40AO-9ZZ20 Loss of HVAC Flashcards
During 40AO-9ZZ20 Loss of HVAC, what are the major mitigating steps for Loss of Normal Chillers
- Attempt to restart Chillers
- Maintain WC < 50°F
- If unable to maintain < 50° CLOSE WCN-70 Radwaste and Control bldg isolation
During a loss of CEDMCS room cooling, what temperature would require a shutdown and why?
- > 104°F
- SCR breakdown may cause slipped/ dropped CEA
If cooling is lost to CEDMCS room, what actions are required?
- Limit CEA motion to only ASI control
- establish temporary ventillation
- Shutdown if > 104°F
What may occur if CEDMCS cabinet fans are lost?
What actions are taken to mitigate?
- Spurious CEA malfunctions
- Limit CEA motion to ASI control
- CEDMCS not in AS
- Open cabinet doors
- Temporary ventillation
When will CEDM coil damage occur if CTMT CEDM cooling is lost?
- RCS ≥ 300°F
- 40 minutes
If CNTMT CEDM cooling is lost how long do you have to restore cooling?
What is required if cooling cannot be restored?
- Restore in 10 minutes OR start rapid shutdown
- Secure S/D if restored in 40 minutes
- Trip Rx before 40 minutes
- Cooldown to < 300 in 4 hours
During a loss of cooling to AF pump rooms:
When is temporary ventilation required?
What is the analyzed temperature?
What is the qualified temperature?
- 101°F temporary ventilation
- < 104°F analyzed**
- 150°F AFA qualified
- 156°F AFB qualified
During a loss of CH pump room cooler, How long can CH pumps run without cooling?
when would you consider stopping a CH pump?
- 100 hours
- > 120°F
If Control Building HVAC is lost, when would you de-energize BOP-ESFAS and why?
- > 119°F in MCR
- simultaneous failure of BOTH load sequencers
- Causes continuous load shed
If Control Building HVAC is lost, when would you be required to down power PMS?
- > 80°F in computer room
What is the CR air temperature limit?
- 80°F
- Restore in 30 days
What is the concern with a loss of ESF Equipment Room Essential HVAC?
- 1 Fan cools 2 inverters
- LCO 3.8.7 entry and restore in 1 hour
(LCO may be exited with temporary ventilation)
What is the most limiting analyzed acceptable temperature limit for DC equipment, battery rooms and class switchgear?
- 120°F
- 30 days
What is the electrical penetration room temperature limit?
- 101°F
- LCO entry and temporary ventilation required
What is the most limiting analyzed acceptable temperature limit for electrical pen rooms?
- 122°F
- 30 days