Which NN buses are grounded and which are ungrounded?
NNN-D11 and NNN-D12 are ungrounded
NNN-D15 and NNN-D16 are grounded
What are the normal and backup power supplies for NNN-D11 and NNN-D12?
Normal: Non-Class MCC through a Voltage Regulator
Backup: Class MCC
What are the normal and backup power supplies for NNN-D15 and NNN-D16?
Normal: Non-Class MCC through a Voltage Regulator
Backup: SIAS Load Shed Panel
- Except D16 for Unit 3 which is a Class MCC
What is the status of NNN-D15/D16 in Units 2 and 3 after a LOOP? LOOP and SIAS (after one minute)?
Unit 2&3 LOOP both panels energized (from SIAS load shed)
Unit 2 LOOP&SIAS NNN-D15/D16 de-energized
Unit 3 LOOP&SIAS NNN-D15 de-energized, NNN-D16 is energized
What is the normal source of supply power to NNN-D11?
non-vital MCC via a voltage regulating transformer