Essential Chilled Water (EC) Flashcards
1
Q
Per LCO 3.7.10, when are BOTH trains of Essential Chilled Water required?
A
LCO 3.7.10 Two EC trains shall be OPERABLE
APPLICABILITY: MODES 1, 2, 3, and 4.
2
Q
What is the makeup to the Essential Chilled Water surge tank
A
- Demineralized Water (DW) is normal makeup water to the Expansion Tank
- CST (CT) (backup)
- Fire Protection
3
Q
What happens to the EC chiller on a loss of EW?
A
- Condenser high refrigerant pressure (actuates on loss of EW to the condenser)
o Does NOT trip on low EW flow
4
Q
What is the purpose of the Hot Gas Bypass line?
A
Hot Gas Bypass
* Prevent surging during low load conditions. (Compressor can’t pump the gas well).
* Hot gas bypass re-directs some of the flow back to the cooler.
5
Q
What is the purpose of the Refrigerant Head Pressure Control Valve (located on the EW outlet from the condenser)?
A
This valve is necessary to prevent “stacking” which occurs during cold or low load conditions.