Boric Acid Concentrator (BAC) Flashcards
1
Q
The BAC CONC TRBL alarms in the control room…
A
…with no time delay.
2
Q
The BAC HUT alarm set points are…
A
hi-hi level alarm at 42’
high level alarm at 17’
low level alarm at 4’
low-low level alarm at 28” (HUT pump trip)
3
Q
When in the normal position, which signals will stop the holdup pump:
A
- Lo-lo holdup tank level (28”)
- Hi-Hi boric acid concentrator flash tank level.
- Other holdup tank pump starts.
- Diversion of letdown flow CH-500 to the pre-holdup ion exchanger when the holdup tank contents are being re-purified (CH-V686 open).
- Electrical protection or loss of control power.
4
Q
A BAC steam vapor release to __(1)__ and requires a __(2)__ due to __(3)__
A
(1) the plant vent
(2) a Radioactive Effluents Discharge Permit
(3) Steam vapor contains tritium as part of the water molecule
5
Q
What cools the BAC concentrates?
A
NC - Nuclear Cooling Water