Diesel Generator Building Ventilation System(VD) Flashcards
What is the purpose of the Diesel Generator Building Ventilation System?
The Diesel Generator Building Ventilation system is designed to maintain the temperature of the D/G room within the minimum and maximum limits for equipment operation and personnel access for inspection, testing, and maintenance.
What is the system designator for the Diesel Generator Building Ventilation System?
VD
What is the purpose of the Diesel Generator Building Ventilation Normal Ventilation Fan?
The Normal Ventilation Fan runs continuously when the D/G is in standby to maintain room temperature between 60F and 110F.
Where is the Diesel Generator Ventilation Normal Ventilation Fan controlled from?
The Normal Ventilation Fan is started via a local pushbutton on the Ventilation Control Panel located just outside the D/G room.
Manually restarted after the D/G is shutdown
What will cause a trip of the Normal Ventilation Fan?
The Normal Ventilation Fan will trip on:
- Diesel Start
- CO2 Fire Protection Actuation
- Emergency Ventilation Fan Start(one or both)
What is the purpose of the Diesel Generator Building Emergency Ventilation Fans?
The Emergency Ventilation Fans maintain the D/G room between 60F and 120F when the D/G is in operation.
How many Emergency Ventilation Fans are there and what is their capacity?
- There are 2 Emergency Ventilation Fans for each D/G.
2. Each fan is 50% capacity, and develops 58,500 CFM.
What is the power supply for the Normal Ventilation Fan?
Non-essential 600VAC MCC MXZ
What is the power supply for the Emergency Ventilation Fans?
EMXE and EMXF
What is the affect of having the Emergency Ventilation Fan control switch in the AUTO position at the Ventilation Control Panel?
AUTO - Emergency Ventilation Fan will automatically start when the D/G starts.
What is the affect of having the Emergency Ventilation Fan control switch in the TEST position at the Ventilation Control Panel?
TEST - A diesel start to the fan circuit is simulated starting the fan.
What is the affect on the Emergency Ventilation Fans with the Bypass Fire Protection Switch in BYPASS?
The Emergency Ventilation Fans will automatically start if the D/G start, and the fans will continue to run if running even with a CO2 initiation signal.
What will cause an Emergency Ventilation Fan to automatically start?
- Diesel Start(manual or automatic)
- Local Control Switch in TEST
- Local Control Switch in PURGE
What will cause an Emergency Ventilation Fan to trip?
- Diesel Shutdown
2. CO2 Fire Protection Actuation unless D/G Sequencer signal is present.
What is the purpose of the Normal Ventilation Outside Air Damper, and how is it controlled?
The normal outside air damper supplies outside air during periods when the D/G is in standby, and the outside air damper has been welded open.