Generators Flashcards

1
Q

What power are your generators?

A

2 x Zenoro ( John Deere) 6068AFM85, 250kw, 3 phase, 400/230v, 450A, 50hz 4 stroke, 4 cylinder inline

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How are your generators wired?

A

Standard 12 wire reconnectable winding, 3-phase brushless,
2/3 pitch windings

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

No excitation off the generators, what would you do?

A
  • Check that the AVR is not in fault
  • Check that the alternator and prime mover are not damaged or in fault
  • Check that none of the generator trips have happened
  • Refer to the manufactures manual, looking at electrical drawings to assist in troubleshooting
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the types of generator excitation?

A
  • Self excitation (static exciter)
  • Brushless excitation
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Manually parallel generators procedure?

A
  • Carryout normal pre start checks
  • Start up generator in manual and check
  • Check the voltage of the incoming generator to confirm excitation. If not excitation then check AVR
  • Check reverse power and overload trips are reset
    Check the incoming machines frequency, this should be slightly higher
  • Switch on check synchroniser
  • Switch on syncroscope
  • Close the breaker when the incoming machine is at 10 to 12 on the syncroscope
  • Once load has taken switch off syncroscope
  • Balance the load
  • Monitor both generator loads, pressures and temps
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Explain active and reactive power?

A

True power (kW) is based on the generators ability to share the total load evenly between each other. Meaning each generator will always have 50% of the load. Reactive power (kVAr) is the level of excitation each generator is providing to overcome its power factor.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the switchboard safeties and how do we test them?

A
  • Circuit breakers can be tested by operating the on and off switch
  • Fuses but are a one time uses
  • Preferential trips, by increasing the load on the generator
  • Reverse power trip can be tested by increasing the load on one generator and decreasing on the other until the generator starts to become a motor
  • Overspeed, can be tested by increasing the amount of fuel being delivered to the engine.
  • Emergency stop by pushing the button
  • Ground fault protection device can be tested by activating the test function on the device
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What are preferential trips and how would you test them?

A

Preferential trips are when a generators load is too high, the switchboard will then remove non essential loads such as an A/C compressor, a boiler, pool heaters, jaquizzi heaters, laundry and galley. This is to prevent the vessel from blacking out.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Explain how a generator produces electricity?

A

The prime mover rotates the rotor inside the stator windings. As the rotor spins it creates a magnetic field, which are then cut across the stator winders, inducing voltage.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Explain reverse power trip?

A

Reverse power trip can be tested by increasing the load on one generator and decreasing on the other until the generator starts to become a motor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What are some of the generator safety devices?

A
  • Overloading will allow preferential trips to go, stopping the vessel from blacking out
  • Shut down alarms for high temperatures and low pressures
  • Emergency stop
  • Overspeed shut down
  • Reverse power
How well did you know this?
1
Not at all
2
3
4
5
Perfectly