40AO-9ZZ13 Loss of Class Instrument and Control Power (PN/PK) Flashcards
During 40AO-9ZZ13 Loss of Class Instrument and Control Power (PN/PK) what is Rx trip criteria?
- Lrdt ≥ 75% unable to restore
- Prdt ≥ 5 psig unable to restore
How are the DG affected by a loss of PK
- Trips if running
- Cannot be started
- DG output brkr loses control power, must be locally opened
How is AF affected by a loss of PKA-M41/ PKA-D21
- AFA trips on overspeed
- AFA MOV’s fail AS-IS
- AFA steam supply vlvs may open when power restored
- AFN losses Control power (swap to Battery Charger)
- Train A DCIV’s Fail OPEN with loss of indication
How is AF affected by a loss of PKB-M42/ PKB-D22
- AFB loses control power (close brkr locally)
- Train B DCIV’s fail OPEN and indication lost
How are the ADV’s affected by a loss of PK or PN
- Any PK 2 ADV’s fail CLOSED, permissive lost
- PNA/PNB 2 ADV’s fail CLOSED
- PNC/PND no effect
How are MSIV’s/ FWIV’s affected by a loss of PK
- Normally aligned directly to battery
- Alternate source PKA/B-M41/42
- Fast Close on loss of power
How is PPCS/PLCS/CVCS affected by a loss of PN?
- PZR LT’s fail low: CH pumps, LD flow, PZR Htrs affected if selected)
- PNA - BAMPS’s Trip due to RWT-LT-200 failing LOW
- PNB - LD isolates CHB-515 closes due to TT losing power
How is BOP-ESFAS affected by a loss of PK/PN?
- Power auctioneered from PK & PN remains functional with one
- PNA/B - RU monitors lose power CREFES/ CPIAS/ FBEVAS auto actuate and cross channel
- Both PK/PN - disabled **when reenergized load shed and resequence occurs
How is CEDMCS affected by a loss of PNA or PNB?
- 2 RTB open (loss of RPS logic)
- CEAC 1 lost on all CPC channels
How is CEDMCS affected by a loss of PNC?
- A and C RTB’s open
- “Pacman” on mimic board
- Pulse counters zeroed for CEA with rod bottom lights
- CEDMCS cabinet C5 loses power
- Subgroup logic prevents motion for ALL subgroups in AS, MS, MG
- Can only move unaffected CEA in MI
- Emergency Boration required
- LCO 3.0.3
How is CEDMCS affected by a loss of PND?
- B and D RTB’s open
- “Anti-Pacman” on mimic board
- Pulse counters zeroed for CEA’s with rod bottom lights
- CEDMCS cabinet C6 loses power
- Subgroup logic prevents moving any subgroup in AS, MS, MG
- Can only move unaffected CEA’s in MI
- Emergency boration required
- LCO 3.0.3
How is PPS (RPS-ESFAS) affected by a loss of PN?
What action is required?
- Parameters that actuate on low parameter will be tripped
- Parameters that actuate on high parameter will NOT trip
- Low DNBR and High LPD trip due to CPC loss of power
- Bypass system remains functional (auctioneered power)
- 3/6 matrices lose half of their power RTB’s A&C or B&D will open
- Bypass ALL associated PPS trip bistables NOT bypassed on another channel
How is PPS (RPS-ESFAS) affected by a loss of PK?
- Associated channel RTB opens (UV coil)
Which class instrument and control power, if lost, would require entry into LCO 3.0.3?
PKB - RCS leakage detection: RU-1 loses power, Sump B CIV fail closed
PNC/D - CEA position indicators, need 2/3 position indicators channels operable
What procedure would you use to address a Loss of PK Battery Charger
- Alarm Response
- NOT AOP unless board is also lost