40AO-9ZZ07 Loss of Condenser Vacuum Flashcards

1
Q

At what condenser pressures does the D AR pump AUTO start?

A

A - ≥4.2” HgA
B - ≥4.8” HgA
C - ≥5.3” HgA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

At what condenser pressure does the SBCS Cond Interlock come in?

A
  • ≥5.5” HgA

- 2/3 shell logic

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How is the SBCS condenser interlock reset?

A
  • Condenser press <5” HgA

- Taking Emergency-Off-Reset to reset

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What condenser pressure causes a Turbine Trip?

A
  • ≥7.5” HgA

- 2/3 logic

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What condenser pressure causes a MFP trip?

A
  • ≥13.5” HgA

- 2/2 logic (turbine exhaust)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

During 40AO-9ZZ07 Loss of Condenser Vacuum, what is Rx Trip Criteria?

A

Generator Online

  • > 7” HgA and ↑
  • <410 MW and >5” HgA
  • <410 MW and >4” HgA for >1 hr
  • < 70 MW and load reduction needed

Generator Offline

  • Prx >12% and SBCS interlock come in
  • Prx 3-12% and >7” HgA ↑ AND, MFP tripped
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the control power for Cooling Tower Fans?

A

NKN-D19

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the required power reduction if BOTH CW pumps in a loop are lost?

A

Reduce power to ≤ 40%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

During 40AO-9ZZ07 Loss of Condenser Vacuum, does the D AR pump need to be running to open shell suctions?

A
  • NO

- Opening all D Suctions x-ties suctions to allow other AR pumps to assist 1 shell

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What Hotwell Level do we maintain and why?

A
  • ≥ 41”

- HDP trip lowers level ≈ 10”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the concern with hotwell m/u during 40AO-9ZZ07 Loss of Condenser Vacuum

A
  • M/U uses vacuum drag, as vacuum ↓ M/U is affected
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

During 40AO-9ZZ07 Loss of Condenser Vacuum, what is the minimum power reduction?
How is it performed?

A
  • 5% (Mentor Guidance 10% over 10 minutes)
  • Allow CEA insert automatically
  • Tavg/ref target +3-3.5°F
  • Boration allowed if CEA’s in manual
  • Do NOT exceed Lpzr 56%
  • Maintain Tavg/ref ±5°F, CEDMCS out of Auto and use 1007/8 if cant maintain
  • Tc ±3°F of program band
How well did you know this?
1
Not at all
2
3
4
5
Perfectly