SPDS Flashcards

1
Q

What is the color scheme for SPDS?

A

Green - as expected/within limits
Yellow - Pre-alarm
Red - alarm
Cyan - invalid or Indeterminate

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What bar graphs display in SPDS?

A
Rx Water Level
Rx Pressure
DW Pressure
DW Temp
Torus Level
Torus Temperature
Rx Power
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What boxes display at the bottom of SPDS?

A
Core Spray
SRV
PCIS
Containment Radiation
Rad Release
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How does the Core Spray SPDS box respond to plant conditions

A

GREEN if:
No CS demand signal OR CS demand and flow sufficient from one pump
β€œON” if flow greater than 750gpm forward

Red if :
If CS demanded but flow insufficient

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How does the SRV SPDS box respond to plant conditions

A

Always Green unless Red

Red if :
ADS demand and ADS valve closed
No ADS, pressure less than lowest lift and SRV open
No ADS, pressure above lowest lift and no SRV open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What causes the reactor power bar grapgh background to turn red?

A

Mode switch placed in refuel or shutdown (or scram signal) and after 7 seconds, APRM still on scale;
Scram demand for >240 seconds and any SRM reads higher than 3E5cps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What inputs are used for the SPDS Water level module?

A

NR, MR, FZ, WR

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is used for the SPDS RPV Pressure Module, what is preference and why?

A

NR, MR A & B, WR

MR A is preferred because has its own RPV tap

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

SPDS, what causes SRV Status Box to change?

A

Open if any relief or safety valve opens (Uses acoustic monitors)
Always green unless REd
Red if - ADS Signal and less than 5 reliefs open
No ADS - Rx press >1112psig and no relieve open
No ADS Rx Press <50psig and any relieve open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the general limit for SPDS Cont Rad Module?

A

200R/Hr

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What causes SPDS Rad Release Module to change?

A

Always green unless red;

Red if any PRM High (U1 chimney, U2/3 chimney, RB Vent Stack)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is status change for the SPDS Primary Cont. Isolation Module:

A

Staus box to red if: Isolation demand signal for Grp I or Grp II demanded and isolation unsuccessful
STAYS GREEN if ONE OF 2 VALVES FAILS CLOSED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

SPDS Alarm Levels for different Parameters:

A

Param. Lo Lo Pre Al Hi Pre Al Hi Al
Rx Power - - 102% 122%
Rx Level 0in 20in 40in -
Rx Press - 925# 1040# 1060#
DW Press - - 1.5# 2#
DW Temp - - - 200F
Torus Level 11ft 14ft 16ft 27ft
Torus Temp - - 95F 110F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly