Plant Modifications and Tag Audits Flashcards
What are Vital to Operations(VTO) Drawings/Documents?
Vital to Operations(VTO) drawings/documents are those deemed critical to support plant operations, maintenance, and testing.
What are the VTO Drawings/Documents listed in OMP 2-10?
- Mechanical Flow Diagrams
- Electrical One-Line/Three-Line Drawings
- Electrical One-Line list for 600V Breakers
- Electrical Low Voltage Breaker List
Where are the pending engineering change documents and drawings located in the Control Room?
Located at column CC-56 in the Control Room file cabinet
What is the purpose of a Safety Tag Audit?
A safety tag audit is a physical verification that the tags for clearances in effect greater than 30 days are in place and undamaged, and that components are in the position listed on the Tag List.
What is the frequency of Safety Tag Audits?
- Monthly
- Quarterly
- Yearly
What is required if there are discrepancies found during a Safety Tag Audit?
- If a large number of discrepancies are found, the extent of the audit will be increased to provide assurance that remaining clearances are correct.
- Damaged, illegible, or missing tags shall be reprinted and replaced, then documented on the details tab.
What is the Test Method for verifying compliance with Plant Status Control?
The Test Method for verifying compliance with plant status control is to perform an audit of the Plant Status Control and Test Tags.
What is the frequency of Plant Status Control Audits?
- Monthly - checks any tags in effect greater than 30 days
- Quarterly - checks any tags in effect greater than 30 days and directs completion of a Quarterly Audit that is reviewed by the Shift Manager.
- Annually(4th Quarter) - Adds checks for components out of normal position greater than 1 year and determines if previous evaluation is valid.
What is required if there are discrepancies found during the Plant Status Control Audits?
- Replace any Plant Status Control Tags that are found missing or damaged.
- If a component is found incorrectly positioned the Shift Manager shall be notified and proper paperwork completed prior to any repositioning.
When are Electrical Circuit Isolation Tags used?
- Electrical Isolation Tags are NOT utilized for personnel safety.
- Electrical Isolation Tags are used for isolations left unattended by the implementer.
What are some examples of components that would have an Electrical Isolation Tag?
- Lifted Leads
- Open Sliding Links
- Removed Fuses or Plugs
- Installed Temporary Jumpers
- Open Knife Switches
What color Electrical Isolation Tag is used by Operations and Maintenance?
- Operations - White Tags
2. Maintenance - Blue Tags
Where are Electrical Isolation Tags used, and where are they not allowed?
- Electrical Isolation Tags are not used in the Containment.
- Electrical Isolation Tags are used in all other locations, including the Annulus.
What is the definition of Operational Control?
Having the authority and responsibility to position/reposition and tag site equipment or devices.
Where is Operational Responsibility designated for specific components?
- The Equipment Data Base
2. Attachment 1 of SD 3.1.36