40AO-9ZZ06 Loss of IA Flashcards
What is the entry criteria for Loss of IA
- No IA compressors running
- All IA compressors with lowering/no pressure
- “IA Header Press Lo Press” alarm (95psig)
- “IA system trouble” alarm (filter dp, dryer trouble, compressor trouble)
- “IA N2 backup vlv Open” alarm (85psig)
- Loss of IA press in 1 or more headers
During a loss of IA what is Rx trip criteria
- Unstable plant conditions (CRS says so)
- Unable to restore IA to CNTMT
- RCP B/O is being directed to RDT
- Prior to isolating air to CNTMT or Aux Bldg
During a loss of IA:
What pressure will affect plant power production stability?
What pressure is the most unstable
- 70 psig
- 40 psig (CVCS, spray, RDT affected)
On a loss of IA what action do you take if LD, Seal B/O, or SGBD isolation vlv fails closed
- Take HS to close
- Prevent uncontrolled operation when IA restored
What is the Power supply to IAU-UV-2
PKA
How is the RDT affected by a loss of IA
- Seal B/O directed to RDT
- RDT CANNOT be pumped
During a Loss of IA when would you run air dryers in parallel
- Large DP between air receiver and downstream of dryer
- 1 dryer in svc and stby is available
- IA press is 80psig or greater
When does N2 backup automatically align to IA hdr?
When does it reclose?
- 85 psig
- 105 psig
What is the concern if N2 is supplying the IA header?
What actions are required
- O2 deficient atmosphere in Aux Bldg below 100’
- Start at least 1 FBEV AFU aligned to Aux Bldg
During a loss of IA when would you isolate IA to fuel pool gates
- 28 psig or lower, Isolate IA
During a loss of IA at what pressure do CD pump mini-flow vlv fail and to what position?
- 80psig
- Fail OPEN
During a loss of IA at what pressure do HD pump disch vlv fail and to what position
- 80 psig
- Fails CLOSED
During a loss of IA at what pressure do HDT High lvl dump fail and to what position
- 80 psig
- Fail OPEN
During a loss of IA at what pressure does SBCV’s fail and to what position
- 80 psig
- Fails CLOSED
During a loss of IA at what pressure do MFP mini-flows fail and to what position?
- 75-65 psig
- Fail OPEN