Condenser Circulating Water(RC) Flashcards
What is the purpose of the Condenser Circulating Water System?
- Removes energy from the Main and Feedwater Pump Turbine exhaust steam to condense the steam and add some degree of subcooling to the condensate
- Provides an alternate suction source to the Auxilairy Feedwater(CA) Pumps
What is the system designator for Condenser Circulating Water System?
RC
What is the purpose of the Condenser Tube Cleaning System?
Cleans the inside of the Main and Feedwater Pump Turbine Condenser tubes to help maintain cycle efficiency
What is the system designator for the Condenser Tube Cleaning System?
RA
What is the purpose of the Vacuum Priming System?
The Vacuum Priming System removes air from selected waterboxes in the Condenser Circulating Water System and from the Low Pressure Service Water end bells on the Hydrogen Coolers to maintain both systems full
What is the system designator for the Vacuum Priming System?
ZP
What is the purpose of the Cooling Tower Water Treatment System?
The Cooling Tower Water Treatment System maintains chemistry of the Condenser Circulating Water
What is the system designator for the Cooling Tower Water Treatment System?
YT
What is the general flow path through the Condenser Circulating Water System?
- Condenser Circulating Pumps take a suction on the outlet of the water boxes of the ‘A’ Main Condenser and discharge to the Cooling Towers
- Flow is normally directed to the top of all three Cooling Towers through the riser pipe which distributes water to the Hot Water Distribution Basin
- The Hot Water Distribution Basin distributes the water around the top of the Cooling Towers. The water then falls approximately 49 feet through the Splash Bars transferring heat to the surrounding air drawn in by the Cooling Tower Fans.
- Water collects in the Basin where it is directed to the outlet through screens that collect debris.
- Water flows via gravity to the inlet water boxes of the ‘C’ Main Condenser.
- The flow to the Main Condensers is split into two trains which flow through each of the condensers.
What is the purpose of the Main and Main Feedwater Pump Condensers?
- Maintains plant efficiency by providing a low pressure exhaust region for steam exiting the turbines
- Provides subcooling to the condensate to increase NPSH
- Heat sink for a load rejection
What is the design/purpose of the Condenser Circulating Water Pumps?
- 4 pumps per unit
- 3 are normally in service at 100% power
- 690,000gpm total capacity
What is the power supply to the Condenser Circulating Water Pumps?
A - 1(2)TA
B - 1(2)TB
C - 1(2)TC
D - 1(2)TD
What is the Condenser Circulating Water Pump interlock associated with each pump’s suction?
- The pump suction valve must be open to start the pump
2. The suction valve cannot be closed while the pump is running
What is the Condenser Circulating Water Pump interlock associated with the pump suction and discharge valves?
The suction valve must be open before, and closed after, the discharge valve
What is the Condenser Circulating Water Pump interlock associated with the number of condenser trains in service?
Only two pumps can start if half of the main condenser is isolated(one train isolated)
What is the Condenser Circulating Water Pump interlock associated with the Cooling Tower inlet isolation valves?
Only one pump can start if only one Cooling Tower inlet isolation is open
What is the Condenser Circulating Water Pump interlock associated with an isolated flow path?
No pumps can start if the main condenser is isolated OR all three cooling tower inlet isolation valves are closed
What is the Condenser Circulating Water Pump interlock associated with each pump’s discharge valve?
- When the pump discharge valve is closed, the pump will trip
- Each pump’s discharge valve will close automatically if the pump is secured
- The pump’s discharge valve will open automatically 6 seconds after its associated pump starts
What is the Condenser Circulating Water Pump “Norm-TV” interlock?
A key-switch and valve selector switch is provided for the discharge valves of RC pumps. When selected the discharge valve position will be lifted to 42 degrees open following a pump start to prevent runout.
What is the design/purpose of the Cooling Towers?
- 3 Cooling Towers available per unit
- 13 fans per tower
- 3 Towers normally in service at 100% power with all fans running
What are the power supplies for the Cooling Tower Fans?
A - 1HTA
B - 2HTA
C - 1HTA or 2HTA
What is the Cooling Tower interlock associated with the DC brake?
- The fans cannot be started if the DC brake is not functioning
- When a fan is shutdown the DC brake will energize
What is the Cooling Tower interlock associated with vibrations?
High vibrations will trip a running fan
What is the Cooling Tower interlock associated with low temperatures?
The “LOW TEMP AUTO TOWER SHUTDOWN” automatic shutdown of the cooling tower fans will occur based on RC cold water temperature as long as the system has been enabled on the OAC by the operator. This is to keep RC cold water temperature greater than 65F.
What is the difference between safe standing ice and unsafe standing ice?
Safe ice is a buildup of ice on the Cooling Tower louvers that doesn’t cover and hang over the side of the louver.
What is the purpose of Cooling Tower Blowdown?
- Used to prevent over-concentration of chemicals in the RC system
- Discharges to the Low Pressure Service Water(RL) System
- Approximately 5000gpm
Where does Cooling Tower Makeup come from?
Cooling Tower Makeup comes from the RL system to makeup for all evaporation losses and blowdown
Which condensers utilize Condenser Tube Cleaning Pumps Reinjection Pumps?
Only the main condenser uses RA Reinjection Pumps
What is the purpose of the RA Reinjection Pumps?
- Two Reinjection Pumps power section of the Main Condenser
- Transport the balls from the upper quadrants to the lower quadrants of the ‘A’ condenser section
What is the purpose of the RA Recirculation Pumps?
- Two Recirculation Pumps per section of the main condenser and one Recirculation Pump per CFPT
- Transport the balls from the ball extraction tubes of the bottom quadrants through the ball collectors to the condenser inlets
What is the purpose of the RA Ball Collectors?
Located between recirculation pumps and the injection nozzles and are used to collect RA balls for surveillance and system shut down
Which Condenser Train has the best vacuum?
The ‘C’ Condenser train has the best vacuum because that is where circulating water enters first