APRM Flashcards
What is the purpose of the APRM?
Provides a continuous indication of core thermal power in power range
Initiates rod blocks and scrams when reactor power approaches a limiting safety setting.
How many APRM channels are there? where do they receive signals from?
6 APRM channels.
21 LPRMs to APRM channels 1,2,&3
20 LPRMs to APRM channel 4,5,6
What is the power supply for the APRM Channels?
APRM Channel Recorders?
APRM 1,2,3 - RPS A APRM 4,5,6 - RPS B Recorder APRM 1,2,3 - ESS Recorder APRM 4,5,6 - IB Indicating lights on 5 panel apron from ESS Bus
What type of logic is included in the APRM circuit for RPS Scrams?
1 out of 2 taken twice.
Allows one in each channel to be bypassed without scram.
What is the purpose of the APRM Averaging Circuit
Produces a signal equal to the average of all LPRM inputs.
Where is the output of the APRM Averaging Circuit sent?
Directly to 902-5 panel recorders Back Panel Meters Assigned OPRM and RBM for power references Plant Process Computer Trip Units
How does APRM Averaging Circuit output relate to core power.
It is directly proportional to the core bulk thermal power
What is the purpose of the APRM Count Circuit?
Generates a signal to indicate the number of operable LPRMs that are assigned to an APRM channel
When TRIP does the ARPM Averaging Circuit Feed? and what are their results?
HI Trip - Rod Block
Downscale Trip - Rod Block
What TRIP does the APRM Count Circuit directly feed? What is the signal and what is the result?
INOP Trip - <50% LPRM assigned to one APRM channel Operable
Triggers alarm and Rod Block
The APRM INOP Trip is fed by the Count Circuit and if less than ____% LPRM are Operable for that channel an alarm comes in. How many LPRMs being inop/bypassed does it take for the alarm to come in?
50% - Alarm comes in after the 9th because one more will remove any margin
What is the TS requirement for LPRMs being operable and supporting APRMs?
Each APRM channel has to have at least 2 operable LPRMs per level (A,B,C,D) and 50% of its LPRM’s - TS Bases 3.3.1.1
On the APRM Count Circuit, what is the value of each LPRM? What is the minimum readout for APRM’s 1,2,3 to be OPERABLE?
Each LPRM is equal to 5%. APRM 1,2,&3 count readout will be 55% because they have 21 LPRMs assigned. Must have 11 available. 11 x 5% is 55%
What is the purpose of the APRM Flow Converter?
Provides flow signal for use in setting flow-biased rod block and scram trip functions.
What are the APRM Flow Converter Setpoints (Normal Operation - Dual Loop in RUN)?
Rod Block Flow Bias Setpoint - 0.56W+54% Rod Block Maximum (clamp) - 108% Scram Flow Biased Setpoint - 0.56W +66% Scram Maximum (Clamp) - 119%