Electrical Flashcards
Megger testing? Minimum values? Where is it listed?
Used to measure the insulation resistance of electrical equipment. It involves applying a high voltage between the conductors and the ground and measuring the resistance to current flow.
Min 1 megga ohm
The Institute of Electrical and Electronics Engineers (IEEE)
IEC (nternational Electrotechnical Commission standards
Describe a megger test of your main alternators?
- Disconnect the main alternators
- Connect the terminals, one the the alternator winding, one to the alternator frame/ ground
- Apply the test voltage
- Record insulation resistance reading
- Compare to guidelines
What is phasing?
In three-phase power systems, there are three alternating currents (AC) that are 120 degrees out of phase with each other. Each phase is represented by a sinusoidal waveform, and they are labeled as phase A, phase B, and phase C.
What classification requirements are there for electrics?
- Compliance with international standards such as IEC (International Electrotechnical Commission) 60092 series, which covers electrical installations in ships
- Adequate insulation and protection against electrical shock hazards
- Protection against overcurrent, short circuits, and overvoltage conditions to prevent equipment damage and ensure system safety
- Requirements for emergency power systems
- Implementation of explosion-proof, flameproof, or intrinsically safe electrical equipment
How to megger test a motor?
- Disconnect the motor
- Connect the terminals, one the the motor winding, one to the motor frame/ ground
- Apply the test voltage
- Record insulation resistance reading
- Compare to guidelines
what types of earthing systems are fitted onboard a vessel?
- Return Earth
- Grounding to ships hull
Earth fault alarms?
Earth fault alarms continuously monitor the electrical circuit for any imbalance in current flow between the phases and the earth. It then alarms once above the limit. Onboard ours are set at 7amps and high high is 10amps.
Describe some common electrical faults?
- Short circuit
- Earth fault
- Overload
- Corrosion
- Blown fuses
- Connections vibrating loose
- Water
How would you test for common electrical faults them?
- Visual inspections
- Insulation resistance testing with a meggar tester
- Continuity test with multimeter
- Earth fault half test
- Load testing equipment
- Thermal imagining for hot spots
How would you know you have an earth fault?
Onboard we have alarms and a reading of how big our earth leak is. Some vessels will have earth fault lights that show there is a fault.
In some cases the breaker may trip, if this repeats its self multiple times, this could indicate an earth fault.
Describe your main electrical system?
Onboard we have the MSB and ESB. Our vessels can take upto 318amp, 400v and 50hzs via shore power
Our generators are 250kw, 400v, 50hz, 450amp each, we have 2.
The emergency generator 106 kW
What purpose does the neutral leg have in a 4 wire system?
In a 3-phase 4-wire system, which typically consists of three hot wires (phases) and one neutral wire, the neutral helps balance the load between the phases. this providing a factor of safety.
How is an appliance earthed with a 3 phase 4 wire system?
In addition to the three phase wires (L1, L2, L3) and the neutral wire (N), there is often a separate earth (ground) wire. This earth wire is connected to the metal parts of the appliance and to the ground connection in the electrical panel or distribution board.
Why do we use an isolation transformer?
It will isolate the vessels 400v power supply from the shore powers 400v supply. This removing any risk of galvanic corrosion occurring
What is the acceptable limit for ground faults?
Onboard moonsand we have two alarm limits, high is set at 7amps and high high is at 10amps. But we keep a good practice of trying to keep it at zero or as close to it as possible.
What is a continuity test?
A continuity test is a basic electrical test used to determine if there is a complete (unbroken) path for current to flow in a circuit or component. It checks whether an electrical circuit can carry current by measuring the resistance between two points.
What electrical maintenance do we carry out on board?
- Visual inspections
- Checking connections
- Cleaning cabinet filters
- Checking calibration
- Testing preferential trips, reverse power, over speed, under and over voltage
- Battery tests
- Inspect and cleaning windings
- Lighting inspections
- AVIT inspections
- Alarm monitoring
- Ground faults
How would you trace an earth fault?
- Isolate a distribution board and see if it disappears
- bring everything on the board back online one at a time till it returns
- Split that system in half, repeating till the component is found
- Rectify the problem
- Record findings into PMS
Why is it important to fix earth faults quickly?
- Risk of electric shock
- Fire risk
- Preventing damage
- Maintaining system reliability and performance
How to test reverse power trip and why?
Reverse power trip can be tested by increasing the load on one generator and decreasing on the other until the generator starts to become a motor
What is the load of your bowthruster motor, how is it run?
150kw, 400v, 50hz by a slip ring motor/ squirrel cage motor. A Variable frequency drive is installed to allow the motor to gradually increase and decrees
How does a frequency drive work? How do you calculate frequency?
An electronic device that controls the speed and torque of an electric motor by varying the frequency and voltage supplied to the motor.
- AC converts to DC power using the rectifier
- Capacitors then smooth out the DC power
- The smoothed DC is then converted back to AC power with a variable frequency and voltage using an inverter
- The control circuit then adjusts the values as needed
- The motor will now spin at a speed until changed
Frequency Counter: Use a frequency counter, an instrument that directly measures the frequency of an electrical signal. This is the most straightforward method and provides an accurate reading.
Safety devices fitted to bow thruster / board?
- Circuit breaker
- Thermal overload relays
- Temperature sensors
- Oil level sensors
- Interlocking systems
- Emergency stop
- Ground fault protection
Direct online starter / Star Delta start, what are the safeties, how do they work?
DOC
- Circuit breakers
- Thermal overload relays
- Emergency stop
- Under voltage protection
When the start button is pressed, the control circuit energizes the contactor, closing the main contacts and supplying full voltage to the motor. Safety devices like thermal overload relays continuously monitor the current and temperature.
Star-Delta Starter
- Time relay
- Circuit breaker
- Thermal overload Rely
- Interlock system
- Emergency stop
- Under voltage protection
When the start button is pressed, the control circuit energizes the star contactor, connecting the motor windings in star configuration, which reduces the voltage and current. After a preset time, the timer relay switches to delta configuration by de-energizing the star contactor and energizing the delta contactor, applying full voltage to the motor.