APRM Flashcards

1
Q

What is the purpose of the APRM?

A

Provides a continuous indication of core thermal power in power range

Initiates rod blocks and scrams when reactor power approaches a limiting safety setting.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How many APRM channels are there? where do they receive signals from?

A

6 APRM channels.
21 LPRMs to APRM channels 1,2,&3
20 LPRMs to APRM channel 4,5,6

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the power supply for the APRM Channels?

APRM Channel Recorders?

A
APRM 1,2,3 - RPS A
APRM 4,5,6 - RPS B
Recorder APRM 1,2,3 - ESS
Recorder APRM 4,5,6 - IB
Indicating lights on 5 panel apron from ESS Bus
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What type of logic is included in the APRM circuit for RPS Scrams?

A

1 out of 2 taken twice.

Allows one in each channel to be bypassed without scram.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the purpose of the APRM Averaging Circuit

A

Produces a signal equal to the average of all LPRM inputs.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Where is the output of the APRM Averaging Circuit sent?

A
Directly to 902-5 panel recorders
Back Panel Meters
Assigned OPRM and RBM for power references
Plant Process Computer
Trip Units
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How does APRM Averaging Circuit output relate to core power.

A

It is directly proportional to the core bulk thermal power

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the purpose of the APRM Count Circuit?

A

Generates a signal to indicate the number of operable LPRMs that are assigned to an APRM channel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When TRIP does the ARPM Averaging Circuit Feed? and what are their results?

A

HI Trip - Rod Block

Downscale Trip - Rod Block

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What TRIP does the APRM Count Circuit directly feed? What is the signal and what is the result?

A

INOP Trip - <50% LPRM assigned to one APRM channel Operable

Triggers alarm and Rod Block

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The APRM INOP Trip is fed by the Count Circuit and if less than ____% LPRM are Operable for that channel an alarm comes in. How many LPRMs being inop/bypassed does it take for the alarm to come in?

A

50% - Alarm comes in after the 9th because one more will remove any margin

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the TS requirement for LPRMs being operable and supporting APRMs?

A

Each APRM channel has to have at least 2 operable LPRMs per level (A,B,C,D) and 50% of its LPRM’s - TS Bases 3.3.1.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

On the APRM Count Circuit, what is the value of each LPRM? What is the minimum readout for APRM’s 1,2,3 to be OPERABLE?

A

Each LPRM is equal to 5%. APRM 1,2,&3 count readout will be 55% because they have 21 LPRMs assigned. Must have 11 available. 11 x 5% is 55%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the purpose of the APRM Flow Converter?

A

Provides flow signal for use in setting flow-biased rod block and scram trip functions.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What are the APRM Flow Converter Setpoints (Normal Operation - Dual Loop in RUN)?

A
Rod Block Flow Bias Setpoint - 0.56W+54%
Rod Block Maximum (clamp) - 108%
Scram Flow Biased Setpoint - 0.56W +66%
Scram Maximum (Clamp) - 119%
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What are the APRM Flow Unit Setpoints for Single Loop?

A

Rod Block: 0.56W +49%
Rod Block Max (Clamp) : 108%
Scram (half) Hi-Hi: 0.56W + 61%
Scram Max (Clamp): 115%

17
Q

What are the Flow Unit Setpoints when Mode Switch is not in RUN

A

Hi - Rod Block - 11%

Hi-Hi - Half Scram - 14%

18
Q

How does the APRM/LPRM Flow Unit Logic Sequence function?

A

Recirc loop flow element signal sent to “summer” then to 2 flow converters
Flow converter feeds Trip signals and ouputs to APRM Channels, OPRM and Rod Block Monitors

19
Q

What Trips does the Flow Unit feed?

A

If Either of the 2 Flow Units have 110% flow - Hi Trip
The Flow Unit outputs are summed - If there is a 7.5% Mismatch - mismatch trip

Both trips result in Rod Block

20
Q

How does the Slope Bias Circuit Funtion?

A

Means that Rod Block and scram setpoints raised and lowered as a function of RR Pump Flow

21
Q

With no RR Flow, what are the Hi-Hi and Hi Flow Bias setpoints?

A

Hi - 54%

Hi-Hi - 66%

22
Q

How does the RPV Mode Switch Interact with APRM Trips and Setpoints?

A

It modifies the RPS Trips and Interlocks based on mode switch position.
Mode switch interlock ensures taht Rx Power will not exceed 14% when reactor is below 785psig (safety limit)

23
Q

What is the safety limit for core thermal power?

A

Below 685 psig limit is below 25% power

24
Q

WHat are the scram and rod block setpoint limits when not in RUN?

A

11% power - Rod Block

14% power - SCRAM

25
Q

What is the AGAF? limit?

A

It is a ratio of actual power to indicated power.

Must be within 2% nominal value per TS. <1 is conservative.

26
Q

Why is RR Loop flow used for the flow signal?

A

Used because it is steady and because core flow signal is noisy

27
Q

Where are NI Scram signals sent? Rod Block signals?

A

Scram signals to RPS

Rod Block Signals to RMCS

28
Q

What are the APRM INOP signals?

A

9 or more LPRMs Bypassed
Module Unplugged
Mode Switch out of Operate

29
Q

What is the APRM Downscale Trip?

A

6% - Rod Block - Bypassed when Mode Switch Out of Run

- Scram when companion IRM Hi-Hi

30
Q

What happens with loss of respective RPS?

A

Rod Block and 1/2 scram on loss of APRMs and flow converter

Power-plex shuts down

31
Q

What happens to APRM on loss of IB?

A

APRM channels 4,5,6 recorders blank

32
Q

What happens to APRM on loss of ESS Bus?

A

APRM channels 1,2,3 recorders blank and all APRM status lights de-=energize

33
Q

What happens to APRM on LPRM Detector Short Circuit or spike?

A

Causes increase in affected APRM and may cause Hi-Hi alarm if high enough