TB 62 2-INCH HIGH-RISE HOSE SYSTEMS Flashcards

1
Q

TB 62 2-INCH HIGH-RISE HOSE

This hose is of a single jacket construction utilizing nitrile rubber impregnated synthetic yarn as the cord material. It comes in 50 foot lengths with 1-1/2” couplings and is ribbed to reduce wear and increase grip. The shoulder of the couplings are tapered to reduce snagging

A

reference

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

TB 62 2-INCH HIGH-RISE HOSE

Under pressure, the hose can be bent to within ___ inches before it will kink.

A

12

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

TB 62 2-INCH HIGH-RISE HOSE

Nozzle Pressure -

GPM -

Friction Loss 100’ -

A

75

200

35

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

TB 62 2-INCH HIGH-RISE HOSE

To secure the hose pack, place a strap about ____-inches above the bottom of the pack on each side.

A

8

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

TB 62 2-INCH HIGH-RISE HOSE

packs will weigh ___ pounds

Single Layer Pack
40” tall x 22” wide

Double layer pack
32” tall x 16” wide

A

38

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

TB 62 2-INCH HIGH-RISE HOSE

loaded. If the orifice plate has not been removed, open the valve fully. If the orifice plate has been removed, the outlet should be opened one and one-half turns, then adjusted from there.

A

reference

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

TB 62 2-INCH HIGH-RISE HOSE

This system utilizes a Pressure Reducing Valve (PRV) when the pressure at the outlet exceeds 150 psi. Therefore, it is possible in new construction to encounter orifice plates on the upper floors where the system pressure falls below 150 psi. This will typically be the top six to eight floors.

A

reference

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

TB 62 2-INCH HIGH-RISE HOSE

The service test pressure for this hose is 300 psi.

A

reference

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

TB 62 2-INCH HIGH-RISE HOSE

Removal of the orifice plate is recommended in order to get the maximum flow from the outlet.

Failure to do so will restrict the flow from the outlet to ___ gpm at a minimum of ___ psi residual pressure.

A

200

50

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

TB 62 2-INCH HIGH-RISE HOSE

Place the female coupling of the first section of hose about ____-inches below the gauge of the bottle. Attach the reducer to the female coupling.

A

ten

How well did you know this?
1
Not at all
2
3
4
5
Perfectly