Service Water Flashcards

1
Q

What is the purpose of Service Water?

A

Provide strained river water of suitable water and quality for plant equipment cooling requirements.
TO achieve design objective:
Meets cooling requiremnt during Rx Shutdown mode
*****Cools RBCCW during ALL OPERATING CONDITIONS
Operate at higher pressure than any load it services
Provide inexhaustible supply of make-up water to Hotwell via STANDBY COOLANT SUPPLY so feedwater flow can be maintained

*****Provide cooling to auxiliary loads in RB, TB, and aux buildings during ALL modes of operation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Where does SW discharge from the plant?

A

2 headers:
36” non-contaminated Header
48” Contaminated Header - Monitored

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What support does SW provide for FP?

A

normal keep fill, EMERGENCY Packup

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What provides power to the Stanby Coolant Isolation MOVs?

A

MCC 25-1 (35-1)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How does SW provide backup to TBCCW for CRD pumps?

A

Manual swap to SW if TBCCW lost

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the power supply for the SW pumps?

A

Bus 23/24 (33/34)

2/3 SW Pump can be supplied by 24 or 34

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How many SW pumps must be running?

A

at least 2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How many SW strainers are there? Purpose?
Power?
When do they reposition?

A

3 in parallel to remove debris from SW Pp Discharge
Powered by 28-2
Strainers automatically clean when DP reach ~4-5psid or manually by pushing start P/ or placing Auto/Manual Switch in manual
On a High D/P, all three reposition at same time then backwash one at a time

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the largest heat load to SW?

A

RBCCW - and coolant must ALWAYS be maintained

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How is SW flow to It’s loads controlled?

A
TCV at outlet of:
RBCCW Hx
TBCCW Hx
Turbine Oil COolers
Control HVAC Condensers
Main Generator H2 Coolers
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What impact does a LOCA have on SW?

A

If all 3 pumps (2 units and 2/3) are running and supplied by the same unit, then the “A” pump will load shed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What provides power to the isolation valves in SW system?

A

Unit 250vdc MCC -

TBCCW Hx, H2 Cooler and SWC - to be isolated as non-essential laods during emergency conditions

How well did you know this?
1
Not at all
2
3
4
5
Perfectly