What is the purpose of the Containment Air Release and Addition System?

A

The Containment Air Release and Addition System provides a means of controlling containment pressure between the administrative limits of +0.25psig and -0.08psig during normal plant operations, including startup and shutdown evolutions

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the system designator for the Containment Air Release and Addition System?

A

VQ

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Is the Containment Air Release and Addition System safety related?

A

The system is not safety related with the exception of the containment isolation valves.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the normal pressure band maintained inside Containment?

A

+0.25psig to -0.08psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How many Containment Air Release Fans are there, and what is there flow rate?

A
  1. There are two Containment Air Release Fans

2. The normal flow rate is a maximum of 200-300cfm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What will cause a Containment Air Release Fan to trip?

A

Low flow 80cfm to prevent the fan from overheating

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Will the Containment Air Release Fans trip on low pressure in the Containment to prevent exceeding the design vacuum limit?

A

No, they will continue to run regardless of the pressure in Containment

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What it’s the purpose of the Containment Air Release Valve(VQ-10)?

A
  1. The Containment Air Release Valve modulates to control the release rate.
  2. VQ-10 is controlled from a controller in the Control Room at the HVAC panel.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What conditions must be met to open the Containment Air Release Valve(VQ-10)?

A
  1. Containment pressure is greater than 0psig

2. The VQ-10 controller has been re-zeroed by placing the controller in MANUAL and setting demand to zero.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What conditions will cause the Containment Air Release Valve(VQ-10) to automatically close?

A
  1. Containment pressure is 0psig decreasing
  2. High radiation is sensed in the VQ system ventilation exhaust(EMF-35 or EMF-36 trip 2)
  3. The VQ totalizer becomes inoperable
  4. Fails closed on loss of instrument air
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What indications/controls are located on the Containment Air Release Valve(VQ-10) Controller?

A
  1. Used in Automatica Mode to set the discharge limit(max 350cfm)
  2. Totalizer measures the total volume released in SCF(zeroed with “reset total” button)
  3. Display toggles between flow rate, total flow, and valve position
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What will cause the Air Addition Valve(VQ-13) to automatically close?

A

Containment pressure increasing to 0psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the requirement to open the Air Addition Valve(VQ-13)?

A

Containment pressure less than 0psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What will cause the Containment Air Addition and Release System Containment Isolation Valves to automatically close?

A

Containment Ventilation Isolation Signal(S sub h)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is required to start an Exhaust Fan?

A

The heater breaker must be closed in the filter train for the exhaust fan for it to be allowed to start

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the purpose of the heater in the filter unit?

A

The heater is for temperature and humidity control

17
Q

How does the Operator Aid Computer average containment pressure?

A
  1. Uses eight narrow range and two wide range pressure transmitters
  2. If pressure is within narrow range span, then uses the average of the narrow range
  3. If pressure is not within the narrow range span, then it uses the average of the wide range
18
Q

What inputs will generate a Containment Ventilation Isolation Signal?

A
  1. Manual “Phase A”(1.2# Containment Pressure) - train related
  2. Manual “Phase B, VX Initiate, Containment Vent Isolation” - train related
  3. Safety Injection Signal
  4. EMF-38 and EMF-39L Trip 2 - Either will actuate both trains of containment ventilation isolation signal
19
Q

What affect will a Containment Ventilation Isolation Signal have on the Containment Air Addition and Release System?

A
  1. Air release in progress - CLOSES containment isolation valves. Fans trip on low flow.
  2. Air addition in progress - CLOSES containment isolation valves.
20
Q

What are the power supplies to the Containment Isolation Valves in the Air Release path?

A

VQ-2A: EMXK

VQ-3B: EMXB

21
Q

What is the power supply to the Containment Isolation Valves in the Air Addition line?

A

VQ-16A: EMXK

VQ-15B: EMXB

22
Q

How can you remember the power supplies for the containment isolation valves?

A

Outboard valves are EMXB and are both ‘B’ valves

Inboard valves are EMXK and are both ‘A’ valves

23
Q

What is the power supply to the Containment Air Release Fans?

A

A - MXK

B - MXZ

24
Q

What is the power supply to the Containment Air Release Filter Heaters?

A

Heater A - SMXA

Heater B - SMXB

25
Q

What type of alarms are associated with the Containment Air Addition and Release System, and where are they received?

A
  1. Alarms:
    A. Containment pressure annunciators: High, Hi-Hi, Low, and Lo-Lo
    B. Filter high temperature annunciators
  2. Alarms are received in the Control Room and on the OAC
26
Q

What components are contained in the filter units?

A
  1. One pre-filter
  2. One HEPA filter
  3. Three carbon trays
  4. A deluge connection