Feedwater System(CF) Flashcards
What is the purpose of the Feedwater System?
The Feedwater System takes condensate from the Condensate System(CM), heats it to improve efficiency and delivers it a the proper flow, temperature, and pressure to the steam generators to maintain the required steam generator water level.
What is the system designator for the Feedwater System?
CF
How many High Pressure Feedwater Heaters are there, and what is their capacity?
- There are two trains of HP Feedwater Heaters, each train containing one ‘A’ and ‘B’ Heater.
- Each heater train is 50% capacity
What is the capacity of the High Pressure Feedwater Heater Bypass Valve?
The bypass valve is 50% capacity
What is used to heat Feedwater in the ‘B’ Heater?
- Extraction Steam
- ‘A’ Heater Drains
- Drains from the MSR 1st Stage Reheat Drain Tank
What is the temperature increase across the ‘B’ Heaters?
Approximately 36F
What is used to heat Feedwater in the ‘A’ Heater?
- Extraction Steam
2. Drains from the MSR 2nd Stage Reheat Drain Tank
What is the temperature increase across the ‘A’ Heaters?
Approximately 37F
What is the final Feedwater temperature upon leaving the ‘A’ Heaters?
Approximately 440F
What is the purpose of the High Pressure Cleanup Valve, CF-26, and where does the flow path end?
- The High Pressure Cleanup Valve, CF-26, is used to cleanup main feedwater and condensate prior to feeding the S/Gs during startup.
- The HP Cleanup Valve directs water from the outlet of the HP Feedwater Heaters to the Upper Surge Tank Dome. The valve actually taps off of the HP Feedwater Heater bypass line.
What is the interlock between the High Pressure Cleanup Valve, CF-26, and the Low Pressure Cleanup Valve, CM-123, and why?
- The two valves cannot be closed at the same time.
2. This ensures that there is always a recirculation path available.
What is the interlock between the High Pressure Cleanup Valve, CF-26, and the Main Feedwater Pumps?
The High Pressure Cleanup Valve, CF-26, cannot be opened unless:
1. Feedwater Pump ‘A’ suction and discharge valves are open OR Feedwater Pump ‘B’ suction and discharge valves are open.
AND
2. Both Feedwater Pump Turbines’ Control Valves are closed.
These interlocks prevent over pressurization of the condensate piping downstream of CF-26, and to have a cleanup flowpath established before CF-26 is opened
How are the High Pressure Feedwater Heaters removed from service, as a train or individually?
They are isolated using a combined switch for both heaters in a train.
What is the purpose of the Feedwater Equalization Line?
The Feedwater Equalization Line provides a head for distribution of CF flow an tempering flow to the steam generators. There are four Feedwater lines for, one for each steam generator, and one tap for tempering flow to all four steam generators.
What is the purpose of the Steam Generator Feedwater Bypass Control Valve?
The S/G Feedwater Bypass Control Valve is used to control feed flow at low power conditions up to 15% rated flow.
What type of valve is the Steam Generator Feedwater Bypass Control Valve, and how does it fail?
- The bypass valve is pneumatically operated.
2. The bypass valve will fail closed on a loss of Instrument Air(VI)
How many solenoids have to lose power to cause a closure of the S/G Feedwater Bypass Control Valve?
There are two solenoids in series located in the single supply air line. If one solenoid loses power the valve will fail closed.
What will cause the S/G Feedwater Bypass Control Valve to automatically close?
The S/G Feedwater Bypass Control Valve will auto close on:
- CF Isolation Signal
- Associated Doghouse Hi-Hi Level
- Transfer of ASP to Local
What is the purpose of the Steam Generator Feedwater Control Valves?
The Steam Generator Feedwater Control Valves control feed flow when total feed flow is greater than or equal to 15% up to 100%.