ARM Flashcards

1
Q

What is the purpose of the ARMs?

A

Warn of abnormal radiation levels in areas where radioactive material may be present, stored, handled or inadvertently introduced and to provide information regarding radiation levels at selected locations within the plant that are normally frequented by plant personnel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the purpose of a radiation source or “bug”?

A

provides a small non-zero reading to allow differntiating between a low rad level and a failed detector
a downscale alarm with a bug source would indicate an instrument failure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Where are teh ARM indicators?

A

Located on the back panel in the control room and indicate the local radiation level

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What alarms or indications of abnormal conditions are available in the MCR for ARMs?

A

902-3 Panel - Downscale or high trip - Common alarm

902-11 - AMBER Seal in light on trip unit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How are the 902-3 ARM alarms reset?

A

They can be reset by taking the normal/bypass switch on the 902-2 panel to “bypass”
when the condition clears the indicator trip unit must be reset on the unit itself

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How does a ARM trip unit function?

A

trip unit de-energizes relays on trip signal.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How does a loss of power impact the ARM Trip Unit?

A

Trip Unit de-energizes relays on a trip signal. Loss of power will give same indication as a High Rad condition and downscale condition.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Some ARMs have two inputs to the recorder, in order to provide a full range of indication. Example: Refuel Floor and Charcoal Adsorbers

A

Some ARMs have 2 inputs to the recorder, in order to provide a full range of indication. Example: Refuel Floor and Charcoal Adsorbers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Where is the ARM Bypass Switch

A

902-2 panel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How are ARM’s tested?

A

There is a trip check button on the back panel indicator

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is an ARM Aux Unit?

A

They are stationed at SOME of the ARM locations to provide a LOCAL alarm and indication of HIGH Level trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What ARM locations have Aux Units?

A
RFP rooms
517 RB (TIPS)
517 RB South Access
613 RB
RWCU Area
Stock COntrol Room
RW Control Room
RW Barreling Area
OGFB Charcoal Adsorber Vault
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the power for ARM System?

A

INSTRUMENT BUS - NOT 24/48vdc

How well did you know this?
1
Not at all
2
3
4
5
Perfectly