24/48vdc System Flashcards

1
Q

What is the purpose of the 24/48 vdc system?

A

Provide power to NI, PRM, SIV instrument under all plant conditions

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Where are the 24/48 vdc batteris?

A

Unit Battery rooms

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Where is the 24/48 battery charger fed from?

A

AC input from Instrument Bus

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is unique about the 24/48vdc system?

A

It is the only grounded battery system.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

For the 24/48vdc system how many knife switches are and how what do they connect in?

A

3 - Undervoltage, Overvoltage, voltmeter

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How is the 24/48vdc system configured?

A

It is a 2 pole system, positive and negative battery system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the undevoltage set for 24/48?

A

22.8V

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How many UV, OV, and Voltmeters are there for the 24/48 system?

A

2 of each. One per pole

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How many distribution panels are there associated with the 24/48 system?

A

2 per unit (2A and 2B)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What happens on a loss of 2A dist. panel (24/48)?

A

Loss of SRM channel 21&22, IRM channels 11 through 14 (mult. alarms.
Breakers that power SRMs and IRMs power Div II SIV level switches - therefore, half scram on RPS A
Sping goes downscale initially

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What happens on loss of 24/48 2B DP

A

Loss of SRM 23 & 24, IRM 15 thru 18; multiple alarms
Div I SIV Rosemont level switch - causes RPS B half scram
Loss of Power to RBCCW and Service Water Rad Monitors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What happens on loss of 24/48 VDC 3A DP?

A

Loss of SRM 21 & 22, IRM 11-14; multiple alarms

Reserve feed for 2/3 chimney monitor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What happens on loss of 3B 24/48 DP?

A

Loss of SRM 23 & 24, IRM 15 thru 18, multiple alarms

Loss of power to RBCCW and Service Water Rad Monitors

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Which Units Receive half scram signal on loss of 24/48?

A

Unit 2 Only - Loss of 2aDP - Div II SIV level switch power lost
loss of 2B DP - Div I SIV level switch power lost

How well did you know this?
1
Not at all
2
3
4
5
Perfectly