TB 8 Electrical Hazards Flashcards
TB 8 Electrical Hazards
electrical accidents in the United States account for over 700 deaths a year and OSHA statistics indicate that electrocution accounts for 12% of worker deaths annually. NIOSH statistics also document that over the last 20 years, electrocutions to first responders have resulted in more than 25 deaths in the fire service.
reference
TB 8 Electrical Hazards
The Los Angeles Fire Department (LAFD) resources respond to over 3000 electrocutions, wires down, and other electrical emergencies annually.
reference
TB 8 Electrical Hazards
AMPS- Current flow, or electron flow,
Current flows from points of high voltage to points of low voltage on the surface of a conductor and is measured in Amperes.
The flow of electricity maybe compared with the flow of
water through a fire hose. Quantity of electricity is expressed in Amperes (amps); conversely, water
is measured in gallon per minute (gpm).
reference
TB 8 Electrical Hazards
VOLTS- Voltage is the difference in electrical potential between two points in a circuit.
Electrical pressure is measured in volts, while the comparable term in water hydraulics would be pounds per square inch (psi).
reference
TB 8 Electrical Hazards
KILOVOLTS- The measure of 1000 volts.
reference
TB 8 Electrical Hazards
OHMS- Resistance determines how much current will flow through a component.
The resistance to a flow of water through a hose would be termed friction loss and would be measured in pounds per square inch.
reference
TB 8 Electrical Hazards
WATTS- Power is the amount of current times the voltage level at a given point measured in wattage or watts. (Watts = amps x volts.)
reference
TB 8 Electrical Hazards
Even overhead communication cable normally found on the lowest level of a power pole can be energized with up to ____ volts.
50
TB 8 Electrical Hazards
Streetlights can be fed from conductors carrying ___ - ___ volts or more.
120-6150
TB 8 Electrical Hazards
Watts = amps x volts
Amps = watts x volts
Volts = watts x amps
reference
TB 8 Electrical Hazards
Maintain a safe distance from transmission towers: a minimum of ___ feet should be adhered to.
35
TB 155
Maintain a 35’ distance from transmission LINES
Spot fires or low ground fires can be fought with hose lines if heavy smoke or flame is not within 100’ of the power lines
TB 8 Electrical Hazards
Maintain clearance a minimum of ___ feet beyond the outermost wire of electrical transmission lines.
100
TB 155
Maintain a 35’ distance from transmission LINES
Spot fires or low ground fires can be fought with hose lines if heavy smoke or flame is not within 100’ of the power lines
TB 8 Electrical Hazards
ELECTRICITY FIRE HYDRAULICS
Conductor = Hose
Current = Water
Voltage = Pressure
Amperes = Gallons per minute
Ohms = Friction Loss
reference
TB 8 Electrical Hazards
Getting electricity to the consumer can be broken down into three systems:
Generation,
Transmission
Distribution System.
reference
TB 8 Electrical Hazards
Transmission lines are used to carry high voltage electricity the long distances from generating plants to distribution stations.
reference
TB 8 Electrical Hazards
Voltages on transmission lines range from 69kv to over 1000kv. Most of the transmission lines coming into Los Angeles are ____ kv, but many lines are higher than that. All voltages above 69kv are referred to as transmission voltages.
230kv
TB 8 Electrical Hazards
Strings of insulators on transmission towers can range from ___ to ___ feet long depending on the voltage they are trying to hold back from contacting the towers that support them.
3 to 20
TB 8 Electrical Hazards
The component of the electric system that delivers electrical energy to the consumer or residence
consists of distribution stations and distribution lines.
This system works by stepping down the voltage while
proportionately stepping up the amps with transformers the same way the voltage was stepped up in the generation system at the beginning of the circuit.
reference
TB 8 Electrical Hazards
There are over 150 distribution stations where the electricity is received at ___kv and stepped down to ___ kv. This is the voltage known as primary circuit voltage. The ___kv primary lines run from a distribution station to the neighborhood that it feeds.
- 5
- 8
- 8
TB 8 Electrical Hazards
The LADWP has many consumers that are connected to the grid at high-voltage(any voltage 600 volts and over). The most common are large commercial or industrial consumers such as hospitals, malls, high-rise buildings, metro rail stations and large complexes, which are connected at 34.5kv.
reference
TB 8 Electrical Hazards
Transformers are designed to reduce the voltage in the system to a voltage usable by the consumer.
reference
TB 8 Electrical Hazards
HIGH-VOLTAGE CAPACITOR
A capacitor is a type of electronic component which passively acts as a form of conductor.
When a charge of opposing currents is run through the device then a field is generated in which energy is stored. This energy can then be tapped through various means, allowing it to run devices which require electricity to work.
High-voltage capacitors have been known to retain a deadly electrical charge even weeks after power has been removed from the circuit.
reference
TB 8 Electrical Hazards
Overhead Transformers - Pole-mounted transformers are the most common distribution transformer. They are installed on the ___kv circuits to step the voltage down to ___ volts for most residential consumers.
4.8kv
120/240
TB 8 Electrical Hazards
Pad-Mounted Transformers - Transformers for subsurface electrical are mounted above ground on
concrete bases called pad-mounted transformers. These large boxes are connected to 4.8kv circuits
reference
TB 8 Electrical Hazards
Conductors – The conductors are materials that allow an electric current to flow through them easily.
reference
TB 8 Electrical Hazards
Insulator – Insulators are appliances which will prevent the flow of electricity and provides support to the conductor. They are most commonly made of glass or porcelain.
reference
TB 8 Electrical Hazards
Service Connection – The wires that connect the customer or home to the secondary transformer and may be high or low voltage.
reference