSR sends start signal to EDG and bypasses all trips except Overspee and Diff Current
FSR Seals in
What is the condition of the ASR when auto-start signals clear?
Auto Resets
How fast must the EDG start on initiation signal?
13 seconds and fully loaded in 30 seconds
What is the Starting Sequence for EDG Aux Components?
Start Signal: Fuel Priming Pump Starts Governor Oil Booster Pump Starts Air Start Solenoid Opens Red Run Light on in MCR (ONLY THAT START SIGNAL RECEIVED) DG CWP STARTS
200RPM:
Immersion Heater De-energizes
Fuel Priming Pump Stops
Air Start Solenoid De-energizes
800RPM:
Vent Fan Starts
Field Flashes
900RPM - Ramps to 3300V, Flashing stops - goes to 4160V&60Hz
What happens to EDG Auxiliaries on EDG Start Signal?
Fuel Priming Pump Starts Governor Oil Booster Pump Starts Air Start Solenoid Valve Opens Red Run Light Comes on IN MCR DGCWP Starts
What does the EDG Red Run Light in MCR indicate?
Start signal received.
Does not necessarily mean that EDG is running
What happens to EDG Auxiliaries at 200RPM?
ESR relay defeats 15 second failure to start relay
Immersion Heater De-energizes
Fuel Priming Pump Stops
Air Start Solenoid De-energizes
90 Sec Timer starts - If Main Lube Oil <21psig after timeout - EDG Trip
What happens to EDG Auxiliaries on 800RPM?
Vent Fans Start
Field Flashed from DG 125VDC
What is the EDG Shutdown Sequence?
On stop signal (NOT TRIP)
Immediately - Field Excitation removed
6 minute cooldown timer begins - ECR keeps SDR energized fro 6 minutes
After 6 minutes: engine shuts down, DGCWP shuts down and 7 minute fuel rack to 0 time delay
Vent fan keeps running and must be manually secured
When does the ASR AND FSR start?
Autostart only
What happens during a Rx SCRAM or LOOP when DG is already loaded DG for Surveillances?
Change Droop to 5
Adjust DG Frequency to 60 Hz and voltage to 4160Hz
IF EDG WERE TIED TO GRID FOR SURVEILLANCE WHEN AUTO START SIGNAL IS RECEIVED, THE ONLY CHANGE WILL BE THE BYPASSING OF SELECTED ENGINE AND BREAKER TRIPS
What breaker interlock exists for the 2/3 EDG?
Cannot be closed on both 23-1 and 33-1 at same time
What is the sequence of occurence for 2/3 Breaker on units with LOOP/LOCA?
Don’t Close on me with ECCS on thee!
If U2 experiences a LOOP but no LOCA, EDG will start and close on U2.
If U3 then has LOOP LOCA, EDG will divorce 2 and close on U3;
If U2 then has LOCA, EDG will divorce U3 and run unloaded until Keylock switched by Operator