40AO-9ZZ15 Loss of Annunciators Flashcards
1
Q
What are entry conditions for 40AO-9ZZ15 Loss of Annunciators?
A
- Annunciator check fails
- All windows lit for no reason
- Invalid alarms on panel
- Alarm windows dimly lit
- All windows flash bright and extinguish
- No alarm when there should be
- PWR OR GND TRBL alarm
2
Q
What are the power supplies for the Annunciator Logic Cabinets?
A
Rule of 58
Cabinet 1:
- Norm - NKN-D43
- Alt. - NNN-D15
Cabinet 2:
- Norm - NKN-D42
- Alt. - NNN-D16
3
Q
How are the units affected by a loss of NKN-M45 with a SIAS?
A
- U1/2 - Loss of ALL annunciators
- U3 - Loss of HALF annunciators
- U3 NNN-D16 B/U power is class vs SIAS L/S
4
Q
Are the Annunciator Logic Cabinets inverters NORMAL seeking or POWER seeking?
A
- Normal seeking
5
Q
What action during 40AO-9ZZ15 Loss of Annunciators could provide operators with AUDIBLE alarm indications?
A
- Ensure PC audible alarms are turned ON
6
Q
What action during 40AO-9ZZ15 Loss of Annunciators is required if PC is NOT available?
A
- Stabilize plant
- Stop unnecessary evolutions
- COLSS PC ALARM response
- Contact OCS
7
Q
During 40AO-9ZZ15 Loss of Annunciators, when would it be required to Notify Unit Ops Manager?
A
- ≥ 4 annunciator panels are non-functional