40AO-9ZZ09 RPCB LOFP Flashcards

1
Q

What are the entry conditions for RPCB LOFP?

A
  • Alarms indicating LOFP

- Unexplained drop in FWP disch press or speed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are RPCB LOFP Exit criteria?

A

Condition 1:

  • Power stable, going to raise power
  • CEA > TIL
  • AOP direct to ZZ05

Condition 2:

  • Power stable, maintain power
  • CEA > TIL
  • AOP directs to ZZ05

Condition 3:

  • Power Stable
  • CEA > TIL
  • CEA overlap restored
  • AOP direct to ZZ04 or ZZ07 (change modes)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

During Reactor Power Cutback (LOFP) 40AO-9ZZ09 what is Rx Trip Criteria?

A
  • ≥ 74% MFP trips and RPCB fails to actuate (Auto and Man.)
  • CEA deviates from subgroup >6.6” and any reg group < TIL
  • Both MFP Trip
  • SGWL approaches trip setpoints (≤44.2% NR, ≥91% WR)
  • CPC ASI (pt 187) ±0.45 trending 0.5
  • Turbine Load ≤ 410 MW and vacuum >5” HgA or >4”HgA for 1 hour
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the MFP trips?

A

Overspeed - > 6350 RPM
Low Suction Press - < 245 psig (B 10 sec A 15 sec)
High disch. Press - > 1750 psig
Low Vacuum - > 13.5” HgA
Low Control Oil Press. - < 75 psig
High Thrust Brng press - > 40 psig
Low BRNG Oil Press. - < 4 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How does a Loss of NNN-D15 affect the MFP’s?

A
  • A MFP controls Fail CLOSED

- No auto RPCB

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How does a Loss of NNN-D16 affect the MFP’s?

A
  • B MFP control vlvs Fail CLOSED
  • No Auto RPCB
  • Both MFP’s lose stop vlv Indication
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How is RPCB LOFP different than RPCB LLR?

What is the concern with incorrect Manual actuation during RPCB LOFP?

A
  • Quick Open Block sent to SBCS for LOFP

- MAN LLR during a LOFP results in HIGHER steam Demand with LOWER feed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How do you clear a SETBACK signal following a RPCB?

A
  • Cleared once input from RPCS is no longer present (Auto Act. OOS adn Test/Reset)
  • Load Limit Pot turned CCW until clear
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

At what power do you remove RPCB from Service?

A

< 70%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

If a RPCB LOFP fails to auto actuate what actions are you allowed to perform manually?

A

≥ 74%

  • Press LOFP and Drop Subgroup buttons
  • Trip Rx if both auto and manual fail

<74 %

  • Manually insert CEA to match Rx/Turbine power
  • If setback - Runback has not lowered turbine load, manually adjust pot unitl ≤ 65% (890MW)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Following a RPCB how long is the allowance for LCO 3.1.7 PDIL’s?

A
  • PDIL may be violated for 2 HOURS following RPCB

- Tracking still required

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Following a RPCB when restoring CEA overlap, what group is adjusted to what position?

A

If Reg Group 3 is > 95”

  • Use MG
  • Withdraw Reg Group 4 to 95” BELOW REG GROUP 3
  • Use 10” pulls
  • Wait 1 minute between pulls
  • If power ↑ > 1% adjust next pull to be < 1%
  • Maintain ±3°F Tavg/ref
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Following a RPCB if power CANNOT be stabilized due to Xe or it is desired to reduce power, at what power level do you stabilize at?

Why?

A

< 12%

  • CPC canned value
  • ↓ condenser tube errosion
  • DCCV swapover
  • Tilt and ASI LCO not applicable < 20%