Low Pressure Service Water System(RL) Flashcards
What is the purpose of the Low Pressure Service Water System?
- Cooling and makeup water supply to various loads on the secondary side of the plant.
- Dilutes low level radioactive waste water.
- Provides discharge flow path for:
A. Nuclear Service Water(RN)
B. Cooling Tower Blowdown Water(RC), and draining
What are the Low Pressure Service Water outside loads?
- Cooling Tower Makeup
- Containment Chilled Water Chillers(YV)
- Low Pressure Service Water Pump Motor Bearing Cooling Water
- Exterior Fire Protection Pump(RY) Motor Bearing Cooling Water
What are the Low Pressure Service Water Turbine Building supplied loads?
- Generator Stator Heat Exchangers(KG)
- Generator Hydrogen Coolers(GH)
- Main Turbine Lube Oil Coolers(LT)
What are the Low Pressure Service Water Service Building Supplied Loads?
- Recirculating Cooling Water Heat Exchangers(KR)
- Station Air Compressor Aftercoolers(VS)
- Fire Protection Jockey Pumps(RF)
- Service Building Chilled Water Chillers(YW)
What is the system interrelation with Liquid Radwaste System(WL)?
The Low Pressure Service Water System provides dilution flow for liquid radwaste discharges, and provides the discharge path.
What is the affect of losing Low Pressure Service Water flow on a Radwaste discharge?
The discharge is terminated when Low Pressure Service Water flow falls below a predetermined setpoint.
What is the system interrelation with the Fire Protection System(RF)?
- If needed the RL system can supply suction to the RF Jockey Pumps.
- Also provides a discharge path for RF when used to cool E and F Instrument Air Compressors(VI) upon a loss of KR and/or RL.
What is the system interrelation with the Condenser Circulating Cooling Water System(RC)?
- Provides makeup to the Cooling Towers of approximately 15Kgpm. One pump supplies the makeup for both units at full power.
- Provides a discharge path for Cooling Tower Blowdown Water.
What is the system interrelation with the Nuclear Service Water System(RN)?
The Low Pressure Service Water system provides a discharge path for the Nuclear Service Water system.
What is the purpose of the Turnaround Valves?
The Turnaround Valves provide minimum flow protection for the RL Pumps by maintaining header pressure at approximately 66psig.
What is the failure position of the Turnaround Valves, and why?
The Turnaround Valves fail in the closed position to maintain supply header pressure for the loads on a loss of air.
How do the Turnaround Valves work to control header pressure?
- The Turnaround Valves are controlled by a pressure sensor at the strainer inlet.
- There are three Turnaround Valves arranged in parallel. Pressure is controlled by bypassing flow
to the discharge header. - The three valves open sequentially based on the Control Room controller output.
Where can the Turnaround Valves be operated manually?
- Control Room at 1MC-13
2. Locally
What system provides the air for the Turnaround Valves, and what is available to ensure the valves fail in the correct position?
- The Instrument Air System provides the air for the valve operators.
- Pressurized air tanks assure the valves close to ensure cooling to major loads when Instrument Air is lost.
How are the Turnaround Valves Manually operated using the valve handwheel?
- The holes in the valve actuator are aligned with the holes in the valve stem by turning the handwheel.
- With the holes aligned a pin is inserted through the holes.
- Turning the handwheel with the pins installed will turn the valve stem and position the valve.