Contaiment Air Release And Addiition System(VQ) Flashcards
What is the purpose of the Containment Air Release and Addition System?
The Containment Air Release and Addition System provides a means of controlling containment pressure between the administrative limits of +0.25psig and -0.08psig during normal plant operations, including startup and shutdown evolutions
What is the system designator for the Containment Air Release and Addition System?
VQ
Is the Containment Air Release and Addition System safety related?
The system is not safety related with the exception of the containment isolation valves.
What is the normal pressure band maintained inside Containment?
+0.25psig to -0.08psig
How many Containment Air Release Fans are there, and what is there flow rate?
- There are two Containment Air Release Fans
2. The normal flow rate is a maximum of 200-300cfm
What will cause a Containment Air Release Fan to trip?
Low flow 80cfm to prevent the fan from overheating
Will the Containment Air Release Fans trip on low pressure in the Containment to prevent exceeding the design vacuum limit?
No, they will continue to run regardless of the pressure in Containment
What it’s the purpose of the Containment Air Release Valve(VQ-10)?
- The Containment Air Release Valve modulates to control the release rate.
- VQ-10 is controlled from a controller in the Control Room at the HVAC panel.
What conditions must be met to open the Containment Air Release Valve(VQ-10)?
- Containment pressure is greater than 0psig
2. The VQ-10 controller has been re-zeroed by placing the controller in MANUAL and setting demand to zero.
What conditions will cause the Containment Air Release Valve(VQ-10) to automatically close?
- Containment pressure is 0psig decreasing
- High radiation is sensed in the VQ system ventilation exhaust(EMF-35 or EMF-36 trip 2)
- The VQ totalizer becomes inoperable
- Fails closed on loss of instrument air
What indications/controls are located on the Containment Air Release Valve(VQ-10) Controller?
- Used in Automatica Mode to set the discharge limit(max 350cfm)
- Totalizer measures the total volume released in SCF(zeroed with “reset total” button)
- Display toggles between flow rate, total flow, and valve position
What will cause the Air Addition Valve(VQ-13) to automatically close?
Containment pressure increasing to 0psig
What is the requirement to open the Air Addition Valve(VQ-13)?
Containment pressure less than 0psig
What will cause the Containment Air Addition and Release System Containment Isolation Valves to automatically close?
Containment Ventilation Isolation Signal(S sub h)
What is required to start an Exhaust Fan?
The heater breaker must be closed in the filter train for the exhaust fan for it to be allowed to start