Emergency Diesel Generators(EQC) Flashcards
What is the purpose of the Emergency Diesel Generators?
The Emergency Diesel Generators provide Emergency AC power to the equipment required to safely shut down the reactor in the event of a loss of normal power source. The Diesel Generators will also supply power to the safeguards equipment as required during a major accident coincident with a loss of normal power source.
What is the system designator for the Emergency Diesel Generators?
EQC
What is the basic description of the Emergency Diesel Generators?
- Each unit has 2 Emergency Diesel Generators.
- The diesel generator is a 16 cylinder diesel coupled to a 7700KW maximum output generator.
- The diesel generator is governed to run at 450rpm.
- The diesel generator is equipped with a turbocharger which serves to assist in fast starting the diesel generators.
What are the three major accident situations that the Emergency Diesel Generators are required to respond to?
- Safety Injection
- Blackout
- A combination of a Safety Injection and Blackout
How will the Emergency Diesel Generators respond to a Safety Injection?
The diesel generator will automatically start, accelerate to rated speed and voltage, and run unloaded. The diesel generator breaker sill not close to supply the bus if normal power is available.
How will the Emergency Diesel Generators respond to a Blackout?
The diesel generator will automatically start and accelerate to rated speed and voltage. The diesel generator breaker will close to supply the essential switchgear, and the blackout loads will be loaded onto the bus.
How will the Emergency Diesel Generators respond to a combination of Safety Injection and Blackout?
During a Blackout followed by a Safety Injection, the diesel generator will start and be loaded with equipment required during a Blackout. When the Safety Injection occurs the Blackout Only loads will be shed, and the Safety Injection Only loads will be started.
What is the Mission Time for the Emergency Diesel Generators?
The mission time for the Emergency Diesel Generators is 7 days. The engines are designed to run at maximum load continuously for 7 days without having to makeup to the liquid support systems.
What type of Diesel engine do we use?
- 16 cylinder
- 4-stroke
- Governed to run at 450rpm
4, Equipped with a turbocharger to assist in fast starting the diesel. - Made by Transamerica Delaval Corporation
What is the purpose of the Shutdown Cylinder?
The Shutdown Cylinder is used to isolate fuel to the engine when a trip signal is received.
How is the Shutdown Cylinder actuated?
Control Air is supplied to extend the Shutdown Cylinder piston to cut off fuel oil to the engine.
How long is the Shutdown Cylinder extended following a Diesel Generator shutdown?
2 minutes
What is the purpose of the Run/Stop Valve?
The Run/Stop Valve is used to stop the diesel generator, when depressed, by supplying 60psig air to extend the Shutdown Cylinder and close the fuel racks.
Does the Run/Stop Valve require AC or DC power to work?
NO
How does a start signal, normal or emergency, affect the Emergency Diesel Generator with the Run/Stop Valve depressed?
The start signal will reset the Run/Stop Valve allowing the Shutdown Cylinder to retract and the diesel generator to start regardless of the Run/Stop initial position.
What is the affect on the Emergency Diesel Generator operation if it was automatically started by the sequencer, and is subsequently tripped by the Run/Stop Valve?
If the diesel generator was started by the sequencer and subsequently stopped by the Run/Stop Valve, the valve will pop back out when the diesel decreases to 44% rated speed. If the signal that caused the sequencer to actuate is still present, the sequencer will attempt to restart the diesel.
What is the purpose of the Generator portion of the EDG?
The Generator converts the mechanical energy of the Diesel engine into 3 phase, 4160VAC, 60Hz power.
Where does the Generator receive its field flash from?
The Diesel Generator field flash is provided by it’s own 125VDC auxiliary power system.
What is the description of the Diesel Generator Breaker?
- The Diesel Generator Breaker is a 1200amp circuit breaker located in cubicle#18 of the essential switchgear ETA or ETB.
