What is the purpose of the Condenser Circulating Water System?
- Removes energy from the Main and Feedwater Pump Turbine exhaust steam to condense the steam and add some degree of subcooling to the condensate
- Provides an alternate suction source to the Auxilairy Feedwater(CA) Pumps
What is the system designator for Condenser Circulating Water System?
RC
What is the purpose of the Condenser Tube Cleaning System?
Cleans the inside of the Main and Feedwater Pump Turbine Condenser tubes to help maintain cycle efficiency
What is the system designator for the Condenser Tube Cleaning System?
RA
What is the purpose of the Vacuum Priming System?
The Vacuum Priming System removes air from selected waterboxes in the Condenser Circulating Water System and from the Low Pressure Service Water end bells on the Hydrogen Coolers to maintain both systems full
What is the system designator for the Vacuum Priming System?
ZP
What is the purpose of the Cooling Tower Water Treatment System?
The Cooling Tower Water Treatment System maintains chemistry of the Condenser Circulating Water
What is the system designator for the Cooling Tower Water Treatment System?
YT
What is the general flow path through the Condenser Circulating Water System?
- Condenser Circulating Pumps take a suction on the outlet of the water boxes of the ‘A’ Main Condenser and discharge to the Cooling Towers
- Flow is normally directed to the top of all three Cooling Towers through the riser pipe which distributes water to the Hot Water Distribution Basin
- The Hot Water Distribution Basin distributes the water around the top of the Cooling Towers. The water then falls approximately 49 feet through the Splash Bars transferring heat to the surrounding air drawn in by the Cooling Tower Fans.
- Water collects in the Basin where it is directed to the outlet through screens that collect debris.
- Water flows via gravity to the inlet water boxes of the ‘C’ Main Condenser.
- The flow to the Main Condensers is split into two trains which flow through each of the condensers.
What is the purpose of the Main and Main Feedwater Pump Condensers?
- Maintains plant efficiency by providing a low pressure exhaust region for steam exiting the turbines
- Provides subcooling to the condensate to increase NPSH
- Heat sink for a load rejection
What is the design/purpose of the Condenser Circulating Water Pumps?
- 4 pumps per unit
- 3 are normally in service at 100% power
- 690,000gpm total capacity
What is the power supply to the Condenser Circulating Water Pumps?
A - 1(2)TA
B - 1(2)TB
C - 1(2)TC
D - 1(2)TD
What is the Condenser Circulating Water Pump interlock associated with each pump’s suction?
- The pump suction valve must be open to start the pump
2. The suction valve cannot be closed while the pump is running
What is the Condenser Circulating Water Pump interlock associated with the pump suction and discharge valves?
The suction valve must be open before, and closed after, the discharge valve
What is the Condenser Circulating Water Pump interlock associated with the number of condenser trains in service?
Only two pumps can start if half of the main condenser is isolated(one train isolated)