40AO-9ZZ03 Loss of Cooling Water Flashcards

1
Q

When does the PW pump Auto start

A
  • 40 psig discharge pressure
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is required if PW is NOT restored

A

Trip the Reactor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is required if TC is NOT restored

A

Trip the Reactor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How do we minimize loads on TC

A
  • Stop SGBD
  • Align AFW
  • Trip both MFP’s
  • Stop HDP’s
  • Stop CD pumps (MFP’s not running)
  • Stop Service air compressor/ IA compressor
  • Use SBCV’s 1007/8
  • Break vacuum when MT<1200 rpm
  • Stop CW pumps
  • Stop EHC
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How long do we have to restore NC flow to RCP’s

A
  • 3 minutes without seal injection

- 10 minutes with seal injection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is required if unable to restore cooling to RCP’s

A
  • Trip the Rx
  • Stop all RCP’s
  • Isolate Seal Bleedoff
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the actions for a NC leak inside containment

A
  • Close NC CIV’s BEFORE TRIP
  • Trip the Rx
  • Stop RCP’s
  • Isolate Bleedoff
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

When cross connecting EW to NC how far do you throttle SDC HX outlet vlv

A
  • RCP low NC flow alarm clears (>450 gpm)

- EW system flow <8500 gpm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the TCA for a loss of cooling to a RCP

A

30 Minutes

  • Reduce power or isolate cooling water and shutdown RCP
  • FSAR time requirement
How well did you know this?