- The breakers’ control power is supplied from 125V bus EDE or EDF
What is the EDG Breaker closure logic following an automatic start due to a Blackout?
The EDG Breaker will close:
1. After load shed is initiated by the sequencer
AND
2. Diesel speed is greater than or equal to 95%
What is the EDG Breaker closure logic following an automatic start due to a Safety Injection?
The EDG Breaker will close:
- Only if a Blackout signal is present
- If initially closed while in parallel with the grid the EDG Breaker will trip open
What are the Diesel Generator Breaker trips?
- 86N, 86S, or 86B except during a LOCA
- Generator Neutral Lockout(86DGN)
- Instantaneous Overcurrent(50)
- Reverse Power(32) for 3-30 seconds
- Loss of Field(40)
- Sequencer LOCA when parallel to the grid
- Trip when the Diesel is shutdown
What is the purpose of the Governor?
The Governor is used to sense and control the diesel engine speed, and deliver fuel to the engine so as to maintain a constant operating speed.
What are the two modes of Governor operation and when are they used?
- Speed Droop Mode - used when operating in parallel to the grid.
- Isochronous Mode - used when the diesel is operating on an isolated bus.
When operating in the Droop Mode what are voltage and frequency a function of?
When operating in parallel with the grid, both voltage and frequency are a function of the grid.
When operating in Droop Mode what is the affect of adjusting the Voltage Regulator?
Adjusting the Voltage Regulator when in parallel with the grid determines reactive loading and power factor.
When operating in Droop Mode what is the affect of adjusting the Governor(Speed)?
Adjusting speed when in parallel with the grid determines how much real load is carried by the EDG.
What is the affect on Reactive Load and Power Factor when picking up Real Load while operating in the Droop Mode?
As real load is picked up, reactive load increases as well due to counterforce causing a reduction in voltage from the generator. This causes power factor to move in the leading direction.
What action is taken by the operator if a leading Power Factor is observed?
The operator should adjust the Voltage Regulator to raise voltage and obtain a lagging Power Factor.
When operating in the Isochronous Mode what are voltage and frequency a function of?
When operating with the EDG carrying the essential bus voltage and frequency are a function of the EDG.
When operating in Isochronous Mode what is the affect of adjusting the Voltage Regulator?
The reactive loading will only change if the number of loads on the bus is changed. The Voltage Regulator adjustments directly control voltage on the bus when operating in Isochronous Mode.
When operating in Isochronous Mode what is the affect of adjusting the Governor(Speed)?
Adjusting the EDG Governor will directly control speed and frequency because there is only so much load on an isolated bus.
How is the Governor response to changes in load when operating in the Isochronous Mode as compared to the Droop Mode?
When operating in the Isochronous Mode the Governor responds quickly to changes in load, unlike the Droop Mode.
How will a Diesel Generator’s frequency respond to a full load rejection while in the Isochronous Mode?
Speed(Frequency) will increase until the governor returns speed to its set value.
How will a Diesel Generator’s frequency respond to a partial load rejection while in the Isochronous Mode?
Speed(Frequency) will increase, but not to the magnitude if it were a full load rejection, until the governor returns speed to its set value.
What is the purpose of the Exciter-Voltage Regulator?
The Exciter-Voltage Regulator controls generator output voltage by controlling the amount of current supplied to the generator field.
Where is the Diesel Engine Control Panel located, and what indications/controls are located at the panel?
- The Diesel Engine Control Panel is located in the diesel room.
- The Diesel Engine Control Panel contains the D/G local annunciator panel, controls, indications for the D/G auxiliaries, D/G start/stop controls, and the mode selection controls.
Where is the Diesel Generator Control Panel, and what controls/indications are located at the panel?
- The Diesel Generator Control Panel is located in the diesel room.
- The Diesel Generator Control Panel contains indications and controls necessary to manually tie the D/G to the essential switchgear. The DGCP also contains the recording and timing equipment to measure D/G start and operating parameters.