Ship Blackout Flashcards

1
Q

Em gen doesn’t start, procedure for paralleling generators manually?

A
  • Carryout normal pre start checks
  • Start up generator in manual and check
  • Check the voltage of the incoming generator to confirm excitation. If not excitation then check AVR
  • Check reverse power and overload trips are reset
    Check the incoming machines frequency, this should be slightly higher
  • Switch on check synchroniser
  • Switch on syncroscope
  • Close the breaker when the incoming machine is at 10 to 12 on the syncroscope
  • Once load has taken switch off syncroscope
  • Balance the load
  • Monitor both generator loads, pressures and temps