40AO-9ZZ13 Loss of Class Instrument and Control Power (PN/PK) Flashcards

1
Q

During 40AO-9ZZ13 Loss of Class Instrument and Control Power (PN/PK) what is Rx trip criteria?

A
  • Lrdt ≥ 75% unable to restore

- Prdt ≥ 5 psig unable to restore

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How are the DG affected by a loss of PK

A
  • Trips if running
  • Cannot be started
  • DG output brkr loses control power, must be locally opened
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How is AF affected by a loss of PKA-M41/ PKA-D21

A
  • AFA trips on overspeed
  • AFA MOV’s fail AS-IS
  • AFA steam supply vlvs may open when power restored
  • AFN losses Control power (swap to Battery Charger)
  • Train A DCIV’s Fail OPEN with loss of indication
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How is AF affected by a loss of PKB-M42/ PKB-D22

A
  • AFB loses control power (close brkr locally)

- Train B DCIV’s fail OPEN and indication lost

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How are the ADV’s affected by a loss of PK or PN

A
  • Any PK 2 ADV’s fail CLOSED, permissive lost
  • PNA/PNB 2 ADV’s fail CLOSED
  • PNC/PND no effect
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How are MSIV’s/ FWIV’s affected by a loss of PK

A
  • Normally aligned directly to battery
  • Alternate source PKA/B-M41/42
  • Fast Close on loss of power
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

How is PPCS/PLCS/CVCS affected by a loss of PN?

A
  • PZR LT’s fail low: CH pumps, LD flow, PZR Htrs affected if selected)
  • PNA - BAMPS’s Trip due to RWT-LT-200 failing LOW
  • PNB - LD isolates CHB-515 closes due to TT losing power
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How is BOP-ESFAS affected by a loss of PK/PN?

A
  • Power auctioneered from PK & PN remains functional with one
  • PNA/B - RU monitors lose power CREFES/ CPIAS/ FBEVAS auto actuate and cross channel
  • Both PK/PN - disabled **when reenergized load shed and resequence occurs
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How is CEDMCS affected by a loss of PNA or PNB?

A
  • 2 RTB open (loss of RPS logic)

- CEAC 1 lost on all CPC channels

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How is CEDMCS affected by a loss of PNC?

A
  • A and C RTB’s open
  • “Pacman” on mimic board
  • Pulse counters zeroed for CEA with rod bottom lights
  • CEDMCS cabinet C5 loses power
  • Subgroup logic prevents motion for ALL subgroups in AS, MS, MG
  • Can only move unaffected CEA in MI
  • Emergency Boration required
  • LCO 3.0.3
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

How is CEDMCS affected by a loss of PND?

A
  • B and D RTB’s open
  • “Anti-Pacman” on mimic board
  • Pulse counters zeroed for CEA’s with rod bottom lights
  • CEDMCS cabinet C6 loses power
  • Subgroup logic prevents moving any subgroup in AS, MS, MG
  • Can only move unaffected CEA’s in MI
  • Emergency boration required
  • LCO 3.0.3
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How is PPS (RPS-ESFAS) affected by a loss of PN?

What action is required?

A
  • Parameters that actuate on low parameter will be tripped
  • Parameters that actuate on high parameter will NOT trip
  • Low DNBR and High LPD trip due to CPC loss of power
  • Bypass system remains functional (auctioneered power)
  • 3/6 matrices lose half of their power RTB’s A&C or B&D will open
  • Bypass ALL associated PPS trip bistables NOT bypassed on another channel
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How is PPS (RPS-ESFAS) affected by a loss of PK?

A
  • Associated channel RTB opens (UV coil)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Which class instrument and control power, if lost, would require entry into LCO 3.0.3?

A

PKB - RCS leakage detection: RU-1 loses power, Sump B CIV fail closed

PNC/D - CEA position indicators, need 2/3 position indicators channels operable

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What procedure would you use to address a Loss of PK Battery Charger

A
  • Alarm Response

- NOT AOP unless board is also lost

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What additional action must also be done if a PK battery charger is lost

A
  • Electricians perform Weekly battery ST - W/in 2 HOURS
  • OPS perform disch. Eval.
  • Place Spare Charger in SVC