Reactor Protection System(IPX) Flashcards
What is the purpose of the Reactor Protection System?
Ensure the reactor core and primary system are prevented from exceeding their safety limits during normal operation and design bases anticipated operational occurrences, and to assist the Engineered Safeguards Actuation System in mitigating the consequences of an accident.
What features of the Reactor Protection System allow it to be reliable during all conditions?
- Diversification - several different methods are used to monitor the same parameter or indicate the same plant condition.
- Redundancy - multiple instrumentation channels are used to monitor the same parameter.
- Independence - each channel of measurement and each train of protection is physically and electrically independent.
- Failsafe - the system is designed to supply a trip signal upon failure. All bistables will supply an initiation single upon loss of power to the circuit or bistable.
- Isolation from Control Circuits - the protective system and control systems circuits are isolated from each other with isolation amplifiers.
What type of logic is used by the Reactor Protection System?
2 out of 4 logic
What is the purpose of the Reactor Trip System?
- Prevent core damage from an anticipated transient
- Limit core damage from infrequent faults
- Preserve the integrity of the Reactor Coolant System pressure boundary during limiting fault conditions
What is the purpose of the Solid State Protection System(SSPS)?
The SSPS combines input signals into required logic and generates Reactor Trip and Safeguard Signals as required.
What type of signals does the Solid State Protection System generate?
- Automatic reactor trips
- Safeguards actuations
A. Safety Injection
B. Phase A
C. Phase B
D. Main Steam Isolation
E. Feedwater isolation - Annunciators, status lights, computer inputs, and a means for semi-automatic testing of logic circuits
What is the purpose of the Reactor Trip Breakers?
The Reactor Trip Breakers interrupt power to the Rod Drive MG Sets, thus causing a reactor trip, based on input from the Solid State Protection System.
What is the basic design/sequence of the Reactor Trip Breakers?
- There are two Reactor Trip Breakers in series so only one breaker is required to open for power to be interrupted to the Rod Drive MG Sets.
- One Reactor Trip Bypass Breaker is in parallel with each Reactor Trip breaker.
What is the purpose of the Rector Trip Bypass breakers?
- When racked in, and closed, the Bypass Breakers will allow the Reactor Trip Breaker that it’s in parallel with to be opened without a reactor trip. This arrangement allows testing of the Reactor Protection System and Reactor Trip Breaker operation without having to shutdown.
What is the purpose of the Trip Plate(RED) located inside the Reactor Trip Breaker cubicle?
Trip Plate(RED) - this plate is used to ensure that the breaker is tripped prior to engaging the breaker racking tool. This plate must be depressed to allow opening the Racking Shutter.
What is the purpose of the Racking Shutter located inside the Reactor Trip Breaker cubicle?
The Racking Shutter covers the area where the racking tool is inserted. To lower this plated you must depress the trip plate and then pull down on this plate.
What other components/indications are located inside the Reactor Trip Breaker cubicle?
- Springs Charged/Discharged indicator window
- Push-to-Close pushbutton
- Manual Charging Lever for manual charging of springs
- Test-Connect-Disconnect position indicator
How many trip coils does each Reactor Trip and Bypass Breaker have, and what are they?
- Each Reactor Trip and Bypass Breaker have two trip coils.
- The two trip coils are:
A. Undervoltage Coil
B. Shunt Trip Coil
How do the Undervoltage Coils in the Reactor Trip and Bypass Breakers work?
- The Undervoltage Coil de-energizes to trip the breaker.
2. The UV Coil is energized from the SSPS and holds the UV trip plunger out against spring force.
How do the Shunt Trip Coils in the Reactor Trip and Bypass Breakers work?
The Shunt Trip Coil is de-energized when the breakers are closed. When energized, the ST Coil will move the trip plunger causing the breakers to open.