40AO-9ZZ07 Loss of Condenser Vacuum Flashcards
At what condenser pressures does the D AR pump AUTO start?
A - ≥4.2” HgA
B - ≥4.8” HgA
C - ≥5.3” HgA
At what condenser pressure does the SBCS Cond Interlock come in?
- ≥5.5” HgA
- 2/3 shell logic
How is the SBCS condenser interlock reset?
- Condenser press <5” HgA
- Taking Emergency-Off-Reset to reset
What condenser pressure causes a Turbine Trip?
- ≥7.5” HgA
- 2/3 logic
What condenser pressure causes a MFP trip?
- ≥13.5” HgA
- 2/2 logic (turbine exhaust)
During 40AO-9ZZ07 Loss of Condenser Vacuum, what is Rx Trip Criteria?
Generator Online
- > 7” HgA and ↑
- <410 MW and >5” HgA
- <410 MW and >4” HgA for >1 hr
- < 70 MW and load reduction needed
Generator Offline
- Prx >12% and SBCS interlock come in
- Prx 3-12% and >7” HgA ↑ AND, MFP tripped
What is the control power for Cooling Tower Fans?
NKN-D19
What is the required power reduction if BOTH CW pumps in a loop are lost?
Reduce power to ≤ 40%
During 40AO-9ZZ07 Loss of Condenser Vacuum, does the D AR pump need to be running to open shell suctions?
- NO
- Opening all D Suctions x-ties suctions to allow other AR pumps to assist 1 shell
What Hotwell Level do we maintain and why?
- ≥ 41”
- HDP trip lowers level ≈ 10”
What is the concern with hotwell m/u during 40AO-9ZZ07 Loss of Condenser Vacuum
- M/U uses vacuum drag, as vacuum ↓ M/U is affected
During 40AO-9ZZ07 Loss of Condenser Vacuum, what is the minimum power reduction?
How is it performed?
- 5% (Mentor Guidance 10% over 10 minutes)
- Allow CEA insert automatically
- Tavg/ref target +3-3.5°F
- Boration allowed if CEA’s in manual
- Do NOT exceed Lpzr 56%
- Maintain Tavg/ref ±5°F, CEDMCS out of Auto and use 1007/8 if cant maintain
- Tc ±3°F of program band